2-4
BE1-50/51B Controls and Indicators
9252000991 Rev N
Locator
Control or Indicator
Function
K
Auxiliary Output
Jumper Terminations
Configures the auxiliary output contacts to close with either the
instantaneous (50) trip and/or the timed (51) trip.
Jumper E2 to E1A to close the auxiliary contact with the timed (51)
trip. This jumper is yellow and factory installed to close the
auxiliary output contacts with the timed trip.
Jumper E3 to E1B to close the auxiliary contact with the
instantaneous (50) trip. This jumper is blue and factory installed to
close the auxiliary output contacts with the instantaneous trip.
Users with unit revision R and previous in units 9252000100
through 109, refer to Section 6 for the location of the auxiliary
output jumper terminations.
Users with BE1-50/51B unit revisions Q, R, and S in 100 series
relays and unit revisions H and previous in 200 series relays, refer
to Section 6 for the location of the auxiliary output jumper
terminations and the location of SW3. (Note: In all previous
revisions, the reference designator for SW3 was SW8.)