BASENHURT TEBAS EFka110 Скачать руководство пользователя страница 14

 

14 

 

 
 
 
 

Meaning of parameters 

 
P1:
 

This parameter allows to select the measurement type, pH or redox (mV).  
When setting P1=0 (pH reading with two decimal), please note that the two decimal places are visible only 
for pH values below 10, because the display can show up to three digits. However, generally the precision of 
pH measurements with one decimal is sufficient in most applications. 

P2: 

This parameter allows to configure the working mode of level contact:  
0 = NO (normally open, standard configuration) 
1 = NC (normally closed, fail-safe mode) 

P3: 

This parameter allows to store the status of the ON/OFF button at the system shutdown: 
0 = at start-up the pump is always enabled  
1 = at start-up the pump restores its status at shutdown 

P4: 

This parameter allows to set the pump working mode: 
0 = OFF 

 the pump is always off, independently from measured value: this option allows to monitor the 

measurement without intervening, for example during the plant start-up 
1 = ON 

 the pump is always on, independently from measured value: this option is used to manually force 

the dosage, for example during the plant start-up or maintenance 
2 = ON/OFF acid 

 this option is typically used for acidification; the pump activates when the measurement 

exceeds the “working thr½ hysteresis” level, and deactivates when the measurement falls below the 
“working threshold – ½ hysteresis” value 
3 = Proportional acid 

 the pump is definitely active when the measurement is greater than the “working 

thr ½ hysteresis” level, and definitely off when measurement is lower than the “working threshold 
– ½ hysteresis” value, while for measurements between these limits, the operating time of the pump is 
proportional to the distance of measurement from the limits. The time base is fixed (90 seconds) and 
operation follows the trend shown in the table below:

 

Measurement = pH ; Working threshold = 7.20 pH ; Hysteresis = 0.40 pH 

Measure 

<= 7.00 

7.10 

7.20 

7.30 

>= 7.40 

% dosage 

0% 

25% 

50% 

75% 

100% 

Pump ON 

never 

23 seconds 

45 seconds 

67 seconds 

always 

Pump OFF 

always 

67 seconds 

45 seconds 

23 seconds 

never 

4 = ON/OFF chlorine 

 this option is typically used for chloration or alkalinization; the pump activates when 

the measurement is lower than the “working threshold – ½ hysteresis” value, and deactivates when the 
measurement exceeds the “working thr ½ hysteresis” level. 
5 = Proportional chlorine 

 the pump is definitely active when the measurement is lower than the “working 

threshold – ½ hysteresis” value, and definitely off when measurement is greater than the “working threshold 
+ ½ hysteresis” level, while for measurements between these limits, the operating time of the pump is 
proportional to the distance of measurement from the limits. The time base is fixed (90 seconds) and 
operation follows the trend shown in the table below:

 

Measurement = Redox ; Working threshold = 680 mV ; Hysteresis = 20 mV 

Measure 

<= 670 

675 

680 

685 

>= 690 

% dosage 

100% 

75% 

50% 

25% 

0% 

Pump ON 

always 

67 seconds 

45 seconds 

23 seconds 

never 

Pump OFF 

never 

23 seconds 

45 seconds 

67 seconds 

always 

P5: 

This parameter allows to set the working threshold used when the pump operates in automatic control. 

P6: 

This parameter represents the intervention hysteresis around the working threshold; in the case of ON/OFF 
controls it can be set between zero and 2.00 pH (or between zero and 200 mV), while in the case of 
proportional controls the hysteresis must have a value between 0.20 and 1.00 pH(or between 20 and 100mV). 

P7: 

At the device start-up, some electrodes require a stabilization (or polarization) time, during which the 
measurement is not reliable. This parameter allows to set a delay at start-up (in minutes), during which the 
pump is off and the display alternates between the measurement and the “PAU” message. Typically, in the 
case of pH electrode a delay of 1 minute is sufficient, while in the case of redox electrode it is recommended 
to set a delay of at least  20 min. Sometime this standby time is also useful to compensate for hydraulic delays 
that can occur at the plant start-up. Once the set time has elapsed, the pump begins to operate normally. 

