background image

DECS-400 Digital Excitation Control System

SZF-5

 9-10

• Microprocessor-based design
• Five Control Modes, with autotracking between modes

- Automatic Voltage Regulation (AVR)

- Power Factor (PF)

- Field Current Regulation (FCR)

- Field Voltage Regulation (FVR)

- Var Control

• 0.20% Voltage Regulation Accuracy
• Two pre-position set points for each mode
• Two Programmable Analog Outputs
• Setup from Front Panel HMI or by PC (local or remote)
• 40 Standard Stability Settings
• Time synchronization using IRIG or NTP (via Ethernet)
• Optional Integral Power System Stabilizer

- Dual input, integral of accelerating power (IEEE PSS2A/2B)

- Customer selectable speed-only sensing

- Two wattmeter power measurement

- Optional Frequency Based Operation

- Generator or Motor control modes

• Customizable Stability Setting with two PID setting groups
• Reactive Droop, Line Drop Compensation
• Generator Voltage Soft-Start during Buildup
• Real Time Metering for 19 Generator Parameters
• Voltage Matching
• Autotracking with Optional Backup DECS-400
• Flexible Remote Set point Control

- Contact inputs
- Proportional Analog input, ±10 Vdc or 4-20 mA
- Digital Communications

Local RS-232, ASCII, Modem Capabilities

RS-485, Modbus™, RJ-45 Ethernet

(continued on page 2)

The DECS-400 Digital Excitation Control System is a microprocessor-based controller that provides excitation
control, flexible logic control, and optional power system stabilization for synchronous machines in an
integrated package. The controller provides an analog output to control the DC output of an external rectifier
bridge and monitors machine parameters to control, limit, and protect the synchronous machine from
operating beyond its capability limitations.

The optional Power System Stabilizer is an IEEE-type PSS2A/2B, dual input, "integral of accelerating power"
stabilizer that provides supplementary damping for low-frequency local mode, inter area, and inter unit power
system oscillations.

Setup and initial operation are facilitated by Basler Electric's user-friendly BESTCOMS PC software that
incorporates real time monitoring test analysis, flexible oscillography, trending, and expanded testing
capabilities, including means for performing frequency response tests with a graphic display of results. This
replaces the need for an external Dynamic System Analyzer.

DECS-400

Digital Excitation

Control System

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A. 62249   PHONE 618-654-2341   FAX 618-654-2351

DESCRIPTION  and

SPECIFICATIONS

Pages 2 through 6

FEATURES and

FUNCTIONS

Pages 6 through 9

FRONT VIEW

and DIMENSIONS

Page 9

INTERCONNECT

DIAGRAM

Page 10

BESTCOMS SOFTWARE

Pages 10 and 11

CUTOUT and ORDERING

Page 12

FEATURES

ADDITIONAL INFORMATION

INSTRUCTION MANUAL

Request Publication 9369700990

            WINDOWS

®

 

SOFTWARE

Interface for setting and communicating with Basler products

   Request BESTCOMS-DECS400

Содержание DECS-400

Страница 1: ...itation control flexible logic control and optional power system stabilization for synchronous machines in an integrated package The controller provides an analog output to control the DC output of an external rectifier bridge and monitors machine parameters to control limit and protect the synchronous machine from operating beyond its capability limitations The optional Power System Stabilizer is...

Страница 2: ...is suitable for use in single or dual controller systems on virtually any synchronous machine The DECS 400 is at the heart of custom Basler Electric excitation systems that typically include the digital controller supplementary protective and control devices a power potential transformer and associated AC breaker or contactor SCR firing circuits and a power rectifier section as sembled in suitable...

Страница 3: ...e Reactive Differential Compensation Enable 2nd Pre Position Accessory Input Remote Set Point Control Analog input for remote set point control Select one of two configurations 10 Vdc or 4 20 mA dc Control Outputs Isolated analog output for set point control Output drives external Firing Circuit Rectifier Bridge Select one of three configurations 10 Vdc 0 10 Vdc or 4 20 milliamperes dc Meter Drive...

Страница 4: ... from 0 90 in 1 increments time to reach nominal value is adjustable from 1 7 200 s in 1 s increments Sequence of Events Recording Events are time and date stamped and stored in volatile memory 127 event capacity 50 ms scan interval SER can be triggered by input output status changes alarms or system operating status changes Data Logging Oscillography Stores 6 records with up to 6 variables per re...

Страница 5: ... Includes a two step limiter with a definite time delay for the higher limit level adjustable between 0 and 60 s Summing point type limiter with PI control loop Protection Functions Field Overvoltage Range 1 to 2000 Vdc time delay 0 2 to 30 s dual setting groups Field Overcurrent Range from 0 1 to 9 999 Adc time delay 0 1 to 20 s dual setting groups Generator Undervoltage Range from 0 to 34 500 Va...

Страница 6: ...hile a slower controller can provide improved damping of first swing oscillations with the PSS off line Optional Power System Stabilizer The DECS 400 may be purchased with an integral Power System Stabilizer function that duplicates the excellent performance of the Basler PSS 100 Power System Stabilizer without the complications of an additional control device The PSS provides damping for local mo...

Страница 7: ...on The DECS 400 has provisions for paralleling two or more generators using reactive droop or for using reactive differential compensation with the addition of an external current transformer with secondary currents of 1 or 5A ac The current input burden is less than 1VA so existing metering CTs can be used Inputting a negative value for droop provides Line Drop Compen sation to offset line or tra...

Страница 8: ...and timer gates Inputs to the logic are in the form of discrete information including switching inputs system status data protection status data limiter status data alarm status data and PSS status data The outputs of the logic module can be used to control the relay outputs as well as various other functions inside the DECS such as control functions start stop mode select etc protection functions...

Страница 9: ... for an external Dynamic System Analyzer DSA and associ ated transducers Communications DECS 400 comes complete with Windows based PC software designed to make the programming and cus tomization of the DECS 400 easy and fast The software includes a PID selection program that allows the user to select stability settings quickly and easily in a user friendly format The PC software has monitoring scr...

Страница 10: ...ystem setup and testing As shown in the Protection screen below left choices are made using drop down screens and parameters are familiar Reminders are also provided at the bottom of the screen for input units and available parameter range Tabs identify general functions and related functions are on adjacent pages As shown on the Underexcitation Limiter Screen below right graphics are also used to...

Страница 11: ...ting can also be performed using screens such as the Test Signal screen which can initiate pre programmed tests that may be monitored using the Real Time Monitoring function illustrated in the Analysis screen above right BESTCOMS for the DECS 400 also incorporates greater Windows functionality as shown in the screen shot below The screen simultaneously displays the systems status and alarms window...

Страница 12: ...re 4 Front Panel Cutout Dimensions front panel mounting bracket Figure 3 Dimensions Isolation Transducer DECS 400 U PSS 1 Integrated power system stabilizer 2 None POWER SUPPLY L 24 48 Vdc C 125 Vdc 120 Vac CURRENT SENSING 1 1 A CT secondary 5 5 A CT secondary BATTERY BACKUP U Battery backup for real time clock MODEL NUMBER NOTE Effective January 2008 battery backup feature is standard Printed in ...

Отзывы: