
1-6
9469200997
CEM-2020
DGC-2020ES
Figure 1-2. CEM-2020H Overall Dimensions
Connections
Contact Expansion Module connections are dependent on the application. Incorrect wiring may result in
damage to the module.
Note
Operating power from the battery must be of the correct polarity.
Although reverse polarity will not cause damage, the CEM-2020 will
not operate.
Be sure that the CEM-2020 is hard-wired to earth ground with no
smaller than 12 AWG copper wire attached to the chassis ground
terminal on the module.
Terminations
The terminal interface consists of plug-in connectors with screw-down compression terminals.
CEM-2020 connections are made with one 5-position connector, two 18-position connectors, and two 24-
position connectors with screw-down compression terminals. These connectors plug into headers on the
CEM-2020. The connectors and headers have dovetailed edges that ensure proper connector orientation.
The connectors and headers are uniquely keyed to ensure that the connectors mate only with the correct
headers. Connector screw terminals accept a maximum wire size of 12 AWG (3.31 mm
2
). Maximum
screw torque is 5 inch-pounds (0.56 N
•
m).
Operating Power
The Contact Expansion Module operating power input accepts either 12 Vdc or 24 Vdc and tolerates
voltage over the range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse
Содержание DGC-2020ES
Страница 6: ...iv 9469200997 Revision History DGC 2020ES ...
Страница 7: ...9469200997 v DGC 2020ES Contents Contents CEM 2020 1 1 Troubleshooting 2 1 ...
Страница 8: ...vi 9469200997 Contents DGC 2020ES ...
Страница 20: ...1 12 9469200997 CEM 2020 DGC 2020ES ...
Страница 26: ...2 6 9469200997 Troubleshooting DGC 2020ES ...
Страница 27: ......