BARTEC
www.bartec.de
11-85M1-7D0002-03/2017-BAR
TEC-320201
M
Reservation
Technical data subject to change without notice. No claims for damages arising from alterations, errors or misprints shall be allowed.
EN 1/4
Safety instructions
The device may only be used within the specifi ed
ambient and working temperature range. Utilisa-
tion in ranges other than those specifi ed or the
modifi cation of the product by anyone other than
the manufacturer is not permitted and will exempt
BARTEC from liability for defects and from any
further liability. Incorrect installation may cause
malfunctioning. The generally applicable statutory
rules and other binding directives relating to work-
place safety, accident protection and environmen-
tal protection must be observed. The applicable
laws and directives must be complied with before
commissioning or restarting the device. The device
may be operated only if it is in a clean and undam-
aged condition. Conversions and modifi cations are
not permitted.
Marking
Particularly important points in these Instructions
are marked with a symbol:
DANGER
!
DANGER draws attention to a risk which will lead to
death or a serious injury if not avoided.
WARNING
!
WARNING draws attention to a risk which can lead
to death or serious injury if not avoided.
CAUTION
!
CAUTION draws attention to a risk which can lead
to injuries if not avoided.
NOTICE
i
ATTENTION draws attention to measures to avoid
damage to property.
Note
Important instructions and information on eff ective,
economical and environmentally compatible han-
dling.
Technical data
Method of measurement
conductive (conductive liquids > 2 µS)
Sensors
2 x 0.25 mm², stainless steel, protected by
partially permeable PTFE insulation
Colour: red, white
Rated resistance: 6 Ω/m
Sensitivity: determined by the RDA 01, RDW 03,
RLA
net
or RLW monitoring electronics
Return conductor
2 x 0.25 mm², copper with FEP insulation
Colour: red, white
Cable diameter
5 mm
Minimum bending radius
6 x cable diameter
Tensile strength
210 N
Temperature resistance
-50 °C to +180 °C
Fire protection
V0 according to fi re protection standard UL 1581
Water leakage detection system
The SCR sensor cable (illustration with connections
assembled by the customer) is a component in the
BARTEC water leakage detection system. It works
in connection with the RDA 01, RDW 03, RLA
net
or
RLW monitoring electronics. Other components in
the BARTEC water leakage detection system are
the PS point sensor, zone divider module, T branch,
plug set, socket set, and accessories (see Cata-
logue).
Description
The system detects even small liquid leaks quickly
and reliably. Optical and acoustic alarms are emit-
ted from the RDA 01, RDW 03, RLA
net
or RLW
monitoring electronics. At the same time, fl oating
contacts are set for signals to the building services
management and control tasks. The SCR sensor
cable has two NiCr sensor wires with PTFE partially
perforated insulation and two fully insulated return
conductors along its entire length. The high-quality
outer FEP plastic braiding off ers ideal mechanical
protection. In the event of contact with a conducti-
ve fl uid (e.g. water) the electric contact resistance
between the two sensor wires is reduced. This
change is measured, detected and signalised by
BARTEC´s RDA 01, RDW 03, RLA
net
or RLW mo-
nitoring electronics. The defi ned resistance in the
SCR sensor cable of approx. 6 Ω/m in connection
with the RLA
net
or RLW monitoring electronics al-
lows a precise location of the leak. The location of
the leakage is shown in metres on a large display
and it can be transmitted to the building services
management through diff erent interfaces.
Accessories
Connection/splicing
Sheathed cable: LIYY 4 x 0.5 mm²
Plug set: M12, 4-pin
Socket set: M12, 4-pin
End plug: M12 (for RLW, RLA
net
, T branch)
End resistor: M12 (for RDA 01, RDW 03)
Zone divider module: T branch
Assembly material
Fixing tape: self-adhesive
Identifi cation plate: “sensitive sensor cable”
Operating Instructions
SCR Sensor cable, Type 17-85M1-1761