P8: 

This parameter allows to set a time limit within which the measure must return to the working threshold value 
(P5), otherwise an alarm is generated. A time between 0 (feature disabled) and 600 min. (10 hours) can be 
set. The alarm time count begins when the system detects a measurement out of range, and automatically 
resets when the measure returns within the threshold value. If the measurement remains outside this 
threshold longer than the set time, an alarm is generated and the display alternates between the measurement 
and the “ALL” message. When the alarm is active, the dosage is disabled and normal operation is resumed 
when the alarm is reset by pressing the ON/OFF button, by turning the pump off and on again, or 
automatically when measurement returns to an acceptable value. This condition may occur due to an 
insufficient dosage, such as not to allow the achievement of the threshold value. 

Содержание TEBAS EFka110

Страница 1: ...1 Pompa perystaltyczna Peristaltic pump EFka110 PL INSTRUKCJA OBS UGI I INSTALACJI EN INSTALLATION AND MAINTENANCE INSTRUCTIONS...

Страница 2: ...zenie elektryczne 4 Panel steruj cy 6 Konfiguracja 6 Kalibracja 8 Utrzymanie 9 Rozwi zywanie problem w 9 INSTALLATION AND MAINTENANCE INSTRUCTIONS Packing list page 11 Technical specifications 11 Prin...

Страница 3: ...e ochronn r kawice odzie okulary itp Pompa musi by obs ugiwana tylko przez wykwalifikowany personel Zawsze nale y u ywa oryginalnych cz ci zamiennych Niezastosowanie si do instrukcji mo e spowodowa us...

Страница 4: ...pH 0 do 1000 mV Redox ZASADA DZIA ANIA Zasada dzia ania pomp perystaltycznych opiera si o ci nienie a nast pnie zwolnienie w w yku wewn trznym przez rolk zamontowan na uchwycie kt ra jest nap dzana p...

Страница 5: ...i na dole po prawej stronie g owicy pompy oznaczon na rysunku ze strza k w d 2 Odetnij w yk PCW i umie nakr tk mocuj c na rurce 3 Zamontuj rurk na sto kowym uchwycie na z czu t ocznym przesuwaj c a do...

Страница 6: ...trz rozdzia Konfiguracja dioda LED szybko miga dioda LED ON zielone wiat o sta e wita o wskazuje normalne dzia anie miga gdy pojawi si alarm KONFIGURACJA Aby skonfigurowa pompy odpowiednio do Twoich p...

Страница 7: ...7 30 7 40 dozowania 0 25 50 75 100 Pompa ON nigdy 23 sekund 45 sekund 67 sekund zawsze Pompa OFF zawsze 67 sekund 45 sekund 23 sekund nigdy 4 ON OFF chlor ta opcja jest zazwyczaj u ywana do chlorowan...

Страница 8: ...ym roztworem pH procedura nie powiedzie si a na wy wietlaczu pojawi si komunikat Err W trakcie normalnej pracy mo liwe jest aby wy wietli warto ci OFFSET naciskaj c i warto ci GAIN naciskaj c aby spra...

Страница 9: ...pierw zwolnij lewe z cze a nast pnie obr uchwyt tak jak pokazano na rysunku Ustaw pomp na ci g prac P4 1 ale zatrzymaj j przyciskiem ON OFF W lewe z cze do nowego w yka do jego obudowy upewniaj c si e...

Страница 10: ...to be handled by qualified personnel only Always use original spare parts for maintenance Failure to follow instructions can cause damage to the equipment and in extreme cases to people Warranty The E...

Страница 11: ...0 to 1000 mV redox PRINCIPLE OF OPERATIONS The principle of operation of the peristaltic pumps is based on the pressure and subsequent release of the internal tube by the roller mounted on the roller...

Страница 12: ...the pump body marked with the exiting arrow 2 Cut the PVC Crystal tube and insert the tube fixing nut onto the tube 3 Mount the tube on the conic hose of the injection fitting pushing it to reach the...

Страница 13: ...the automatic mode is disabled see Configuration section the LED flashes quickly ON LED green light fixed ON indicates normal operations flashes when an alrm occurs CONFIGURATION To configurate the pu...

Страница 14: ...nt is lower than the working threshold hysteresis value and definitely off when measurement is greater than the working threshold hysteresis level while for measurements between these limits the opera...

Страница 15: ...FSET calibration is displayed 4 Press ON OFF to confirm the calibration or wait for a few seconds for exiting without saving and keeping the previous calibration Notes The redox calibration is a singl...

Страница 16: ...le paying attention that the rounded part is positioned inwards Then turn the roller holder clockwise so that the tube is inserted in its seat Insert the right fitting in its seat and secure the trans...

Отзывы: