Bartec RDW 03 Скачать руководство пользователя страница 2

11-85F3-7D0001/A-03/2018-EHT

-205600

2-wire  
connection cable 

x

 m sensor cable SCR  

pre-terminated

max. 0.75 mm

2

plug

socket

1

2

socket mount connection cable at terminal 1 and 3 (none polarity)

RDW 03

Reservation 

Technical data subject to change without notice. Changes, errors and misprints may not be used as a basis for any claim for damages.

www.bartec.de

EN 2/4

BARTEC

Operating Instructions 

RDW 03 Monitoring Electronics

M

Monitoring examples sensors

RDW 03

terminal

4-wire  
connection cable 
 
from BARTEC 
Type 05-0068-0070

The brown and the yellow wire must be cut.

x

 m sensor cable SCR  

pre-terminated

plug 
SCR end resistor 
220 k

Ω 

Type 05-0080-0164

white

 

brown

green

 

yellow

plug

socket

1

2

terminal

 220 k

1

2

RDW 03

terminals 2, 4, 6 and 8 are not needed.

RDW 03

1

2

terminal

Remove resistance on terminals 5 and 7.

terminals 2, 4, 6 and 8 are not needed.

Assembly instruction

SCR plug and socket for sensor cable SCR and connection cable.

Installation sensor cable

plug/socket

Installation connection cable

Wire white with perforation

terminal 1

wire 1

Wire white

terminal 2

wire 2

Wire red with perforation

terminal 3

wire 3

Wire red

terminal 4

wire 4

shrink sleeve

25 mm

plug

socket

Technical data 

plug/socket

Wire gauge

0.25 mm

2

/0.75 mm

2

Cable outlet

Pg 7, max. 6 mm

Dimensions

max. length 60 mm,  
max. 

 20 mm

Material of shell

PA

Flammability acc. UL-94

V-2

Operating temperature

- 40 °C to + 85 °C

Commissioning

A suitable overcurrent protection mechanism must 
be provided in the power supply of the device and 
labelled  with  the  name  of  the  device.  This  also 
serves as a separator, for all poles, and must be 
easily reachable for the user. 

DANGER

!

Disconnect the device from the power supply befo-
re work on the wiring.

NOTICE

i

Loss of function due to incorrect procedure.
•  All maintenance and troubleshooting work  
  may only be carried out by authorised qualified 
  personnel.
•  Directive 2014/35/EU must be taken into 
  consideration.

The company operating the device must maintain it 
in a proper condition, operate it correctly, monitor it 
and clean it regularly. 
• Use a screwdriver to knock out the required  
   cable entries in the terminal compartment and  
   mount the included cable glands and lock nuts
• Connect the sensor to terminals of the  
   electronic monitoring (see terminal assignment)
• Connect floating contacts  
   (see terminal assignment)
• Connect supply voltage, either AC 230 V or  
   DC 24 V (safety extra-low voltage according to 
   VDE 0100/T 410)

i

 

NOTE

The  application  of  the  supply  voltage  causes  the 
automatic  insertion  of  the  RDW  03  system  (this 
guarantees the automatic restart after power failure):
LED ‘ready’ lights up  
(dry point sensor or sensor cable)

Leakage check

• immerse the leakage probe in about 3 mm or  
   the sensor cable in about 5 cm of water: 
   LED ‘leakage’ lights up 
   buzzer sounds
• dry point sensor or sensor cable
• confirm with the ‘reset’ button  
   (step 1: buzzer off)

terminal