background image

9171400990 Rev G 

BE1-59N General Information 

1-1 

SECTION 1 

 GENERAL INFORMATION 

PURPOSE 

The available fault current for single-phase-to-ground faults is very limited for ungrounded systems and 
systems, which are grounded through a high resistance. This current limiting reduces the possibility of 
extensive equipment damage, and eliminates the need for a neutral breaker by reducing the fault current 
below the level required to sustain an arc. However, it remains important to detect and isolate single-
phase-to-ground faults in order to prevent their evolution into more dangerous faults such as phase-to-
phase-to-ground and three-phase-to-ground faults. Sensitive voltage relays can be used to detect ground 
faults where the fault current is very small. The BE1-59N Ground Fault Overvoltage Relay is especially 
suited to this task. 

APPLICATION 

High Resistance Grounding 

A common method of grounding an ac generator is to connect a distribution transformer between the 
neutral of the generator and the station ground. The distribution transformer's primary voltage rating is 
equal to, or greater than, the generators rated line-to-neutral voltage. The distribution transformer 
secondary is rated at 200/240 Vac or 100/120 Vac, and a resistor is connected across the secondary 
winding. When reflected through the transformer, the resistor is effectively a high resistance. 

 

 

 

 

 

 

R

p

 = R

s

 x N

2

 

 

 

 

Where: 

R

p

 is the effective primary resistance 

 

 

 

 

R

s

 is the actual value of the secondary resistor 

 

 

 

 

N is the turns ratio of the distribution transformer 

To determine resistor sizing: 

  Determine the thermal limit P (in watts) of the voltage transformers. 

 Use 

R

Vpri

V

=

2

sec)

(

 to determine resistance in ohms, where Vsec = 120 x 3 = 360V. This assumes a 

120V VT secondary in a worst-case condition. 

  Size the watt rating of the resistor for 1/3 of the VT thermal limit to keep the resistor from excessive 

heating. A smaller watt rating can be used if tripping for a ground condition. 

Available single-phase-to-ground fault current at the generator terminals is greatly reduced by the high 
effective resistance of the distribution transformer and secondary resistor. The distribution transformer 
provides isolation for the protection scheme and reduces the voltage to a convenient level. 

The BE1-59N Ground Fault Overvoltage Relay is connected across the secondary resistor to detect the 
increase in voltage across the distribution transformer caused by a ground fault in the generator stator 
windings. A ground fault at the generator terminals will result in rated line-to-neutral voltage across the 
transformer primary, while ground faults near the neutral will result in lower voltages. The overvoltage 
relay setpoint must be higher than any neutral voltage caused by normal unbalances in order to avoid 
nuisance trips. This will allow a certain percentage of the stator windings to go unprotected by the 
overvoltage relay. The overvoltage relay function typically protects 90 to 95% of the generator stator 
windings. 

The BE1-59N Ground Fault Overvoltage Relay monitors the fundamental frequency (50 or 60 Hz) 
voltage, which accompanies a ground fault, but is insensitive to the third harmonic voltage present during 
normal operation. One hundred percent protection of the generator stator windings is obtainable with the 
optional overlapping undervoltage element. The under voltage element is tuned to the third harmonic 
voltage which is present in the generator neutral under normal conditions. The undervoltage element 
detects the reduction of the normal third harmonic voltage, which accompanies a ground fault near the 
neutral point of the generator. 

An undervoltage inhibit feature is included with the third harmonic undervoltage element. This feature 
supervises the operation of the ground fault relay to prevent operation during startup and shutdown by 
monitoring the generator terminal voltage. 

Содержание BE1-59N

Страница 1: ...INSTRUCTION MANUAL FOR GROUND FAULT OVERVOLTAGE RELAY BE1 59N P0050 20 Publication 9171400990 Revision G 09 07 ...

Страница 2: ......

Страница 3: ...ntrols and Indicators Functional Description Installation Testing WARNING To avoid personal injury or equipment damage only qualified personnel should perform the procedures in this manual NOTE Be sure that the relay is hard wired to earth ground with no smaller than 12 AWG copper wire attached to the ground terminal on the rear of the unit case When the relay is configured in a system with other ...

Страница 4: ...on or operation The availability and design of all features and options are subject to modification without notice Should further information be required contact Basler Electric BASLER ELECTRIC ROUTE 143 BOX 269 HIGHLAND IL 62249 USA http www basler com info basler com PHONE 1 618 654 2341 FAX 1 618 654 2351 CONFIDENTIAL INFORMATION of Basler Electric Highland Illinois USA It is loaned for confide...

Страница 5: ...02 Revised the power supply information in Sections 1 and 3 E 12 01 Updated power supply information in the style chart on page 1 3 and in the example on page 1 2 Updated pickup voltage ranges and accuracies on page 1 4 Updated power supply description paragraphs on page 3 3 Updated unit case covers on pages 4 9 and 4 10 Updated drawings of front cover to show the new pushbutton switches instead o...

Страница 6: ...iv BE1 59N Introduction 9171400990 Rev G This page intentionally left blank ...

Страница 7: ...NDICATORS 2 1 INTRODUCTION 2 1 SECTION 3 FUNCTIONAL DESCRIPTION 3 1 INTRODUCTION 3 1 INPUTS 3 1 FILTERS 3 1 OVERVOLTAGE COMPARATOR 3 1 DEFINITE TIME DELAY OPTIONAL 3 1 INVERSE TIME DELAY OPTIONAL 3 2 REFERENCE VOLTAGE CIRCUIT 3 2 UNDERVOLTAGE ELEMENT OPTIONAL 3 2 Undervoltage Operation 3 2 Undervoltage Inhibit 3 2 OUTPUTS 3 2 PUSH TO ENERGIZE OUTPUT PUSHBUTTONS 3 2 POWER SUPPLY STATUS OUTPUT 3 3 P...

Страница 8: ...vi BE1 59N Introduction 9171400990 Rev G This page intentionally left blank ...

Страница 9: ...to keep the resistor from excessive heating A smaller watt rating can be used if tripping for a ground condition Available single phase to ground fault current at the generator terminals is greatly reduced by the high effective resistance of the distribution transformer and secondary resistor The distribution transformer provides isolation for the protection scheme and reduces the voltage to a con...

Страница 10: ...curs the BE1 59N Ground Fault Overvoltage Relay will detect the presence of the secondary zero sequence voltage 3VO The BE1 59N Ground Fault Overvoltage Relay greatly reduces the risk of equipment damage by detecting and isolating the first ground on an ungrounded system Figure 1 1 Ungrounded 3 Phase 3 Wire System MODEL AND STYLE NUMBER BE1 59N electrical characteristics and operational features a...

Страница 11: ...th 1 to 20 Vac pickup range F Two output relays with normally open NO contacts one overvoltage and one undervoltage F6 Inverse time delay for overvoltage and definite time delay for undervoltage J Relay control power is 125 Vdc or 120 Vac nominal D Two current operated target indicators one per function 2 Undervoltage element range 0 1 to 2 5 Vac low range with sensing input 5 S Push to energize o...

Страница 12: ...or a voltage level that exceeds the pickup setting by 5 or 1 volt whichever is greater Definite Adjustable from 00 1 to 99 9 seconds in steps of 0 1 seconds Accuracy is within 2 or 100 milliseconds whichever is greater A setting of 00 0 provides instantaneous timing Inverse Response time decreases as the difference between the monitored voltage and the setpoint increases The inverse time character...

Страница 13: ...rated targets may be specified Internally operated targets should be selected when normally closed NC output contacts are specified Current Operated Targets Minimum Rating 200 mA flowing through the trip circuit Continuous Rating 3 A 1 Second Rating 30 A 2 Minute Rating 7 A Type Tests Shock Withstands 15 G in each of three mutually perpendicular planes without structural damage or performance degr...

Страница 14: ... Agency Recognition Certification UL Recognition UL recognized per Standard 508 File E97033 NOTE Output contacts are not UL recognized for voltages greater than 250 volts Gost R Certification Gost R certified No POCC US ME05 B03391 complies with the relevant standards of Gosstandart of Russia Issued by accredited certification body POCC RU 0001 11ME05 P0050 21 Voltage Difference from Pickup Figure...

Страница 15: ... A 2 4 2 2 2 0 1 8 1 6 1 4 1 2 1 0 0 8 0 6 0 4 0 2 SCALE B 4 8 4 4 4 0 3 6 3 2 2 8 2 4 2 0 1 6 1 2 0 8 0 4 SCALE C 12 11 10 9 8 7 6 5 4 3 2 1 SCALE D 24 22 20 18 16 14 12 10 8 6 4 2 Voltage Difference from Pickup Figure 1 4 Undervoltage Inverse Time Curves ...

Страница 16: ...1 8 BE1 59N General Information 9171400990 Rev G This page intentionally left blank ...

Страница 17: ...A Overvoltage Pickup Adjustment A multiturn potentiometer that sets the overvoltage comparator threshold voltage Continuously adjustable over the range indicated by the style chart B Overvoltage Pickup LED A red LED that illuminates when overvoltage exceeds the pickup setting C Overvoltage Time Dial Pushbutton switch that selects the desired overvoltage output delay either definite time from 00 1 ...

Страница 18: ...These pushbuttons allow manual actuation of the output relays Output relay actuation is achieved by inserting a nonconductive rod through the front panel access holes I Undervoltage Pickup LED A red LED that illuminates when undervoltage exceeds the pickup setting J Undervoltage Pickup Adjustment A multiturn potentiometer that sets the undervoltage comparator threshold voltage Continuously adjusta...

Страница 19: ...B rejection of the fundamental OVERVOLTAGE COMPARATOR The overvoltage comparator circuit receives a sensing voltage from the band pass filter and a reference voltage from the front panel setting The comparator determines within five cycles if the fundamental frequency 50 or 60 hertz is less than or greater than the reference setting When the input exceeds the setting the resulting comparator outpu...

Страница 20: ...f the voltage level swings above the reference setting before the delay timer has cycled the output contacts reset within 7 0 cycles In the event that both trip conditions undervoltage and overvoltage are present the undervoltage response is inhibited The third harmonic pickup setting i e UNDERVOLTAGE PICKUP is a front panel mounted potentiometer continuously adjustable on the high range from 0 5 ...

Страница 21: ...nd reset targets consist of red LED indicators located on the relay front panel A latched target is reset by operating the target reset switch on the front panel If relay operating power is lost any illuminated latched targets are extinguished When relay operating power is restored the previously latched targets are restored to their latched state A relay can be equipped with either internally ope...

Страница 22: ...3 4 BE1 59N Functional Description 9171400990 Rev G This page intentionally left blank ...

Страница 23: ...minimum current of 200 milliamperes must flow through the output trip circuit If a wiring insulation test is required remove the connection plugs and withdraw the relay from its case MOUNTING Because the relay is of solid state design it does not have to be mounted vertically Any convenient mounting angle may be chosen Panel cutting and drilling dimensions are shown in Figures 4 1 and 4 2 Case dim...

Страница 24: ...4 2 BE1 59N Installation 9171400990 Rev G Figure 4 1 Panel Cutting Drilling Semi Flush Case ...

Страница 25: ...9171400990 Rev G BE1 59N Installation 4 3 Figure 4 2 Panel Cutting Drilling Double Ended Projection Mount Case ...

Страница 26: ...4 4 BE1 59N Installation 9171400990 Rev G D1427 27 12 04 01 Figure 4 3 Case Dimensions Side View Double Ended Semi Flush Case ...

Страница 27: ...9171400990 Rev G BE1 59N Installation 4 5 Figure 4 4 Case Dimensions Side View Double Ended Projection Mount Case ...

Страница 28: ...4 6 BE1 59N Installation 9171400990 Rev G Figure 4 5 Case Dimensions Rear View Semi Flush Case ...

Страница 29: ...9171400990 Rev G BE1 59N Installation 4 7 Figure 4 6 Case Dimensions Rear View Projection Mount Case ...

Страница 30: ...4 8 BE1 59N Installation 9171400990 Rev G P0002 12 01 31 01 Figure 4 7 Case Cover Dimensions Front View ...

Страница 31: ...e made with wire no smaller than 14 AWG Typical external connections are shown in Figures 4 8 and 4 9 Typical internal connections are shown in Figure 4 10 1 1 2 2 3 3 1 N O contacts shown Also available with N C contacts Target available with N O contact only 2 Optional auxiliary overvoltage relay available with N O or N C contacts 3 Optional auxiliary undervoltage relay available with N O or N C...

Страница 32: ...4 10 BE1 59N Installation 9171400990 Rev G Figure 4 9 Sensing Input Connections ...

Страница 33: ...9171400990 Rev G BE1 59N Installation 4 11 Figure 4 10 Typical Internal Connection Diagram with Optional Normally Open Output Contacts ...

Страница 34: ... Basler Electric to coordinate repairs STORAGE This protective relay contains aluminum electrolytic capacitors which generally have a life expectancy in excess of 10 years at storage temperatures less than 40 C 104 F Typically the life expectancy of a capacitor is cut in half for every 10 C rise in temperature Storage life can be extended if at one year intervals power is applied to the relay for ...

Страница 35: ...fied tolerances When evaluating results consider three prominent factors Test equipment accuracy Testing method External test set components tolerance level OPERATIONAL TEST Step 1 Perform test setup Figure 5 1 and apply power to the relay Verify that the POWER LED is ON and that the power supply status contact is open Figure 5 1 Typical Test Setup Step 2 Set all TIME DIALS if any to the zero posi...

Страница 36: ...e ΔV of interest Step 10 Press and release S2 of Figure 5 1 to assure that K1 is de energized Reset the timer Press S1 The timer recorded by the counter should be within 5 or 25 milliseconds whichever is greater of the time given in Figure 1 3 for the particular ΔV of the test Step 11 By changing ΔV steps 9 and 10 may be repeated to verify any segment of the characteristic curve that is of interes...

Страница 37: ...e step change and the resulting output response Step 20 Set the UNDERVOLTAGE TIME DIAL to the desired characteristic curve Reference Figure 1 4 Step 21 Adjust the voltage output of T2 to twice that of T1 Step 22 Decrease the voltage of T1 by an amount that represents any ΔV of interest Step 23 Press and release S2 of Figure 5 1 to assure that K1 is de energized Reset the timer Press S1 The time re...

Страница 38: ...5 4 BE1 59N Testing 9171400990 Rev G This page intentionally left blank ...

Страница 39: ...ROUTE 143 BOX 269 HIGHLAND IL 62249 USA http www basler com info basler com PHONE 1 618 654 2341 FAX 1 618 654 2351 ...

Отзывы: