BARTEC

Operating Instructions 

RDA01 Monitoring Electronics 

Type 17-85F4-2.22

M

NOTICE

i

BARTEC recommends a system inspection at least 
once  a  year.  The  countermeasures  introduced 
when detecting a leak must be adjusted in terms 
of weighting and reaction speed to the damage to 
be  averted.  The  operator  must  clarify  insurance 
requirements (building, liability etc.), for example 
inspection intervals, scope of inspections, training 
of the operating staff .

WARNING

!

Serious accidents due to damaged components.

•  Inspect the device and cables regularly for  
  cracks, damage and to check that connections 
  are secure.

NOTICE

i

Damage to the device due to incorrect cleaning.

•  Do not use compressed air to clean soiled 
  RDA01 monitoring electronics.

Troubleshooting

WARNING

!

Serious accidents due to the failure to use original 
spare parts.

•  Only replace parts with original parts.

Faulty  devices  can  be  repaired.  They  must  be 
replaced in line with these Operating Instructions.

Accessories, spare parts 

i

 

NOTE

The  monitoring  electronics  require  a  terminal 
resistance  (05-0080-0164)  in  the  last  PS  point 
sensor (factory installed) or at the end of the SCR 
sensor cable. 

See the BARTEC catalogue for further accessories 
and spare parts.

Disposal

The components of the BARTEC water detection 
system contain metal and plastic parts. 

Statutory requirements for electronic waste must 
therefore  be  complied  with  during  disposal  (e.g. 
disposal by an approved disposal company).

Service Address

BARTEC GmbH
Max-Eyth-Str. 16
97980 Bad Mergentheim
Germany
Phone: +49 7931 597 0
[email protected]
www.bartec.de

Terminal assignment  

Connection/Function

terminating 

resistor

sensivity

reset

leakage

open circuit 

operation

sensor

Presented condition: operation/no leakage

Dimensions

 in mm

Module wide: 22.5 mm

Sensitivity

The sensitivity of the sensor can be infl uenced in 
two diff erent ways:
a) “Sensitivity” potentiometer on the front of the 
  enclosure
b) “Termination resistance” selector switch on 
  the side wall of the enclosure must be set 
  to the termination resistance on the end of the 
  sensor. Factory setting: 220 kΩ

Transport, storage

NOTICE

i

Damage to the device caused by incorrect transport 
or incorrect storage.
•  Transport and storage only permitted in the 
  original packaging.

Maintenance and troubleshooting 

Water detection system

DANGER

!

Disconnect the device from the power supply before 
work on the wiring. 
The company operating the device must maintain it 
in a proper condition, operate it correctly, monitor it 
and clean it regularly. 
The PS point sensor and SCR sensor cable them-
selves are maintenance-free.
•  Care must be taken when mounting the PS 
  point sensor that the electrodes are clean and 
  free from grease
•  By means of suitable inspection intervals in line
  with the degree of contamination or the 
  amount of dust to be expected, it is necessary
  to ensure that the electrodes of the PS point 
  sensor and of the SCR the sensor cable are 
  kept clean and free from grease. This is 
  achieved by cleaning with methylated spirits
  or a household detergent with fat solvent.
•  Plug-in connections on the installation route
  must be installed so that they are protected 
  against moisture. When monitoring surfaces, 
  the customer should use spacers on the fl oor 
  for this purpose.

A recurring inspection of the monitoring electronics 
is fundamentally not necessary because the elec-
tronics are self-monitoring.