VEX SERIES
INSTALLATION INSTRUCTIONS
800.533.3948
•
www.barronltg.com
10070040 Rev 4 - 03/14
3
5. Push excess wire into junction box.
6. Align holes in canopy with those in mounting plate.
Use supplied screws to secure canopy to mounting plate,
tightening until canopy is pulled tight to ceiling.
7. Snap in arrows (2) to faceplate (1) as required, storing
unused arrows in a safe place. Then snap faceplate (1)
to housing (4).
8. For double-faced signs, replace backplate with extra
EXIT faceplate.
Extension Rod Mounting (VEPA)
1. Fasten VEPA to extension rod using the supplied lock
nuts.
2. Attach sign to canopy by inserting canopy into sign then
sliding to the side to lock.
3. Make electrical connections by feeding AC wires through
the top access route on EXIT sign.
4. All electrical connections should be made inside junction
box.
Make Electrical Connections as follows:
Note:
Cap unused leads to prevent shorting.
5. Fasten VEPA to canopy using 8-32 x ¼” machine screws.
Extension rod
Lock nut
VEPA
Lock nut
Canopy
8-32 x 1/4 “
screws
Note:
AC
connections
should be
made inside
VEPA
enclosure.
120V AC
White - Common
Black - 120V
Green - Ground
277V AC
White - Common
Orange - 277V
Green - Ground