a. The MVC-300 is designed for 'through-the-panel' mounting.  Refer to the drilling template of
Figure 3-1 and to the outline drawing Figure 3-2.  The front panel of the MVC-300 is detachable by
removal of the knob and locking nut from the MANUAL VOLTAGE ADJUST control and the four
corner screws.  The MVC-300 can be installed in any position without affecting its operating charac-
teristics, however, it is preferable that the device be mounted vertically to improve ventilation.  The
MANUAL VOLTAGE ADJUST control can be removed and installed remotely by using terminals 14,
15 and 16 or a Basler motor operated control (MOC 2) with a 10 k ohm control element can be
connected to terminal 14, 15, and 16.  See Figure 3-3 Interconnection Diagram.  It is imperative that
the MVC-300 be connected to provide an output which corresponds to the voltage regulator ratings
in order to prevent damage to the MVC-300 or the regulator.  When the MVC-300 and voltage
regulator are properly matched, the MVC-300 provides smooth control of the generator output
voltage in the manual mode.

b. The chart (Table 3-1) is used to determine the appropriate input voltage and to select the output
voltage.  Based on voltage regulator model, from column 1, the proper voltage input rating from
column 3 is selected and connections are made between the generator and terminals 23 and 24
which will supply the specified voltage. The MVC-300 has a wire jumper connected from the printed
circuit board of the MVC-300 to the barrier strip. Column 4 indicates the correct terminal for this
jumper connection.

SECTION 3

INSTALLATION AND OPERATION

3-1. INSTALLATION

Содержание 9 1210 00 106

Страница 1: ...ELECTRONIC MANUAL VOLTAGE CONTROL Model MVC 300 Part Number 9 1210 00 106 Publication Number 9 1210 00 993 Date July 1993 Revision F July 1996...

Страница 2: ...c Company Highland IL It is loaned for confidential use Subject to return on request and with the mutual understanding that it will not be used in any manner detrimental to the interests of Basler Ele...

Страница 3: ......

Страница 4: ...switch are provided on the front panel Table 1 1 provides the electrical and physical specifications of the MVC 300 Table 1 1 Specifications Input Power 120 Vac 10 Single Phase 50 320 Hz 240 Vac 10 S...

Страница 5: ...build up circuit relinquishes control to the MANUAL VOLTAGE ADJUST control on the front panel c The AUTO OFF MAN voltage control mode switch allows transfer from the voltage regulator to the Manual V...

Страница 6: ...3 3 Interconnection Diagram It is imperative that the MVC 300 be connected to provide an output which corresponds to the voltage regulator ratings in order to prevent damage to the MVC 300 or the reg...

Страница 7: ...3 2 Figure 3 1 Panel Drilling Template...

Страница 8: ...3 3 Figure 3 2 MVC 300 Outline Drawing...

Страница 9: ...3 4 Figure 3 3 MVC 300 Interconnection Diagram Typical...

Страница 10: ...and place the AUTOMATIC OFF MANUAL voltage control mode switch in MANUAL position Note that the voltage may be unstable hunting if the MANUAL VOLTAGE ADJUST control is set below 30 Vac c Allow the gen...

Страница 11: ...UAL VOLTAGE ADJUST control fully counter clockwise CCW Remove the 120 Vac source from Terminals 23 and 24 and select 32 volt operation by moving the jumper to Terminal 32 Apply the 120 Vac source to T...

Страница 12: ...ch test procedure Due to a protective coating repair replacement of individual components on the printed circuit board assembly should not be attempted and the complete replacement of the board is rec...

Страница 13: ...e does not build up proceed to Step 4 Step 4 Verify that internal fuses F1 and F2 are good If either fuse is defective or blown replace fuse and proceed to Step 5 If both fuses are not defective or bl...