BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions    

15

 

Technical Specification 

Product 

BG1600M Intermittent Pilot Ignition Control with Rollout Switch 

Ignition Type 

Indirect 

Ignition Source 

High voltage spark, capacitive discharge 

High Voltage Cable 
Maximum Length 

48 in. (1,220 mm) (Resistive wire recommended, rated for at least 15kV.) 

Flame Sense Cable 
Maximum Length 

48 in. (1,220 mm) 

Flame Detection Means 

Flame Rectification 

Flame Detection Type 

Remote 

Minimum Flame Current 

0.15 microamperes 

Flame Failure Response 
Time 

2 seconds maximum 

Maximum Spark Gap 

0.2 in. (5.1 mm) 

Number of Trials Before 
100% Shutoff 

One 

Trial-for-Ignition Time 

85 seconds 

Prepurge Time 

0 or 15 seconds 

Inter-Purge Time 

15 seconds 

Automatic Recycle Delay 
Period 

None or 5 minutes 

Power Requirements 

Control: 
Operation Current: 

24 VAC (+10%/-15%), 50/60 Hz 
0.2 A n valves 

Contact Rating 

Main Valve: 
Pilot Valve: 

4 A maximum 
2 A maximum 

Wiring Connections 

1/4 in. (6.35 mm) male spade 

Maximum Firing Rate 

400,000 Btu/hr (117 kW) 

Ambient Operating and 
Storage Temperature 

-40 to 170

°

F (-40 to 77

°

C) 

Humidity 

95% RH noncondensing 

Type of Gas 

Natural, Liquefied Petroleum (LP), Manufactured, Mixed or LP Gas-Air Mixture 

Packaging 

Individual pack (1 per box) 
Individual overpack (20 per box) 

Pack Weight 

Individual pack 1 lb (.454 kg) 
Individual overpack 18 lb (8.17 kg) 

Agency Listing 

CSA Certificate Number Pending 

Specifications Standards 

ANSI Standard Z21.20 
CAN/CSA-C22.2 No. 199 

The performance specifications are nominal and conform to acceptable industry standards. All agency certification of BASO products is 
performed under dry and controlled indoor environmental conditions. Use of BASO products beyond these conditions is not recommended and 
may void the warranty. If the product is exposed to water (dripping, spraying, rain, etc.) or other harsh environments, it must be protected. The 
original equipment manufacturer or end user is responsible for the correct application of BASO products. For questionable applications, please 
consult BASO Gas Products LLC. BASO Gas Products LLC shall not be liable for damages or product malfunctions resulting from 
misapplication or misuse of its products. 

 

1007 South 12th Street 
PO Box 170 
Watertown, WI 53094 

Published in U.S.A.

1-877-227-6427 

www.baso.com

Содержание BG1600M

Страница 1: ...Explosion or Fire Do not install the control in an area that is exposed to water for example dripping spraying rain Do not use the control if it has been exposed to water Exposure to water may cause...

Страница 2: ...ould be in accordance with the National Electrical Code NEC and all other local codes and regulations Check the voltage rating marked on the control and make sure it is suited to the application Use a...

Страница 3: ...in the flame for proper sensing signal Pilot Burner Ignitor Flame Sensor 6 GND 24V R O SW Rollout Switch PV MV Figure 1 Wiring for 2 Rod Flame Sense with Rollout Switch Rollout Switch Function The ro...

Страница 4: ...24V THS 2 Connect To 4 24V TH PV 1 Connect To 5 PV MV 3 Connect To 6 MV R O SWH R1 Connect To 7 R O SW SENSE 4 Connect To 8 SENSE NC none NC none 9 INTERN SPARK Rajah Connect To 10 SPARK NOTE NC means...

Страница 5: ...sful ignition at least five times 10 Return the thermostat to a normal temperature setting before leaving the installation WARNING The control module can not be serviced by user If any faults are dete...

Страница 6: ...he pilot valve will be shut off Lockout will occur if your model has no retry For models with retry the control will wait for 5 minutes and then begin another trial for ignition sequence Table 1 LED I...

Страница 7: ...Sensor tip is in the flame For proper sensing the rod tip must be 3 8 10 mm to 1 2 13 mm in the Flame 7 Check Flame Sensor is wired to terminal 8 SENSE and terminal 2 GND BURNER 8 Check that the sense...

Страница 8: ...eturns to the idle state Wait 0 1 second checking memory and relay driver circuits OK Flame on Yes No Flame off 0 7 second Turn pilot and main gas valves off wait 0 7 second inter purge blinking LED o...

Страница 9: ...t pin 2 3 shorting plug to damper No Spark wire and electrode OK Replace module Replace spark wire or electrode Yes Yes No Pilot flame does not light 24V between PV and GND terminals Replace module Ga...

Страница 10: ...clear If all OK replace main valve Yes No Replace module Yes Yes No Gas at main burner Adjust pilot flame size and position or replace pilot burner or main burner After main is lit do valves turn off...

Страница 11: ...sonally should be checked before shutdown and again before the next use Consequence of Unexpected Shutdown Where the cost of an unexpected shutdown would be high the system should be checked more ofte...

Страница 12: ...A40A 602H 24 Resistive Wire Harness with 2 1 4 Terminals bag of 1 WHA40A 603D 24 Resistive Wire Harness with 1 1 4 Terminal and 1 Rajah Terminal box of 25 WHA40A 603H 24 Resistive Wire Harness with 1...

Страница 13: ...BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions 13 Notes...

Страница 14: ...14 BG1600M Intermittent Pilot Ignition Control with Rollout Switch Installation Instructions Notes...

Страница 15: ...perating and Storage Temperature 40 to 170 F 40 to 77 C Humidity 95 RH noncondensing Type of Gas Natural Liquefied Petroleum LP Manufactured Mixed or LP Gas Air Mixture Packaging Individual pack 1 per...

Отзывы: