DECS-400 Digital Excitation Control System

4

SPECIFICATIONS, continued

IRIG-B Time Sync

Standard:

200-98, Format B002, Demodulated (dc level-shifted digital signal) or NTP via Ethernet

Regulation Accuracy

AVR Mode

Voltage regulation ±0.2% over the load range, at rated power factor and constant generator
frequency. Steady state stability is ±0.1% at constant load and frequency. Temperature
Stability ±0.5% between 0 to 50°C at constant load and frequency. Response Time <1
cycle.

FCR Mode

Field Current Regulation is ±1.% of the nominal value for 10% of the rectifier bridge input
voltage change or 20% of the field resistance change. Otherwise, ±5.0%.

VAR Control Mode

Reactive Power Regulation is ±2.0% of the nominal VA rating at the rated frequency.

PF Control Mode

±0.02 Power Factor for real power between 10 and 100% at rated frequency.
(e.g. set point PF = 0.8, PF regulation is between 0.78 and 0.82)

Metering Accuracy

Generator and Bus Voltage:

±1.0%

Generator and Bus Frequency: ±0.1 Hz

Generator Line Current:

±1.0%

Power Factor:

±0.02 PF

Field Current and Voltage:

±2.0%

Aux. Voltage and Current Input: ±1.0%

Generator Power:

Apparent Power (VA) ±2.0%; Active Power (W) ±2.0%; Reactive Power (var) ±2.0%

Power System Stabilizer (PSS)

Operating Mode:

Generator or Motor, ABC or ACB phase sequence

Sensing Configuration: Power and Speed or Speed only
Power Measurement:

2 wattmeter method

Frequency Range:

Responds to power oscillations from 0.1 to 5 Hz. Low-pass and high-pass
filtering prevents unwanted PSS action outside this range.

Soft Start

  Two sets of soft start settings are available when operating in AVR or FCR mode. Bias level is adjust-

able from 0-90% in 1% increments; time to reach nominal value is adjustable from 1-7,200 s in 1 s increments.

Sequence of Events Recording

  Events are time- and date-stamped and stored in volatile memory. 127 event

capacity, 50 ms scan interval. SER can be triggered by input/output status changes, alarms, or system operating
status changes.

Data Logging (Oscillography)

Stores 6 records, with up to 6 variables per record. Sampling rate: 600 data

points per record, pre-trigger adjustable from 0 to 599 data points. Record interval adjustable from 4 ms to 10 s.

Trending

  Stores 1 record, with up to 6 variables per record. Sampling rate is 1200 data points per record, with

total record duration adjustable from 1 hour to 30 days.

Paralleling/Line Drop Compensation

 Can use either reactive droop or reactive differential (cross-current)

compensation. Droop adjustable from 0% to 30% in 0.1% increments. Parallel compensation burden is less than 1
VA. Negative droop settings provide line drop compensation. Adjustable from -30% to 0% in 0.1% increments.

Limiters

Underfrequency Compensation

Choice: Underfrequency compensation with slope adjustable from 0 to 3.00 PU in

.01 PU increments and knee frequency between 15 and 90 Hz, or Volts/Hertz ratio limiter with slope adjustable
from 0 to 3.0 PU in 0.1 PU increments. Provisions for two levels of protection, with duration of high V/Hz limit
adjustable in the range of 0 to 10 s.

Overexcitation

On-line and off-line limiters provided, each a choice between summing point and takeover type

controllers. Dual settings groups. Provisions to scale settings for both type limiters based on an auxiliary analog
input (by others) representing air temperature, hydrogen pressure, etc. Includes a cooldown feature to prohibit
repeated high forcing level operation that could be damaging to the rotor.

Содержание DECS-400

Страница 1: ...itation control flexible logic control and optional power system stabilization for synchronous machines in an integrated package The controller provides an analog output to control the DC output of an external rectifier bridge and monitors machine parameters to control limit and protect the synchronous machine from operating beyond its capability limitations The optional Power System Stabilizer is...

Страница 2: ...is suitable for use in single or dual controller systems on virtually any synchronous machine The DECS 400 is at the heart of custom Basler Electric excitation systems that typically include the digital controller supplementary protective and control devices a power potential transformer and associated AC breaker or contactor SCR firing circuits and a power rectifier section as sembled in suitable...

Страница 3: ...e Reactive Differential Compensation Enable 2nd Pre Position Accessory Input Remote Set Point Control Analog input for remote set point control Select one of two configurations 10 Vdc or 4 20 mA dc Control Outputs Isolated analog output for set point control Output drives external Firing Circuit Rectifier Bridge Select one of three configurations 10 Vdc 0 10 Vdc or 4 20 milliamperes dc Meter Drive...

Страница 4: ... from 0 90 in 1 increments time to reach nominal value is adjustable from 1 7 200 s in 1 s increments Sequence of Events Recording Events are time and date stamped and stored in volatile memory 127 event capacity 50 ms scan interval SER can be triggered by input output status changes alarms or system operating status changes Data Logging Oscillography Stores 6 records with up to 6 variables per re...

Страница 5: ... Includes a two step limiter with a definite time delay for the higher limit level adjustable between 0 and 60 s Summing point type limiter with PI control loop Protection Functions Field Overvoltage Range 1 to 2000 Vdc time delay 0 2 to 30 s dual setting groups Field Overcurrent Range from 0 1 to 9 999 Adc time delay 0 1 to 20 s dual setting groups Generator Undervoltage Range from 0 to 34 500 Va...

Страница 6: ...hile a slower controller can provide improved damping of first swing oscillations with the PSS off line Optional Power System Stabilizer The DECS 400 may be purchased with an integral Power System Stabilizer function that duplicates the excellent performance of the Basler PSS 100 Power System Stabilizer without the complications of an additional control device The PSS provides damping for local mo...

Страница 7: ...on The DECS 400 has provisions for paralleling two or more generators using reactive droop or for using reactive differential compensation with the addition of an external current transformer with secondary currents of 1 or 5A ac The current input burden is less than 1VA so existing metering CTs can be used Inputting a negative value for droop provides Line Drop Compen sation to offset line or tra...

Страница 8: ...and timer gates Inputs to the logic are in the form of discrete information including switching inputs system status data protection status data limiter status data alarm status data and PSS status data The outputs of the logic module can be used to control the relay outputs as well as various other functions inside the DECS such as control functions start stop mode select etc protection functions...

Страница 9: ... for an external Dynamic System Analyzer DSA and associ ated transducers Communications DECS 400 comes complete with Windows based PC software designed to make the programming and cus tomization of the DECS 400 easy and fast The software includes a PID selection program that allows the user to select stability settings quickly and easily in a user friendly format The PC software has monitoring scr...

Страница 10: ...ystem setup and testing As shown in the Protection screen below left choices are made using drop down screens and parameters are familiar Reminders are also provided at the bottom of the screen for input units and available parameter range Tabs identify general functions and related functions are on adjacent pages As shown on the Underexcitation Limiter Screen below right graphics are also used to...

Страница 11: ...ting can also be performed using screens such as the Test Signal screen which can initiate pre programmed tests that may be monitored using the Real Time Monitoring function illustrated in the Analysis screen above right BESTCOMS for the DECS 400 also incorporates greater Windows functionality as shown in the screen shot below The screen simultaneously displays the systems status and alarms window...

Страница 12: ...re 4 Front Panel Cutout Dimensions front panel mounting bracket Figure 3 Dimensions Isolation Transducer DECS 400 U PSS 1 Integrated power system stabilizer 2 None POWER SUPPLY L 24 48 Vdc C 125 Vdc 120 Vac CURRENT SENSING 1 1 A CT secondary 5 5 A CT secondary BATTERY BACKUP U Battery backup for real time clock MODEL NUMBER NOTE Effective January 2008 battery backup feature is standard Printed in ...

Отзывы: