Base LV-8RS Скачать руководство пользователя страница 2

LV-8RS

Low Voltage Power Distribution Module

The LV-8RS distributes power from a low voltage power source to 8 fused outputs 

through 8 Output Isolation Relay sockets -or- can be configured to provide up to 8 dry 

contact relay outputs. Terminals are provided for control of each output relay by an 

Access Control system. Output devices can be powered separately from the control 

relays by configuring Common Power Jumpers. A 2-pole Disconnect Relay socket 

is provided and easily interfaces with Fire, Life Safety or Alarm Panels to provide 

Emergency Power Disconnect. Relay auxilary contact terminals are provided for alarm 

monitoring of the Disconnect feature.

Each of the 8 outputs includes a removable jumper clip easily configurable for one 

of 3 modes of operation:

  1) D position - Disconnect or Fail Safe operation of the output.

    This means the output is disconnected by the Disconnect Function.

  2) C position - Continuous or Fail Secure operation of the output.

    This means the output is unaffected by the Disconnect Function.

  3) DRY position - A jumper in this position configures the output for dry relay

    contacts. Since an output in this mode is not powered, the jumper blocks the

    installation of a fuse in the corresponding output fuseholder.

The LV-8RS includes red LED indicators at each of the 9 relay positions for identifica

-

tion of energized relays.

The module is 5.00” wide x 8.00” long. The installed height with relays is 2.50”. 

Standoffs are included for mounting the circuit board in a user-supplied enclosure.  

Relays and 3AG-type Fuses are provided separately.  To meet UL Listing require-

ments, the relays selected should be Idec Corp., P/N RH1B-U SPDT or P/N RH2B-U, 

DPDT, 12vdc or 24vdc.

* * *  WARNING  * * *

Turn off all power feeding the module terminals before servicing or changing input/output wiring, removing 

or reinstalling fuses, relays, or jumpers.  Failure to observe this warning may cause electrical shock hazard 

or may damage internal or external circuit components.

The information in this manual is believed to be accurate in all respects. However, BASE Electronics cannot assume 

responsibility for any consequences resulting from the use thereof. The information contained herein is

subject to change and BASE Electronics may issue a revision to incorporate such changes at any time. 

 

INSTALLATION

Locate the unit inside a UL Listed NEMA 1 enclosure (such as a BASE LVPC Low 

Voltage Power Cabinet) close to the source power supply.  Drill (4) 0.187” diameter 

holes to match the (4) corner holes in the printed circuit board.  Push the nylon standoffs 

supplied into each hole and snap the module into place.

Note: To comply with UL294 - Standard For Safety - Access Control System Units 

and the limitations of the UL product Listing, the LV Module should be located within 

the same room as the associated Access Control equipment and interconnect cabling 

to the LV Module inputs. The unit is to be powered from a Class 2 Power-Limited 

UL Listed Source.

POWER SUPPLY WIRING

Common Relay Control and Output Voltage

   If the output devices require a DC 

operating voltage, the Common Power Jumpers can remain intact and only one DC 

power supply needs to be connected to the PWR input terminals. In this mode, the 

DC operating voltage of the control relays, output devices and the power supply must 

match. Example: Output devices = 24VDC Maglocks, Power Supply = 24VDC, Relays 

must also be 24VDC.

Separate Relay Control and Output Voltages

By cutting the Common Power Jumpers, two separate power supplies of like or different 

voltages may be used to power the output devices and control relays. The relay power 

supply must be DC. The output power supply can be either AC or DC.

Connect the power supply input leads to the terminal strip at the lower right side of 

the module as shown in Figure 1. Use a minimum of 18AWG copper conductors for 

this wiring and keep the length to the power supply as short as possible.

The values of the CTL and PWR voltages may be written on the white areas provided 

in the lower right side of the module for easy future reference.

 

Output 

Relay 

Run Power 

Common 

  Power Supply  Power Supply 

Supply Wiring To: 

Power Jumpers

 

DC-1 

DC-1 

PWR 

Uncut

 

DC-1 

DC-2 

(both PWR and CTL) 

Cut

 

AC 

DC 

(both PWR and CTL) 

Cut

OUTPUT MODE CONFIGURATION

Each module includes 8 jumper pins for configuring the mode of operation for each 

of the 8 ouputs. They are installed in the C position from the factory.

C position - Continuous Power Mode

  The output is continuously powered and 

unaffected by the Power Disconnect feature. If all 8 outputs will be configured in the 

C position, there is no need to install a Disconnect Relay in the 2-pole socket.

D position - Disconnect Mode

  The output power will be disconnected by the Discon-

nect Relay when the Fire Panel Interface control circuit is opened. A 2-pole Disconnect 

Relay must be installed in the socket provided.

DRY position - Dry Contact Mode

  The output becomes a dry Form C output. The 

output is not powered or affected by the Power Disconnect feature. Since an output 

in this mode is not powered, the jumper blocks the installation of a fuse in the cor-

responding output fuseholder.

POWER DISCONNECT WIRING

A socket is provided for a 2-pole relay that is used to disconnect the output power PWR 

during facility emergencies. The relay is DC powered from the power feeding the CTL 

terminals. Normally closed dry contacts of a fire or life safety system panel are used to 

control the disconnect relay at the ‘F’ terminals. The alarm contact should be rated for 

the current required by the relay selected (normally less than 50mA at 12VDC).
The auxiliary output contacts of the Disconnect Relay can be monitored. Note that the 

terminals designated NO and NC (shown in Figure 1) stand for Normally Open and 

Normally Closed when the relay is de-energized. The terminal marked ST is a Spare 

Terminal available for termination of an end-of-line resistor if needed.

OUTPUTS AND CONTROLS

Add the operating current ratings for each device to be powered from one output to 

determine the expected operating current flow. Install a fuse for the output that will 

trip when this value is exceeded. The value of the fuse selected for each output may 

be written on the white area below the fuse for easy future reference.

Example A:

  Output 1 - (1) magnetic lock

 

operating current = 0.29A at 12 VDC

 

Install fuse rated just greater than 0.29A = 3/8A or 1/2A

Example B:

  Output 2 - (4) deadbolt locks

 

operating current = (4 x 0.40A) = 1.6A 

 

Install fuse rated just greater than 1.6A = 2A

Wiring to output devices connects to the OUTPUTS terminals. Four terminals are 

provided for each output as follows;

 

#C = output relay Common terminal when in DRY mode

 

 

spare terminal when in C or D modes.

 

NC = output relay Normally Closed terminal, powered when fuse is installed  

 

 

in C or D modes, nonpowered and dry when in DRY mode.

 

NO = output relay Normally Open terminal, powered when fuse is installed  

 

 

in C or D modes, nonpowered and dry when in DRY mode.

 

PC = output power PWR Common terminal in any mode.

Add the operating current ratings for each control relay and install a control fuse that 

will trip when this value is exceeded. The value of the fuse selected may be written 

on the white area below the fuse for easy future reference.

When powering devices over considerable distances, the cabling resistance may be 

so high that the voltage available at the device drops to an unacceptable level.  To 

prevent this from occuring, the system cabling should be designed with adequate 

sized conductors.

Suggested wiring methods for OUTPUTS and CONTROLS are shown in Figure 1.

All fuses must be type 3AG. Output Fuses must be 2.5A maximum or less. Control 

Fuse must be 1.0A Maximum. Fuses are ordered separately - specify desired rating 

when ordering. 

LIGHTNING, TRANSIENT AND NOISE SUPRESSION

Lightning or transient suppression devices may be installed at the LV-8RS output 

terminals to protect control equipment from induced voltages.  A multi-screw, solid 

ground bar should be installed vertically next to the output side of the module for con-

nection of metal oxide varistors, transient suppression diodes, etc. If shielded cable 

is used for output wiring, shield drain wires can be connected to the ground bar for 

line noise suppression. Run a minimum #14AWG green stranded ground wire from 

the ground bar to the closest Service Ground. Grounding bars of the type mentioned 

above can be separately supplied by BASE Electronics.

Отзывы: