General Information
1-2
Indicators
There are two indicators mounted on the front panel of the relay. The SYNC LED (present only in the
BE3-GPR P units with the sync-check option) indicates that the generator and bus inputs are within the
synchronization window set by the user. The liquid crystal display (LCD) is the main human-machine
interface and has capabilities to show any and all information necessary for programming and interpreting
relay actions.
Communications
Communication capability provides a remote serial interface between the relay and a computer. Basler
Electric offers a software package that enhances communications to BE3-GPRs. This software package
also provides a real time metering capability for monitoring generator voltage, frequency, current, watts,
power factor, and volt-amperes.
OUTPUTS
There are eleven isolated form C output contact arrangements. One for each of the nine protective
functions, the sync-check/dead bus function, and the watchdog timer.
SPECIFICATIONS
Timing Accuracy:
(All Functions Except 51V)
Accuracy is ±1% or ±50 milliseconds, whichever is greater.
27
Undervoltage
Trip point and reset set points are settable from 70 to 600 Vac in one volt
steps, and trip timing is adjustable from 0 to 20 seconds in one second
steps. Accuracy is ±2%. Repeatability is ±1.0 %.
59
Overvoltage
Trip point and reset set points are settable from 70 to 600 Vac in one volt
steps, and trip timing is adjustable from 0 to 20 seconds in one second
steps. Accuracy is ±2%. Repeatability is ±1.0 %.
81O
Overfrequency
Trip point and reset points are settable from 35 to 75 hertz in 0.1 hertz
steps. Trip timing is adjustable from 0 to 20 seconds in steps of one
second. Accuracy is ±0.025 Hz. Repeatability is ±0.01 Hz.
81U
Underfrequency
Trip point and reset points are settable from 35 to 75 hertz in 0.1 hertz
steps. Trip timing is adjustable from 0 to 20 seconds in one second
steps. Accuracy is ±0.025 Hz. There are two independent 81U functions
available. Repeatability is ±0.01 Hz.
32R
Reverse Power
Measures three-phase reverse power. Trip point and reset points are
settable from 50 to 999 watts in one watt steps. Trip timing is adjustable
from 0 to 20 seconds in one second steps. At power factors equal to or
greater than the absolute value of 0.5, and at 25
°
C, accuracy is ±2% or
±10W whichever is greater. At temperatures from -25 to 60
°
C, accuracy
is ±5% or ±10W whichever is greater. This function is available only in
the paralleled generator version. Repeatability is ±1.0 %.
Содержание BE3-GPR
Страница 15: ...General Information 1 8 ...
Страница 16: ...General Information 1 9 Figure 1 2 Time Characteristic Curve S1 Short Inverse 99 1369 Similar to ABB CO 2 ...
Страница 17: ...General Information 1 10 Figure 1 3 Time Characteristic Curve S2 Short Inverse 99 1595 Similar To GE IAC 55 ...
Страница 18: ...General Information 1 11 Figure 1 4 Time Characteristic Curve L1 Long Inverse 99 1369 Similar to ABB CO 5 ...
Страница 19: ...General Information 1 12 ...
Страница 20: ...General Information 1 13 Figure 1 5 Time Characteristic Curve L2 Long Inverse 99 1594 Similar To GE IAC 66 ...
Страница 21: ...General Information 1 14 Figure 1 6 Time Characteristic Curve D Definite Time 99 1371 Similar To ABB CO 6 ...
Страница 22: ...General Information 1 15 Figure 1 7 Time Characteristic Curve M Moderately Inverse 99 1372 Similar to ABB CO 7 ...
Страница 23: ...General Information 1 16 Figure 1 8 Time Characteristic Curve I1 Inverse Time 99 1373 Similar to ABB CO 8 ...
Страница 24: ...General Information 1 17 Figure 1 9 Time Characteristic Curve I2 Inverse Time 99 1597 Similar to GE IAC 51 ...
Страница 25: ...General Information 1 18 Figure 1 10 Time Characteristic Curve V1 Very Inverse 99 1374 Similar to ABB CO 9 ...
Страница 26: ...General Information 1 19 Figure 1 11 Time Characteristic Curve V2 Very Inverse 99 1596 Similar to GE IAC 53 ...
Страница 29: ...General Information 1 22 Figure 1 14 Time Characteristic Curve A Standard Inverse 99 1621 ...
Страница 30: ...General Information 1 23 Figure 1 15 Time Characteristic Curve B Very Inverse 99 1376 ...
Страница 31: ...General Information 1 24 Figure 1 16 Time Characteristic Curve C Extremely Inverse 99 1377 ...
Страница 32: ...General Information 1 25 Figure 1 17 Time Characteristic Curve G Long Time Inverse 99 1622 ...
Страница 42: ...Functional Description 3 7 Figure 3 3 Selection Menu Sheet 1 of 6 ...
Страница 43: ...Functional Description 3 8 Figure 3 4 Selection Menu Sheet 2 of 6 ...
Страница 44: ...Functional Description 3 9 Figure 3 5 Selection Menu Sheet 3 of 6 ...
Страница 45: ...Functional Description 3 10 Figure 3 6 Selection Menu Sheet 4 of 6 ...
Страница 46: ...Functional Description 3 11 Figure 3 7 Selection Menu Sheet 5 of 6 ...
Страница 47: ...Functional Description 3 12 Figure 3 8 Selection Menu Sheet 6 of 6 ...