4.4
Programming with miCon-L
Without learning a difficult programming language the
BARTH
®
Mini-PLC can be easily programmed using sim-
ple and vivid graphical function blocks. This block design
meets graphical standards of the latest graphical program-
ming languages.
The miCon-L software suite features programming, simula-
tion and test in one unique software design tool. The flexible
programming option offers a variety of possibilities in indus-
trial, automotive and maritime applications.
Programming the STG-115 follows using the USB port of
your PC with installed miCon-L software suite.
miCon-L also supports full simulation and visualisation ope-
ration modes.
The software provides a variety of visualisation blocks and
interactive elements to control and debug the Mini-PLC.
For detailed information please read the BARTH
®
miCon-L
manual and the BARTH
®
Application Notes on:
www.barth-elektronik.de
4.5
Delivery content
• BARTH
®
Mini-PLC STG-115
• Spring terminal connectors (for supply, input, output)
5
INSTALLATION
5.1
Mounting
The STG-115 must be installed and wired
by a trained technician who knows and
complies with both the universally appli-
cable engineering rules and the regulati-
ons and standards that apply in specific
cases.
The STG-115 is intended for panel mount using four M4
screws to fix the PLC.
Before mounting create a cut-out for the Mini-PLC with the
dimensions 68 x 92 mm.
To fix the PLC place four holes diameter 4.5 mm with the
distances 100 x 80 mm.
To ensure the IP65 protection grade of the
front panel an additional sealing is man-
datory. The sealing has to be applied bet-
ween the front panel and the housing.
The 3M type 5915 is suitable for most
applications.
Please verify the sealing for your applica-
tion! Otherwise the degree of protection
may be insufficient!
Take care to meet the environmental con-
ditions of the STG-115.
After creating the cut-out, place the Mini-PLC properly and
fix it using four M4 screws.
Only use M4 cylinder head type screws
fastening the Mini-PLC, applying a maxi-
mum torque of 0.5 Nm !
Otherwise damage of the front panel may
occur !