Baso L62GB Скачать руководство пользователя страница 3

 

L62GB BASO Safety Shutoff Device Installation Instructions    

3

 

7.  Check the millivoltage output of the thermocouple 

and milliampere dropout range at the BASO power 
unit terminal to see that they meet the values in 
Table 1 and Table 2. Step-by-step procedures for 
these checks are included with the Y99AB BASO 
Test Kit. 

8.  Relight the pilot. 

9.  Observe at least three complete operating cycles 

to make sure that all components are functioning 
correctly. 

10.  Reset the thermostat to a normal temperature 

setting before leaving the installation. 

Repairs and Replacement 

Field repairs 

must not

 be made to the L62GB safety 

shutoff device. If the thermocouple meets the output 
listed in Table 1 and the valve does not function, 
replace the entire device. Any attempt to repair this 
assembly voids the manufacturer’s warranty. For a 
replacement safety shutoff device, contact the nearest 
BASO Gas Productsdistributor. 

Check the millivoltage output of the thermocouple and 
milliampere dropout range at the BASO power unit 
terminal to see that they meet the values in Table 1 
and Table 2. If the readings do not meet these values, 
replace the thermocouple and/or the safety shutoff 
device. 

Table 1: Thermocouple Output 

Thermocouple mV 

Range 

Lead Type 

Turn 

Down 

 

Normal 

Not Less 

Than 

K15 

4 mV 

20-28 

15 

K16 

4 mV 

25-35 

17 

K19 

4 mV 

25-35 

17 

 

Table 2: L62GB Dropout Range 

mA Range of Power Unit Assembly 

Low High 

100 300 

 

Pilot Servicing 

If pilot flame problems occur, check the following: 

 

If the pilot flame burns yellow, it may be due to dirt 
or lint covering the lower portion of the pilot 
burner. Remove dirt and lint using a soft brush or 
a vacuum cleaner. 

 

A flame approximately 0.5 in. (12.7 mm) high must 
surround the thermocouple tip (see Figure 2). 

 

Because this is an electrical connection, the 
thermocouple lead connection to the BASO power 
unit must be clean and free of grease. 

Approximately

1/2 in. (12.7 mm)

 

Figure 2: Flame Position 

Replacement Procedure 

!

  WARNING: Risk of Explosion or Fire. 

Shut off the gas supply at the main manual shutoff 
valve before installing or servicing the L62GB. 
Failure to shut off the gas supply can result in the 
release of gas during installation or servicing, which 
can lead to an explosion or fire, and may result in 
severe personal injury or death. 

 

!

  CAUTION:  Risk of Electrical Shock. 

Disconnect power supply before making electrical 
connections to avoid electrical shock.

 

 

!

  WARNING: Risk of Explosion, Fire, or 

Electric Shock. 

Label all wires before they are 

disconnected when replacing the L62GB. Wiring 
errors can cause improper or dangerous operation 
and may result in an electric shock, fire, or explosion 
leading to severe personal injury or death. 

When necessary, replace the safety shutoff device as 
follows: 

1.  Turn off power to the appliance. 

2.  Close the main manual shutoff valve and the pilot 

valve. 

3.  Disconnect the thermocouple lead from the safety 

shutoff device. 

4. Remove 

the 

cover. 

Содержание L62GB

Страница 1: ...and cause the safety switch to fail 4 Mount the L62GB in any convenient position using the mounting holes in the back of the case 5 Push the circuit wires through the conduit opening on the side of the device strip the ends of the wires just enough to put the bare wire under the terminal screws and attach them to the two wire terminals WARNING Risk of Explosion or Fire Do not attach both wires to ...

Страница 2: ...or fire and may result in severe personal injury or death Make sure all components are functioning properly by performing the following test 1 Test all joints and connections for leaks with a soap solution 2 Set the thermostat to the lowest setting 3 Close the main manual shutoff valve A valve and the pilot valve B valve see Figure 1 and wait at least 5 minutes for unburned gas to escape from the ...

Страница 3: ...ge mA Range of Power Unit Assembly Low High 100 300 Pilot Servicing If pilot flame problems occur check the following If the pilot flame burns yellow it may be due to dirt or lint covering the lower portion of the pilot burner Remove dirt and lint using a soft brush or a vacuum cleaner A flame approximately 0 5 in 12 7 mm high must surround the thermocouple tip see Figure 2 Because this is an elec...

Страница 4: ...e with the sheet metal screws provided The mounting plate is not required for exact replacements 1 2 4 5 3 Universal Mounting Plate BASO Power Unit Terminal Wire Terminals L62GB 3 Cover Figure 3 L62GB 3 Mounting 8 Mount the L62GB 3 using the holes in the universal mounting plate that match the mounting holes for the device being replaced see Table 3 Table 3 Mounting Guide Switch Being Replaced Use...

Страница 5: ... Performance specifications are nominal and conform to acceptable industry standards All agency certification of BASO products is performed under dry and controlled indoor environmental conditions Use of BASO products beyond these conditions is not recommended and may void the warranty Product must be protected if exposed to water dripping spraying rain etc or other harsh environments The original...

Отзывы: