BE1-851E

PERFORMANCE SPECIFICATIONS

INSTANTANEOUS OVERCURRENT WITH
SETTABLE DELAY (50TP, 150TP, 50TN, 150TN,
50TQ, 150TQ)

Pickup:

5A CT: 0.5-150.0A
1A CT: 0.1-30.0A

PU time with TD=0.000 Sec

1

¼

 cyc for P&N @ 5 x PU

2

¼

 cyc for Q @ 5 x PU

Delay time: 0.000 - 60 sec
Time Accuracy:

±0.5% or ±

¼

 cyc for P&N

±0.5% or ±1 cyc for Q

TIME OVERCURRENT (51P, 51N, 51Q)

Pickup:

5A CT: 0.50-16.0A
1A CT: 0.10-3.20A

Time Dial: TD=K=0 - 99 for 46 curve

TD=0.0 - 9.9 for all other curves

Time-Current Characteristics:

The following expression describes the inverse
time current characteristic for each curve:

        T

T

  =    AD    +  BD  +  K = Time to trip

                  M

N

-C

        T

R

 =   RD    =  Time for decaying reset

                 M

2

-1

where D = Time dial, M = Multiple of PU and A, B, C,
N, K and R are constants that govern the shape of
each curve. The protection engineer can set the
constants for the P (programmable) curve to achieve
virtually any characteristic.

BREAKER FAILURE (BF)

Time:

50-999 mSec

Dropout:

5A CT: 0.5A
1A CT: 0.1A

Time Accuracy: ±0.5% or +1

¼

 cyc/ -

¼

 cyc

GENERAL PURPOSE LOGIC TIMERS (62, 162)

Mode:

PU.DO
1 Shot, Non-Retrig.
1 Shot, Retrig.
Integrating
Latch

T1 and T2 Delay Time:

0.000 - 9999 sec.

Time Accuracy:

±0.5% or ±

½

 cyc

RECLOSER (79)

Mode:

Power up to close
Power up to lockout

Reclose Shots:

0 - 4

Reclose, Reset, Fail,
Max. Cycle Timers:

0.100 - 600 sec.

Time Accuracy:

±0.5% or +1

¾

 cyc /

-0 cyc

CURRENT PICKUP ACCURACY

Phase and Neutral:

5A: 2% or 50mA
1A: 2% or 10mA

Negative Sequence:

5A: 3% or 75mA
1A: 3% or 75mA

SETTING GROUPS

Setting Groups:

4

Control Modes:

Automatic: CLP; Dynamic load
or unbalance; External:
Discrete input logic; Binary
Input Logic

METERING

Current Range:

5A: 0.5 to 15.0
1A: 0.1 to 3.0

Current Accuracy: ±1%

DEMANDS (IA, IB, IC, IN, IQ)

Demand Interval:

1 - 60 min.

Demand Mode:

Thermal

BREAKER MONITORING

Duty Mode:

I or I

2

Duty Alarm Range:

0-100%

Op Counter Alarm Range: 0-99999
Trip Time Alarm Range:

20-1000 mSec

Constants

Curve

Type

S1

     S2

L1

L2

D

M

I1

I2

V1

V2

E1

E2

A

B

C

G

F

P

    A             B             C             N             K           R

0.2663  0.03393

1.000

1.2969

0.028

0.5000

0.0286

0.02080

1.000

0.9844

0.028

0.0940

5.6143    2.18592

1.000

1.000      0.028

15.750

2.3955

0.00000

1.000

0.3125

0.028

7.8001

0.4797

0.21359

1.000

1.5625

0.028

0.8750

0.3022

0.12840

1.000

0.5000

0.028

1.7500

8.9341

0.17966

1.000

2.0938

0.028

9.0000

0.2747

0.1042

1.000

0.4375

0.028

0.8868

5.4678

0.10814

1.000

2.0469

0.028

5.5000

4.4309

0.0991

1.000

1.9531

0.028

5.8231

7.7624

0.02758

1.000

2.0938

0.028

7.7500

4.9883

0.0129

1.000

2.0469

0.028

4.7742

0.01414 0.00000

1.000

0.0200

0.028

2.0000

1.4636

0.00000

1.000

1.0469

0.028

3.2500

8.2506

0.00000

1.000

2.0469

0.028

8.0000

12.1212 0.00000

1.000

1.000

0.028

29.000

0.0000   1.00000

0.000

0.0000

0.028

1.0000

0 to 600   0 to 25      0 to 1     .5 to 2.5 0.028     0 to 30

S1, S2 

= CO Short Inv, IAC Short Inv

A

 = IEC Standard Inverse

L1, L2 

= CO Long Inv, IAC Long Inv

B

 = IEC Very Inverse

D

 = CO Definite Time

= IEC Extremely Inverse

M

 = CO Moderately Inverse

G

 = IEC Long Time Inverse

I1, I2

 = CO Inverse, IAC Inverse

F

 = Fixed Time

V1, V2

 = CO Very Inv, IAC Very Inv

P

 = Programmable

E1, E2

 = CO Ext Inverse, IAC Ext. Inverse

10

Содержание BE1-851E

Страница 1: ...he relay to replace local indication and control functions such as panel metering alarm annunciation and control switches Three independent communication ports with protocol support allows integration with distributed control systems Real Time Clock with 8 hour capacitor ride through and optional battery backup Available in a fully drawout case configuration FEATURES Pages 2 and 3 APPLICATIONS Pag...

Страница 2: ...fault report Fault summary reports two most recent Fault Summary Records saved to non volatile memory 16 fault records 15 cycles long 24 samples cycle COMTRADEformat COMMUNICATIONPORTS Threeindependentgeneralpurposecommunica tion ports Front RS 232 ASCII communications Rear RS 232 ASCII communications Rear RS 485 ASCII Modbus DNP or other common protocols IRIG B time sync unmodulated SELF TEST AND...

Страница 3: ...nd remote indication metering and control functions required on a typical circuit Applications that require communication capability Applications that require specific current response characteristics The fundamental digital signal processing DSP algorithm provides rejection of harmonics and low transient overreach The RMS DSP algorithm provides true wide band RMS measurement The average DSP algor...

Страница 4: ...chronization from a master clock Real time metering provides amp and unbalance loading telemetry for the protected circuit Contact sensing inputs and alarm monitoring functions provide real time status information Remote control is provided by virtual control and selector switches with select before operate control of programmable outputs BESTlogic BESTlogic programmable logic provides the user wi...

Страница 5: ...2A Typical External Sensing Connections Feeder Breaker Application Figure 2B Typical External Sensing Connections Transformer Backup Application FUNCTIONAL DESCRIPTION continued 5 Figure 2C Alternate Connections for IN ...

Страница 6: ...BE1 851E Figure 3 Typical External Connections FUNCTIONAL DESCRIPTION continued 6 Figure 4 Typical Application Single Line ...

Страница 7: ...BE1 851E FUNCTIONAL DESCRIPTION continued Figure 5 BE1 851E Rear Panel Connections 7 ...

Страница 8: ...BE1 851E Figure 6 BESTlogic Function Blocks 8 ...

Страница 9: ...rdSurgeWithstand Capability Tests for Relays and Relay Systems Associated with Electric Power Apparatus IEC 255 22 1 1MHz Burst Disturbance Tests for Electrical Disturbance Tests for Measuring Relays and Protection Equipment EN 61000 4 4 Electrical Fast Transient Burst Immu nity Test EN 61000 4 3 Radiated Radio frequency Electro magnetic Field Immunity Test Type tested using a 5 watt hand held tra...

Страница 10: ...75mA SETTING GROUPS Setting Groups 4 Control Modes Automatic CLP Dynamic load or unbalance External Discrete input logic Binary Input Logic METERING Current Range 5A 0 5 to 15 0 1A 0 1 to 3 0 Current Accuracy 1 DEMANDS IA IB IC IN IQ Demand Interval 1 60 min Demand Mode Thermal BREAKER MONITORING Duty Mode I or I2 Duty Alarm Range 0 100 Op Counter Alarm Range 0 99999 Trip Time Alarm Range 20 1000 ...

Страница 11: ... Supply K H1 type case with normally open alarm output contacts 0 ASCII protocol communication via RS 485 U Battery backup for Real Time Clock 00 None 9289900017 Escutcheon plate to panel mount one H1 relay 9289900016 Escutcheon plate to panel mount two dovetailed H1 relays 9289924100 Adapter bracket to mount single H1 case in 19 rack 9289929100 Adapter bracket with cutout for ABB FT test switch t...

Страница 12: ...el 1 618 654 2341 Fax 1 618 654 2351 e mail info basler com www basler com P A E Les Pins 67319 Wasselonne Cedex FRANCE Tel 33 3 88 87 1010 Fax 33 3 88 87 0808 e mail beifrance basler com No 59 Heshun Road Loufeng District N Suzhou Industrial Park 215122 Suzhou P R China Tel 86 0 512 6346 1730 Fax 86 0 512 8227 2888 e mail beichina basler com ...

Отзывы: