INSTALLATION INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes for the supply and return air openings

must be cut through the wall as shown in Figure 1
or 2.  Figure 1 is for models WL4843, and WL6023.
Figure 2 is for Models WL4842 and WL6022.

2. On wood frame walls, the wall construction must be

strong and rigid enough to carry the weight of the
unit without transmitting any unit vibration.

       WARING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained.  See Figure 3.

3. Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the installed unit.

WL4842 AND WL6022 ONLY

These units are equipped with adjustable return and
supply air flanges.  The flanges are adjustable side to
side in 1” increments.  This allows these units to be
adjusted so that in side by side applications these units
can replace two 2 Ton units using the same wall
openings.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides.  A bottom mounting bracket is provided
for ease of installation, but is not required.

2. The unit itself is suitable for 0 inch clearance, but

the supply air duct flange and the first 3 feet of
supply air duct require a minimum of 1/4 inch
clearance to combustible material.  If a combustible
wall use a minimum of 30-1/2” x 10-1/2”
dimensions for sizing.  However it is generally
recommended that a 1 inch clearance is used for
ease of installation and maintaining the required
clearance to combustible material.  The supply air
opening would then be 32” x 12”.  See Figures 2
and 3 for details.

        WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire causing damage, injury or death.

3. Locate and mark lag bolt locations and bottom

mounting bracket location.  See Figure 2.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top.  Top

rain flashing is shipped secured to the right side of
the back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top.  See Figure 2.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction).  Be sure to
observe required clearance if combustible wall.

 9. On side by side installations, maintain a minimum

of  20 inches clearance on left side to allow access
to control panel and heat strips, and to allow proper
airflow to the outdoor coil. Additional clearance
may be required to meet local or national codes.

Содержание WL4842

Страница 1: ...NTED PACKAGE AIR CONDITIONERS MODELS WL4842 WL4843 WL6022 WL6023 WL602N Manual 2100 402 Supersedes File Volume III Tab 16 Date 01 28 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ah...

Страница 2: ...gerant Charge 17 Table 8 Rated CFM and Rated ESP 17 Table 9 Maximum ESP of Operation Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Pub...

Страница 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC...

Страница 4: ...1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 MODEL NUMBER CONTROL MODULES CAPACITY 60 5 Ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 REVISIONS KW VENTILATIONOPTIONS B Blank off Plate FILTER OPTIONS N No Filter...

Страница 5: ...Manual 2100 402 Page 3 FIGURE 1 UNITDIMENSIONS WL602N WL6023 WL4843 ONLY MIS 1451...

Страница 6: ...Manual 2100 402 Page 4 FIGURE 2 UNITDIMENSIONS WL6022 WL4842 ONLY MIS 1452...

Страница 7: ...i W A T K C B T K C A T K C B T K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 2 4 8 4 L W 1 8 0 2 0 3 2 1 6 3 0 5 8 0 1 A N A N A N A N A N A N A N A N Z 0 B 0 0 B 2 4 8 4 L W 3 8 0 2 0 3 2 1 5 2 5...

Страница 8: ...h filter by bending the metal tabs holding the 1 inch filter down There are two tabs on each side of the filter NOTE WL6023 and WL4843 models require the use of a return air filter grille While these...

Страница 9: ...upply air duct require a minimum of 1 4 inch clearance to combustible material If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1...

Страница 10: ...Manual 2100 402 Page 8 FIGURE 3 MOUNTINGINSTRUCTIONS WL602N WL6023 WL4843 ONLY MIS 1349...

Страница 11: ...Manual 2100 402 Page 9 FIGURE 4 MOUNTINGINSTRUCTIONS WL6022 WL4842 ONLY MIS 1444...

Страница 12: ...RNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 i...

Страница 13: ...STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED...

Страница 14: ...Manual 2100 402 Page 12 FIGURE 8 COMMONWALLMOUNTINGINSTALLATIONS MIS 550...

Страница 15: ...base to the 24V terminal board in the unit A five conductor 18 gauge copper color coded thermostat cable is recommended The connection points are shown in Figure 9 See Start Up section for important i...

Страница 16: ...Manual 2100 402 Page 14 FIGURE 9 UNIT 24V TERMINAL BOARD MIS 1373A...

Страница 17: ...ined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain proper rotation direction The direction of rotation of the compressor may...

Страница 18: ...ntil the delay on break and delay on make periods have expired During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay High Pressure Switch...

Страница 19: ...t a r e p m e T D O 2 8 e r u t a r e p m e T 2 0 6 L W 0 0 7 1 5 5 3 5 2 6 0 6 4 8 4 L W 0 5 5 1 6 5 4 5 7 6 5 6 TABLE 8 RATED CFM AND ESP l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c...

Страница 20: ...1 1 5 1 1 2 0 6 L W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 1 7 3 3 2 2 7 7 4 2 4 7 2 6 2 5 7 8 7 2 6 7 5 9 2 7 7 3 1 3 8 7 1 3 3 8 7 1 5 3 9 7 1 7 3 B D g e d 0 8 B W g e d 7 6 e d...

Страница 21: ...L4842A WL4843B WL4842B t r a P r e b m u N n o i t p i r c s e D 5 1 C M C t i K t r a t S X X A 9 0 B C M W B 7 0 B C M W A 8 0 B C M W B 5 0 B C M W t i K r e k a e r B t i u c r i C t i K r e k a e...

Отзывы: