Basler DGC-2020ES Скачать руководство пользователя страница 14

1-6 

 

9469200997 

CEM-2020 

 

DGC-2020ES 

 

Figure 1-2. CEM-2020H Overall Dimensions 

Connections 

Contact Expansion Module connections are dependent on the application. Incorrect wiring may result in 

damage to the module. 

 

Note 

Operating power from the battery must be of the correct polarity. 

Although reverse polarity will not cause damage, the CEM-2020 will 

not operate. 
Be sure that the CEM-2020 is hard-wired to earth ground with no 

smaller than 12 AWG copper wire attached to the chassis ground 

terminal on the module. 

Terminations 

The terminal interface consists of plug-in connectors with screw-down compression terminals. 
CEM-2020 connections are made with one 5-position connector, two 18-position connectors, and two 24-

position connectors with screw-down compression terminals. These connectors plug into headers on the 

CEM-2020. The connectors and headers have dovetailed edges that ensure proper connector orientation. 

The connectors and headers are uniquely keyed to ensure that the connectors mate only with the correct 

headers. Connector screw terminals accept a maximum wire size of 12 AWG (3.31 mm

2

). Maximum 

screw torque is 5 inch-pounds (0.56 N

m). 

Operating Power 

The Contact Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates 

voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse 

Содержание DGC-2020ES

Страница 1: ... 143 Highland Illinois 62249 1074 USA Tel 1 618 654 2341 Fax 1 618 654 2351 www basler com info basler com Publication 9469200997 Rev C July 2021 DGC 2020ES Digital Genset Controller Accessories Instruction Manual ...

Страница 2: ...ause cancer birth defects or other reproductive harm Please note that by posting this Proposition 65 warning we are notifying you that one or more of the Proposition 65 listed chemicals may be present in products we sell to you For more information about the specific chemicals found in this product please visit https www basler com Prop65 ...

Страница 3: ... defined as follows Warning Warning boxes call attention to conditions or actions that may cause personal injury or death Caution Caution boxes call attention to operating conditions that may lead to equipment or property damage Note Note boxes emphasize important information pertaining to Digital Genset Controller installation or operation DGC 2020ES Instruction Manual Catalog Available instructi...

Страница 4: ...ume any responsibility to compliance or noncompliance with national code local code or any other applicable code This manual serves as reference material that must be well understood prior to installation operation or maintenance For terms of service relating to this product and software see the Commercial Terms of Products and Services document available at www basler com terms This publication c...

Страница 5: ...n History Manual Revision and Date Change C Jul 21 Removed CEM 2020 UL Recognition for use in Hazardous Locations Minor text edits B Nov 19 Removed Rev Letter from all pages Changed sequential numbering to sectional numbering Moved Instruction Manual Revision History into Preface Removed standalone Revision History chapter A1 Apr 19 Updated Proposition 65 statement A Sep 18 Updated output contacts...

Страница 6: ...iv 9469200997 Revision History DGC 2020ES ...

Страница 7: ...9469200997 v DGC 2020ES Contents Contents CEM 2020 1 1 Troubleshooting 2 1 ...

Страница 8: ...vi 9469200997 Contents DGC 2020ES ...

Страница 9: ... 500 ms Maximum Power Dissipation CEM 2020 14 W CEM 2020H 8 W Contact Inputs The CEM 2020 contains 10 programmable inputs that accept dry contacts Time from a CEM 2020 input application to Shut down the generator via an alarm 700 ms max Close a relay on board the DGC 2020ES 300 ms max Close a relay on board the CEM 2020 550 ms max Notes A CEM 2020 contact input is true on if the input is connected...

Страница 10: ...er with many years of reliable service HALT subjects the device to extremes in temperature shock and vibration to simulate years of operation but in a much shorter period span HALT allows Basler Electric to evaluate all possible design elements that will add to the life of this device As an example of some of the extreme testing conditions the CEM 2020 was subjected to temperature tests tested ove...

Страница 11: ...Electric Products with Respect to the Restriction of Hazardous Substances ROHS2 NFPA Compliance Designed to comply with NFPA Standard 110 Standard for Emergency and Standby Power EAC Mark Eurasian Conformity TC RUUS HO03 B 00742 Physical Dimensions See Installation later in this chapter Weight CEM 2020 2 25 lb 1 02 kg CEM 2020H 1 90 lb 0 86 kg Functional Description Contact Inputs The CEM 2020 pro...

Страница 12: ...and if there is evidence of such immediately file a claim with the carrier and notify the Basler Electric regional sales office or your sales representative If the device is not installed immediately store it in the original shipping package in a moisture and dust free environment Mounting Contact Expansion Modules are contained in a potted plastic case and may be mounted in any convenient positio...

Страница 13: ...9469200997 1 5 DGC 2020ES CEM 2020 Figure 1 1 CEM 2020 Overall Dimensions See Figure 1 2 for CEM 2020H overall dimensions All dimensions are shown in inches with millimeters in brackets ...

Страница 14: ...th screw down compression terminals CEM 2020 connections are made with one 5 position connector two 18 position connectors and two 24 position connectors with screw down compression terminals These connectors plug into headers on the CEM 2020 The connectors and headers have dovetailed edges that ensure proper connector orientation The connectors and headers are uniquely keyed to ensure that the co...

Страница 15: ...le A Bussmann ABC 7 fuse or equivalent is recommended Table 1 1 Operating Power Terminals Terminal Description P1 SHIELD Chassis ground connection P1 BATT Negative side of operating power input P1 BATT Positive side of operating power input Contact Inputs and Contact Outputs The CEM 2020 Figure 1 3 has 10 contact inputs and 24 contact outputs The CEM 2020H Figure 1 4 has 10 contact inputs and 18 c...

Страница 16: ...ation between the Contact Expansion Module and the DGC 2020ES Connections between the CEM 2020 and DGC 2020ES should be made with twisted pair shielded cable CAN interface terminals are listed in Table 1 2 Refer to Figure 1 5 and Figure 1 6 Table 1 2 CAN Interface Terminals Terminal Description P1 HI CAN H CAN high connection yellow wire P1 LO CAN L CAN low connection green wire P1 SHIELD CAN drai...

Страница 17: ... length not including stubs is 40 m 131 ft 4 The J1939 drain shield should be grounded at one point only If grounded elsewhere do not connect the drain to the CEM 2020 Figure 1 5 CAN Interface with CEM 2020 providing One End of the Bus Figure 1 6 CAN Interface with DGC 2020ES providing One End of the Bus DGC 2020ES CEM 2020 Optional P0067 96 Engine 120 ohm Termination CAN H CAN L Other Devices 120...

Страница 18: ... Programmable Logic when None is selected for Alarm Configuration The Remote Contact Inputs screen is found in the BESTCOMSPlus Settings Explorer under the Programmable Inputs category If using the front panel navigate to Settings Programmable Inputs Configurable Inputs The BESTCOMSPlus Remote Contact Inputs screen is illustrated in Figure 1 7 Figure 1 7 Settings Explorer Programmable Inputs Remot...

Страница 19: ...o repair procedures be attempted by anyone other than Basler Electric personnel Before returning the CEM 2020 for repair contact Basler Electric Technical Services Department at 618 654 2341 for a return authorization number Maintenance Preventive maintenance consists of periodically checking that the connections between the CEM 2020 and the system are clean and tight Storage This device contains ...

Страница 20: ...1 12 9469200997 CEM 2020 DGC 2020ES ...

Страница 21: ...ine is equipped with a Volvo or mtu ECU verify that the ECU Configuration setting is set to match the actual ECU configuration Inputs and Outputs Programmable Inputs Do Not Operate as Expected Step 1 Verify that all wiring is properly connected Refer to the Typical Connections chapter in the Installation manual Step 2 Confirm that the inputs are programmed properly Step 3 Ensure that the input at ...

Страница 22: ...are correct Step 4 Confirm that the current sensing transformers are correct and properly installed Incorrect Display of Engine RPM Step 1 Verify that all wiring is properly connected Refer to the Typical Connections chapter in the Installation manual Step 2 Verify that the flywheel teeth setting is correct Step 3 Verify that the prime mover governor is operating properly Step 4 Verify that the me...

Страница 23: ... verify that when the generator is running the GEN STABLE status LED is lit If necessary modify the settings on the SETTINGS BREAKER MANAGEMENT BUS CONDITION DETECTION screen Step 5 Verify the bus status is DEAD Check status by using the Metering Explorer in BESTCOMSPlus and verify that when the generator is running the BUS DEAD status LED is lit If necessary modify the settings on the SETTINGS BR...

Страница 24: ... state if it is being commanded to open and close at the same time Step 4 Verify the breaker is receiving an open command Breaker open command sources are The DGC 2020ES itself when the automatic transfer ATS feature is enabled The DGC 2020ES itself when the RUN WITH LOAD logic element receives a Stop pulse in the programmable logic The DGC 2020ES itself when shutting down the engine due to an act...

Страница 25: ...NGS BREAKER MANAGEMENT BUS CONDITION DETECTION screen to achieve correct detection Step 5 Verify the wiring to the breaker from the DGC 2020ES If it seems OK you can do a manual close and open by modifying the programmable logic Map some unused outputs to the OPEN and CLOSE outputs from the Gen Breaker Block in the programmable logic Map a virtual switch to the logic output that would normally be ...

Страница 26: ...2 6 9469200997 Troubleshooting DGC 2020ES ...

Страница 27: ......

Страница 28: ... basler com No 59 Heshun Road Loufeng District N Suzhou Industrial Park 215122 Suzhou P R CHINA Tel 86 512 8227 2888 Fax 86 512 8227 2887 email chinainfo basler com 111 North Bridge Road 15 06 Peninsula Plaza Singapore 179098 Tel 65 68 44 6445 Fax 65 68 44 8902 email singaporeinfo basler com ...

Отзывы: