9137300990 Rev J 

BE1-81O/U General Information 

1-1 

SECTION 1 

 GENERAL INFORMATION 

INTRODUCTION 

The BE1-81O/U Digital Frequency Relay monitors the frequency of a single-phase, ac voltage and 
provides accurate frequency protection for a distribution system or generator operating at 50 or 60 hertz. 

The BE1-81O/U initiates removal of a load from a distribution system when the system frequency 
decreases below the relay’s adjustable setpoint. When the system frequency returns to normal (as 
defined by another setpoint), the BE1-81O/U permits restoration of the load. The BE1-81O/U may be 
tailored to the operating frequency/time characteristic of a generator to permit removal of the generator 
from service if the generator frequency (or system frequency) exceeds a setpoint. This scheme also 
permits restoration to service when the generator (or system) frequency returns to normal. 

FEATURES 

The BE1-81O/U can be specified with up to four independently adjustable frequency setpoints and time 
delays with associated output relays and target indicators. 

Frequency Setpoints 

Each frequency setpoint has a setting range of 40 to 70 hertz and can be switch selected to detect over-
frequency or underfrequency. BE1-81O/U relays with one or two setpoints are supplied in an S1 case. 
Relays with three or four setpoints are supplied in an M1 case. 

Time Delays 

Each definite time delay setting can be adjusted for a delay of three cycles to 990 seconds.  

Undervoltage Inhibit 

An undervoltage inhibit feature prevents relay operation if the sensed voltage decreases below the 
adjustable front panel setting. 

Targets 

Either internally-operated or current-operated target indicators are available for each setpoint. 

OPERATION 

When the sensed frequency passes through a setpoint in the selected direction, a three-cycle timer 
begins timing. If the condition persists for the duration of the three-cycle timer, the Pickup LED indicator 
lights and the definite time delay is triggered. If the pickup condition persists for the duration of the time 
delay setting, the corresponding output relay energizes, operates the appropriate output contacts, and 
trips the setpoint’s target indicator. 

STYLE NUMBER 

BE1-81O/U electrical characteristics and operating features are defined by a combination of letters and 
numbers that make up the relay style number. The style number describes the features and options of a 
particular relay and appears on the front panel, draw-out cradle assembly, and the relay case. The style 
number identification chart shown in Figure 1-1 illustrates the features and options for the BE1-81O/U 
relay. 

Содержание BE1-81O/U

Страница 1: ...INSTRUCTION MANUAL FOR DIGITAL FREQUENCY RELAY BE1 81O U Publication 9137300990 Revision J 10 07...

Страница 2: ......

Страница 3: ...ols and Indicators Functional Description Installation Testing WARNING To avoid personal injury or equipment damage only qualified personnel should perform the procedures in this manual NOTE Be sure t...

Страница 4: ...tion or operation The availability and design of all features and options are subject to modification without notice Should further information be required contact Basler Electric BASLER ELECTRIC ROUT...

Страница 5: ...ree position Selector Switch S7 All case drawings were updated to show revised case covers Definite time delay options test procedures Section 5 were modified to accommodate the new E1 and E2 timing o...

Страница 6: ...iv BE1 81O U Introduction 9137300990 Rev J This page intentionally left blank...

Страница 7: ...AND INDICATORS 2 1 INTRODUCTION 2 1 FRONT PANEL 2 1 CIRCUIT BOARD 2 2 Multiplier Settings 2 3 Cycles Seconds Settings 2 3 SECTION 3 FUNCTIONAL DESCRIPTION 3 1 INTRODUCTION 3 1 FUNCTIONAL DESCRIPTION 3...

Страница 8: ...Rev J SECTION 5 TESTING 5 1 INTRODUCTION 5 1 TEST EQUIPMENT 5 1 OPERATIONAL TEST 5 1 Frequency Selector Settings 5 2 Definite Time Delay Cycles 5 3 Definite Time Delay Seconds 5 3 Undervoltage Inhibi...

Страница 9: ...cy BE1 81O U relays with one or two setpoints are supplied in an S1 case Relays with three or four setpoints are supplied in an M1 case Time Delays Each definite time delay setting can be adjusted for...

Страница 10: ...gle phase sensing input 3 100 120 Vac 40 to 70 Hz nominal sensing range E One normally open output relay per setpoint E1 Definite time delay selectable for cycles or seconds J 125 Vdc or 120 Vac relay...

Страница 11: ...c 3 9 W 24 6 VA The type L power supply initially requires 14 Vdc to begin operating Once operating the voltage may be reduced to 12 Vdc and operation will continue Relay Outputs One relay output is p...

Страница 12: ...etpoint Actual time delay is the sum of the elapsed time for three cycles of the input frequency timing circuits require three cycle continuous excursion through the setpoint plus the time for the plo...

Страница 13: ...greater than 250 volts and input power supply voltages greater than 150 volts GOST R Gost R certified No POCC US ME05 B03391 complies with the relevant standards of Gosstandart of Russia Issued by ac...

Страница 14: ...1 6 BE1 81O U General Information 9137300990 Rev J Figure 1 2 Inverse Time Overfrequency Characteristic Curves...

Страница 15: ...6 0 8 0 4 0 3 0 2 0 7 6 0 7 0 9 0 5 0 4 0 3 0 8 0 2 0 9 6 7 8 5 4 3 2 1 0 D2645 09 04 07 97 0 1 10 Time Delay Setting Time in seconds 0 10 0 01 1 00 10 00 100 00 Frequency Difference From Setpoint Hz...

Страница 16: ...1 8 BE1 81O U General Information 9137300990 Rev J This page intentionally left blank...

Страница 17: ...when the sensed voltage decreases below the setting of this multi turn potentiometer The Undervoltage Inhibit Control has a setting range of 40 to 120 Vac The BE1 81O U is delivered with the control s...

Страница 18: ...y or overfrequency condition is detected the corresponding pickup indicator lights and stays lit until the frequency returns to a non trip level I Time Delay Selector Switches A set of two thumbwheel...

Страница 19: ...7 1 is placed in the up position and S7 2 is placed in the down position A times 10 multiplier is also obtained when S7 1 is placed in the down position and S7 2 is placed in the up position For a tim...

Страница 20: ...2 4 BE1 81O U Controls and Indicators 9137300990 Rev J This page intentionally left blank...

Страница 21: ...meter accessed through the front panel is used to adjust the undervoltage inhibit level from 40 to 120 Vac BE1 81O U relays are delivered with an undervoltage inhibit setting of 80 Vac Zero Crossing L...

Страница 22: ...3 2 BE1 81O U Functional Description 9137300990 Rev J Figure 3 1 BE1 81O U Functional Block Diagram...

Страница 23: ...CD number that represents the actual sensed frequency with an accuracy of 0 01 Hz within the 30 to 80 Hz limits The BCD frequency data bus passes this data to the frequency comparator logic of each se...

Страница 24: ...in the up position and S7 2 is placed in the down position A times 10 multiplier is also obtained when S7 1 is placed in the down position and S7 2 is placed in the up position For a times 100 X100 m...

Страница 25: ...are energized open during normal operation If the power supply output fails or operating power is removed from the relay the power supply status output relay de energizes and the contacts close Target...

Страница 26: ...3 6 BE1 81O U Functional Description 9137300990 Rev J This page intentionally left blank...

Страница 27: ...Always be sure that external operating conditions are stable before removing a relay from service Also ensure that connecting plugs are installed before replacing the case cover MOUNTING Because the...

Страница 28: ...4 2 BE1 81O U Installation 9137300990 Rev J Figure 4 1 S1 Case Panel Cutting Diagram Semi Flush Mounting...

Страница 29: ...9137300990 Rev J BE1 81O U Installation 4 3 Figure 4 2 S1 Case Panel Cutting Drilling Diagram Projection Mounting Rear View...

Страница 30: ...4 4 BE1 81O U Installation 9137300990 Rev J D2853 21 06 15 99 Figure 4 3 S1 Case Cover Dimensions Front View...

Страница 31: ...9137300990 Rev J BE1 81O U Installation 4 5 Figure 4 4 S1 Case Dimensions Rear View...

Страница 32: ...4 6 BE1 81O U Installation 9137300990 Rev J D2853 22 06 15 99 Figure 4 5 S1 Case Dimensions Semi Flush Mounting Side View...

Страница 33: ...9137300990 Rev J BE1 81O U Installation 4 7 Figure 4 6 S1 Case Dimensions Projection Mounting Side View...

Страница 34: ...nstallation 9137300990 Rev J 25 6 4 DIA 14 25 7 13 3 03 6 06 7 31 14 63 5 69 2 84 154 0 77 0 185 7 371 5 144 5 72 1 4 PLACES 362 0 181 0 2 16 93 D1427 11 Figure 4 7 M1 Case Panel Cutting Diagram Semi...

Страница 35: ...9137300990 Rev J BE1 81O U Installation 4 9 Figure 4 8 M1 Case Panel Cutting Drilling Diagram Projection Mounting Double Ended Rear View...

Страница 36: ...4 10 BE1 81O U Installation 9137300990 Rev J Figure 4 9 M1 Case Cutting Drilling Diagram Projection Mounting Single Ended Rear View...

Страница 37: ...9137300990 Rev J BE1 81O U Installation 4 11 D2856 02 06 15 99 Figure 4 10 M1 Case Cover Dimensions Front View...

Страница 38: ...4 12 BE1 81O U Installation 9137300990 Rev J 14 69 5 56 141 3 373 1 1 2 9 10 20 19 12 11 D1427 09 07 09 93 Figure 4 11 M1 Case Dimensions Rear View...

Страница 39: ...9137300990 Rev J BE1 81O U Installation 4 13 Figure 4 12 M1 Case Dimensions Semi Flush Mounting Side View...

Страница 40: ...Installation 9137300990 Rev J D2856 21 06 15 99 DETAIL A A SHOWING THE ADDITION OF WASHERS OVER THE BOSS TO TIGHTEN THE RELAY AGAINST THE PANEL CASE PANEL Figure 4 13 M1 Case Dimensions Projection Mou...

Страница 41: ...pens the normally open trip contact circuits and short circuits the normally closed trip contact circuits before opening the power and sensing circuits Incorrect wiring may result in damage to the rel...

Страница 42: ...perly contact Technical Sales Support at Basler Electric to coordinate repairs STORAGE This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in excess...

Страница 43: ...Frequency Pickup 1 Connect the relay as shown in Figure 5 1 2 Adjust Selector Switch S7 for setpoint 1 located on the definite time circuit board controlling setpoint 1 to obtain a time delay in cycle...

Страница 44: ...requency Selector Switch 51 11 3 Apply operating power to the relay 4 Apply 60 Hz voltage to the relay sensing input The level of voltage must exceed the setting of the adjustable front panel Undervol...

Страница 45: ...itch S7 for setpoint 1 located on the definite time circuit board controlling setpoint 1 to obtain a time delay in seconds with a x1 multiplier S7 1 down S7 2 down and S7 3 down 3 Adjust the front pan...

Страница 46: ...not light and the setpoint 1 output relay should not trip 7 Increase the level of the sensing input voltage until it exceeds the level of the undervoltage inhibit setting The Undervoltage Inhibit indi...

Страница 47: ...ROUTE 143 BOX 269 HIGHLAND IL 62249 USA http www basler com info basler com PHONE 1 618 654 2341 FAX 1 618 654 2351...