background image

LV-8S

Low Voltage Power Distribution Module

The LV-8S distributes power from a low voltage power source to 8 individually fused 

outputs. Terminals are provided for control of each output by an Access Control 

system. A 2-pole Disconnect Relay socket is provided and easily interfaces with Fire, 

Life Safety or Alarm Panels to provide Emergency Power Disconnect. Relay auxilary 

contact terminals are provided for alarm monitoring of the Disconnect feature.  For 

each of the 8 inputs, the user can select a (C) Continuous power bus terminal or a (D) 

Disconnect power bus  terminal when routing wiring to an Access Controller.

The Disconnect Relay and 3AG-type Fuses are provided separately depending on the 

system voltage needed and output device current requirements.  To meet UL Listing 

requirements, the relay selected should be Idec Corp., P/N RH2B-U, DPDT, 12vdc 

or 24vdc.

The module is 3.75” wide x 8.00” long. The installed height with relay is 2.50”. Stand-

offs are included for mounting the circuit board in a user-supplied enclosure.

* * *  WARNING  * * *

Turn off all power feeding the module terminals before servicing or changing input/output wiring, removing 

or reinstalling fuses or relays, or cutting jumpers.  Failure to observe this warning may cause electrical shock 

hazard or may damage internal or external circuit components.

The information in this manual is believed to be accurate in all respects. However, BASE Electronics cannot assume 

responsibility for any consequences resulting from the use thereof. The information contained herein is

subject to change and BASE Electronics may issue a revision to incorporate such changes at any time.

INSTALLATION

Locate the unit inside a NEMA 1 enclosure (such as a BASE LVPC Low Voltage Power 

Cabinet) close to the source power supply.  Drill (4) 0.187” diameter holes to match 

the (4) corner holes in the printed circuit board.  Push the nylon standoffs supplied 

into each hole and snap the module into place.

POWER SUPPLY WIRING

Connect the low voltage power supply input leads to the terminal strip at the lower right 

side of the circuit board as shown in Figure 1. Use a minimum of 18AWG copper con-

ductors for this wiring and keep the length to the power supply as short as possible.

 

V = +DC voltage (12 or 24)

 

C = DC Common

POWER DISCONNECT WIRING

A socket is provided for a 2-pole relay that is used to disconnect the output power 

during facility emergencies. This relay should be wired to dry contacts of a Fire, Life 

Safety or Alarm Panel at the ‘F’ terminals. The emergency alarm contact should be 

rated for the current required by the disconnect relay selected.

MONITORING THE RELAY

The auxiliary output contacts of the Disconnect Relay can be monitored by an alarm 

system. Note that the terminals designated NO and NC (shown in Figure 1) stand for 

Normally Open and Normally Closed when the relay is de-energized. The terminal 

marked ST is a Spare Terminal available for termination of an end-of-line resistor if 

needed.

OUTPUTS AND CONTROLS

NOTE: The maximum recommended operating current at any single LV-8S output 

should not exceed 2.5 Amperes. The maximum recommended total operating current 

(all output currents added) should not exceed 8 Amperes. All fuses must be type 3AG. 

Output Fuses must be 2.5A maximum or less. Fuses are ordered separately - specify 

desired rating when ordering.

Suggested wiring methods for OUTPUTS and CONTROLS are shown in Figure 

1. Wiring to the access control devices connects to the Controls terminals. Three 

terminals are provided for each LV-8S control input. A control contact wired from 

the ‘D’ terminal loses power when the Disconnect Relay is de-energized. A control 

contact wired from the ‘C’ terminal is continuously powered and not affected by the 

Disconnect Relay.

Wiring to the output devices connects to the Output terminals. Two terminals are 

provided for each LV-8S output.

V = the fused output terminal

C = the DC Common terminal

Add the expected operating current ratings for each device to be powered from one 

LV-8S output to determine the expected operating current flow. Install a fuse for the 

output that will trip when this value is exceeded. The value of the fuse selected for each 

output may be written on the white area below the fuse for easy future reference.

Example A: 

Output 1 - (1) magnetic lock

 

operating current = 0.29A at 12 VDC

 

Install fuse rated just greater than 0.29A = 3/8A or 1/2A

Example B: 

Output 2 - (4) deadbolt locks

 

operating current = (4 x 0.40A) = 1.6A 

 

Install fuse rated just greater than 1.6A = 2A

When powering devices over considerable distances, the cabling resistance may be 

so high that the voltage available at the device drops to an unacceptable level.  To 

prevent this from occuring, the system cabling should be designed with adequate sized 

conductors.  Use the Low Voltage System Cabling Design Guide in this manual for 

help in obtaining the desired results.

LIGHTNING, TRANSIENT AND NOISE SUPPRESSION

Lightning or transient suppression devices may be installed at the LV-8S output terminals to protect control equip-

ment from induced voltages.  A multi-screw, solid ground bar should be installed vertically next to the output side 

of the module for connection of metal oxide varistors, transient suppression diodes, etc. If shielded cable is used 

for output wiring, shield drain wires can be connected to the ground bar for line noise suppression. Run a minimum 

#14AWG green stranded ground wire from the ground bar to the closest Service Ground. Grounding bars of the 

type mentioned above can be separately supplied by BASE Electronics.

LOW VOLTAGE SYSTEM CABLING DESIGN GUIDE

With an improperly designed cabling system, the resistance of wire conductors may cause a voltage drop that 

could significantly affect the performance of the powered device. The resistance of a given length of cabling and 

its voltage drop at the given operating voltage can be calculated. This allows the affect on the powered device to 

be estimated with adjustments in conductor size implemented in the design stage.

Example:

A CCTV camera requires 0.29A at 24 VAC and the estimated cable length from the power supply is 800 feet.  

The camera specifications state that the camera will operate properly down to 21.0 VAC (a voltage drop of 3.0 

volts maximum).  What should be the size of the power cable conductors? From the chart below, we observe that 

a pair of 18AWG stranded copper conductors will have a resistance of 2 x 800 feet x 6.48 ohms/1000 feet. Using 

Ohm’s Law: E = I x R

E (voltage dropped) = I (the required current) x R (the cabling resistance)

 

E = (0.29) x (2 x 800 x (6.48/1000)) = 3.007 volts

Subtracting 3.007 volts from 24VAC leaves 20.993 volts available at the camera, an unacceptable level. When 

16AWG conductors are used in the equation: E = (0.29) x (2 x 800 x (3.67/1000)) = 1.703 volts

Subtracting 1.703VAC from 24VAC  leaves 22.297VAC available at the camera. Taking future expansion of a second 

camera into account, the estimator may decide to increase the conductors to #14AWG as follows:

E = (2 x 0.29) x (2 x 800 x (2.31/1000)) = 2.14VAC dropped

When powering inductive devices (relay coils, electric strikes, magnetic locks, etc.), remember to install reversing 

diodes (DC powered) or metal oxide varistors (AC powered) at the device terminals or as recommended by the 

device manufacturer to counter the affect of Counter Magnetic Force (CMF).

Resistance of Copper Conductors

 

Solid Conductors 

Stranded Conductors

 

Wire Gage 

Resistance 

Wire Gage 

Stranding 

Resistance

 

(AWG) 

(Ω/1000’) 

(AWG) 

(#/AWG) 

(Ω/1000’)

 

10 1.00 10 37/26 1.11

 

12 1.59 12 7/20 1.45

 

14 2.53 14 7/22 2.31

 

16 4.02 16 7/24 3.67

 

18 6.39 18 16/30 6.48

 

20 10.15 20 10/30 10.32

 

22 16.14 22  7/30 14.74

 

24 25.67 24  7/32 23.30

Отзывы: