COMPRESSOR CONTROL MODULE

The compressor control module is standard on the
WL484 and WL605 models covered by this manual and
is optional on the WL423 model.  The compressor
control is an anti-short cycle/lockout timer with high
and low pressure switch monitoring and alarm relay
output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown,
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle the unit will go
into 

manual lockout

 condition and the alarm relay

circuit will energize.  Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute

(30 seconds) DOB = 123 second DOM

1.0 minute

(60 seconds) DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions, the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  A pressure table can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.

Содержание WL423

Страница 1: ...TION INSTRUCTIONS WALL MOUNTED PACKAGE AIR CONDITIONERS MODELS WL423 WL484 WL605 Manual 2100 504 Supersedes NEW File Volume III Tab 16 Date 01 31 08 Bard Manufacturing Company Inc Bryan Ohio 43506 Sin...

Страница 2: ...able 9 Maximum ESP Electric Heat Only 19 Table 10 Pressure Table 19 Table 11 Optional Accessories 20 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Model Nomenc...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...5 2 6 0 0 2 1 5 0 4 5 0 0 4 8 3 2 6 3 0 0 2 1 5 2 1 3 0 0 4 8 3 3 7 1 0 0 0 7 4 MODEL NUMBER CONTROLMODULES See Chart Below VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATI...

Страница 5: ...H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 2 4 L W 8 4 L W 0 6 L W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6 2 9 6...

Страница 6: ...N A N A N 0 1 A N A N A N 0 1 Z 0 B 0 0 B 4 8 4 L W 9 0 B 5 1 B 3 8 0 2 0 3 2 1 1 1 5 2 4 3 2 5 5 3 5 3 0 6 8 8 6 0 1 0 1 0 1 A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A...

Страница 7: ...local regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design airflow requirement of the...

Страница 8: ...shipped already attached to the unit The damper blade is locked in the closed position To allow the damper to operate the maximum and minimum blade position stops must be installed See Figure 2 All ca...

Страница 9: ...required clearance to combustible material The supply air opening would then be 32 x 12 See Figures 3 and 4 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See F...

Страница 10: ...Manual 2100 504 Page 10 of 20 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 11: ...feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fir...

Страница 12: ...Manual 2100 504 Page 12 of 20 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 6 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 504 Page 13 of 20 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...h the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Start Up section for important information on three phase scroll compressor start ups WIRING L...

Страница 15: ...Manual 2100 504 Page 15 of 20 FIGURE 8 UNIT 24V TERMINAL BOARD...

Страница 16: ...f delay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat con...

Страница 17: ...he delay on make time delay has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit wi...

Страница 18: ...0 6 L W 5 7 1 TABLE 6 REFRIGERANTCHARGE l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T 3 2 4 L W 0 0 4 1 4 5 2 5 6 6 4 6 4 8 4 L W 0 5 5 1 6 5 4 5 7 6 5...

Страница 19: ...COOLING Air Temperature Entering Outdoor Coil F l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 3 2 4 L W B D g e d 5 7 B W g e d 2 6 e d...

Страница 20: ...t a l i t n e V l a i c r e m m o C t s u a h x E h t i w r e z i m o n o c E X X X X X X X X X X X X X X X X X X 6 A M C A 0 1 A M C C A L l o r t n o C t n e i b m A w o L R D T C P H C P L X X X X...

Отзывы: