24 VAC Universal Direct Spark Gas Ignition Control
©
2019 BASO Gas Products
7
Part No. BASO-INS-C107UQRG, Rev. C
www.baso.com
TROUBLESHOOTING GUIDE
1. No power up
•
Faulty 24 VAC wiring
•
Thermostat or transformer
•
Faulty control
•
Safety limits
2. Control LED is blinking RED
•
Determine error code, refer to error codes (Table 5), also
refer to the troubleshooting flow chart in the installation
instructions
3. No spark during Trial for Ignition (TFI) time
•
Faulty spark electrode wiring
•
Spark gap too wide
•
Faulty control
4. Burner does not light during trial for ignition time
•
Faulty valve wiring
•
Bad Gas Valve
•
Faulty Control
5. Burner lights but gas valve turns off after TFI
•
Weak flame, flame not in contact with the spark electrode of
flame sensor. Check that flame sensor tip is in the flame.
For proper sensing, the rod tip must be 3/8” (10mm) to 1/2”
(13mm) in the flame. See Figure 1.
•
Dirty or corroded flame sensor
•
Faulty flame sensor wiring
•
Poor burner ground
Note:
For more information on BASO ignitions and other products, plus
complete installation instructions, please visit us at
www.baso.com
.
Figure 1: Proper Flame Sensor Position
CORRECT
FLAME TOO LOW
FLAME TOO HIGH