Fault Reporting
BE1-11
g
Table 83. Legend for Figure 150
Locator
Description
A
A fault summary report and an oscillograph record are triggered when the Pickup logic
expression becomes true.
B
During the time that the Trip expression is true, targets are logged from each of the
protective functions that reach a trip state. If a protective function is not being used for
tripping purposes, the associated target function can be disabled through BESTCOMS
Plus
.
C
Fault clearing time is calculated as the duration of the time that the Pickup logic expression
is true.
D
Breaker operate time is calculated as the time from when the Trip logic expression becomes
true until the fast current detector senses that the breaker has successfully interrupted the
current in all poles of the breaker.
E
A second oscillographic record is triggered to record the end of the fault if the Pickup logic
expression remains in the true state at the time that the first oscillographic record ends. This
second record will have from ¼ to five cycles of pre-trigger data depending upon when the
Pickup logic expression becomes false.
F
Recorded fault current, voltage, and distance magnitudes are displayed on the Targets
screen of the front-panel display. The same information including phase voltage frequency,
auxiliary voltage frequency, and voltage and current angles are recorded in the fault
summary report. The magnitude, angle, and distance results are based on data captured
two cycles after the trip output goes true. This two-cycle delay allows the line transients to
settle to provide data that is more accurate. The post fault current vectors are compared to
pre-fault current vectors captured three cycles prior to protective pickup to perform distance
calculations. If the Trip expression does not become true, the fault was cleared by a down-
stream device. For these pickup-only events, fault current, voltage, angle, and distance
recorded in the fault summary report will be for the power system cycle ending two cycles
prior to the end of the fault record. This is also the case if the fault record was triggered
through BESTCOMS
Plus
.
G
During the time that the Pickup expression is true, the red Trip LED on the front panel
flashes indicating that the BE1-11
g
is picked up.
H
During the time the Trip expression is true, the red Trip
LED on the front panel lights
steadily indicating that the BE1-11
g
is in a tripped state. If targets have been logged for the
fault, the Trip LED is sealed in until the targets have been reset.
I
Breaker operations and interruption duty functions are driven by the breaker status function.
The operations counter is incremented on breaker opening. The magnitudes of the currents
that are used for accumulating breaker duty are recorded for the power system cycle ending
when the breaker status changes state. Thus, breaker duty is accumulated every time that
the breaker opens even if it is not opening under fault.
J
Setting group changes are blocked when the Pickup expression is true to prevent protective
functions from being reinitialized with new operating parameters while a fault is occurring.
Содержание BE1-11g
Страница 1: ...INSTRUCTION MANUAL FOR BE1 11g Generator Protection System Publication 9424200994 Revision U Jul 17...
Страница 2: ......
Страница 21: ...9424200994 Rev U 9 BE1 11g Introduction Figure 1 Style Chart...
Страница 22: ...10 9424200994 Rev U Introduction BE1 11g...
Страница 36: ...24 9424200994 Rev U Quick Start BE1 11g...
Страница 44: ...32 9424200994 Rev U Controls and Indicators BE1 11g...
Страница 54: ...42 9424200994 Rev U Contact Inputs and Outputs BE1 11g...
Страница 61: ...9424200994 Rev U 49 BE1 11g Overexcitation 24 Protection Figure 40 Inverse Time Delay and Reset Time...
Страница 62: ...50 9424200994 Rev U Overexcitation 24 Protection BE1 11g...
Страница 68: ...56 9424200994 Rev U Sync Check 25 Protection BE1 11g...
Страница 74: ...62 9424200994 Rev U Phase Undervoltage 27P Protection BE1 11g...
Страница 82: ...70 9424200994 Rev U Negative Sequence Voltage 47 Protection BE1 11g...
Страница 88: ...76 9424200994 Rev U Phase Overvoltage 59P Protection BE1 11g...
Страница 94: ...82 9424200994 Rev U Auxiliary Overvoltage 59X Protection BE1 11g...
Страница 96: ...84 9424200994 Rev U Stator Ground 64G Protection BE1 11g...
Страница 100: ...88 9424200994 Rev U Vector Jump 78V Protection BE1 11g...
Страница 106: ...94 9424200994 Rev U Frequency 81 Protection BE1 11g...
Страница 150: ...138 9424200994 Rev U Power 32 Protection BE1 11g...
Страница 154: ...142 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Protection BE1 11g...
Страница 158: ...146 9424200994 Rev U Distance 21 Protection BE1 11g...
Страница 170: ...158 9424200994 Rev U Resistance Temperature Detector 49RTD Protection BE1 11g...
Страница 174: ...162 9424200994 Rev U Analog Input Protection BE1 11g...
Страница 192: ...180 9424200994 Rev U Logic Timers 62 BE1 11g...
Страница 198: ...186 9424200994 Rev U Breaker Control Switch 101 BE1 11g...
Страница 206: ...194 9424200994 Rev U Setting Groups BE1 11g...
Страница 236: ...224 9424200994 Rev U Alarms BE1 11g...
Страница 238: ...226 9424200994 Rev U Differential Reporting BE1 11g...
Страница 248: ...236 9424200994 Rev U Demands BE1 11g...
Страница 250: ...238 9424200994 Rev U Load Profile BE1 11g...
Страница 254: ...242 9424200994 Rev U Power Quality BE1 11g...
Страница 262: ...250 9424200994 Rev U Trip Circuit Monitor 52TCM BE1 11g...
Страница 272: ...260 9424200994 Rev U BESTnet Plus BE1 11g Figure 188 Power Quality Page...
Страница 274: ...262 9424200994 Rev U Mounting BE1 11g Figure 190 J Type Case Side Dimensions...
Страница 280: ...268 9424200994 Rev U Mounting BE1 11g Figure 196 Retrofit Mounting Plate Basler P N 9424200073 Part 2...
Страница 282: ...270 9424200994 Rev U Mounting BE1 11g Figure 198 H1 Rack Mount Case Dimensions...
Страница 283: ...9424200994 Rev U 271 BE1 11g Mounting Figure 199 H1 Panel Mount Case Dimensions...
Страница 289: ...9424200994 Rev U 277 BE1 11g Mounting Figure 206 Dovetailing Procedure...
Страница 290: ...278 9424200994 Rev U Mounting BE1 11g...
Страница 297: ...9424200994 Rev U 285 BE1 11g Terminals and Connectors Figure 215 Example of Reversed CT Polarity...
Страница 298: ...286 9424200994 Rev U Terminals and Connectors BE1 11g...
Страница 304: ...292 9424200994 Rev U Typical Connections BE1 11g...
Страница 324: ...312 9424200994 Rev U BESTCOMSPlus Software BE1 11g...
Страница 344: ...332 9424200994 Rev U BESTlogic Plus BE1 11g...
Страница 354: ...342 9424200994 Rev U Communication BE1 11g Figure 263 Modbus Mapping Screen...
Страница 367: ...9424200994 Rev U 355 BE1 11g Timekeeping Figure 275 Front Panel Circuit Board Backup Battery Location...
Страница 370: ...358 9424200994 Rev U Timekeeping BE1 11g...
Страница 374: ...362 9424200994 Rev U Device Information BE1 11g...
Страница 392: ...380 9424200994 Rev U Configuration BE1 11g...
Страница 396: ...384 9424200994 Rev U Introduction to Testing BE1 11g...
Страница 408: ...396 9424200994 Rev U Commissioning Testing BE1 11g...
Страница 422: ...410 9424200994 Rev U Sync Check 25 Test BE1 11g...
Страница 426: ...414 9424200994 Rev U Phase Undervoltage 27P Test BE1 11g...
Страница 442: ...430 9424200994 Rev U Phase Overvoltage 59P Test BE1 11g...
Страница 454: ...442 9424200994 Rev U Auxiliary Overvoltage 59X Test BE1 11g...
Страница 458: ...446 9424200994 Rev U Vector Jump 78V Test BE1 11g...
Страница 466: ...454 9424200994 Rev U Frequency 81 Test BE1 11g...
Страница 496: ...484 9424200994 Rev U Inverse Overcurrent 51 Test BE1 11g...
Страница 516: ...504 9424200994 Rev U Phase Current Differential 87 Test BE1 11g...
Страница 520: ...508 9424200994 Rev U Neutral Current Differential 87N Test BE1 11g...
Страница 526: ...514 9424200994 Rev U Power 32 Test BE1 11g...
Страница 530: ...518 9424200994 Rev U Loss of Excitation Reverse Var Based 40Q Test BE1 11g...
Страница 534: ...522 9424200994 Rev U Distance 21 Test BE1 11g...
Страница 560: ...548 9424200994 Rev U Virtual Control Switches 43 Test BE1 11g...
Страница 570: ...558 9424200994 Rev U Logic Timers 62 Test BE1 11g...
Страница 584: ...572 9424200994 Rev U Troubleshooting BE1 11g...
Страница 614: ...602 9424200994 Rev U Specifications 25 Hz Operation BE1 11g BESTlogic Plus Update Rate cycle...
Страница 622: ...610 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 357 Time Characteristic Curve A Standard Inverse BS 142...
Страница 630: ...618 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 365 Time Characteristic Curve G Long Time Inverse BS 142...
Страница 633: ...9424200994 Rev U 621 BE1 11g Time Curve Characteristics Figure 368 Time Characteristic Curve B Very Inverse BS 142...
Страница 638: ...626 9424200994 Rev U Time Curve Characteristics BE1 11g Figure 373 Time Characteristic Curve C Extremely Inverse BS 142...
Страница 672: ...660 9424200994 Rev U RTD Module BE1 11g...
Страница 694: ...682 9424200994 Rev U BESTCOMSPlus Settings Loader Tool BE1 11g...
Страница 705: ......