Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures
4, 5, 6 and 7 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct.  The spacing between
louvers on the grille shall not be larger than 5/8 inch.

NOTE:  If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

Any grille that meets with 5/8 inch louver criteria may
be used.  It is recommended that Bard Return Air Grille
Kit RG2 through RG5 or RFG2 through RFG5 be
installed when no return duct is used.  (RFG filter is not
included; must order separately.)  Contact distributor or
factory for ordering information.  If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.

FILTERS

A 1-inch throwaway filter is supplied with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A 1-inch washable filter and  a 2-inch
pleated filter are also available as optional accessories.
The internal filter brackets are adjustable to
accommodate the 2-inch filter by bending down the two
horizontal tabs on each filter bracket.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in
the service panel.

If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit.
The damper blade is locked in the closed position.  To
allow the damper to operate, the maximum and
minimum blade position stops must be installed.  See
Figure 2.

All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh air
Blank-off plate in place and is recommended for
maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

Содержание WH612

Страница 1: ...4 INSTALLATION INSTRUCTIONS WALL MOUNTED PACKAGE HEAT PUMPS Model WH612 Manual 2100 480 Supersedes NEW File Volume III Tab 17 Date 12 19 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 M...

Страница 2: ...ormance 23 Table 10 Maximum ESP of Operation 23 Table 11 Pressure Table Cooling 24 Table 12 Pressure Table Heating 24 Getting Other Information and Publications For More Information 3 Wall Mount Gener...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...L MODULES CAPACITY 61 5 ton VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISIONS KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate C Commercial Ventilator Motor...

Страница 5: ...h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 2 1 6 H W 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3 4...

Страница 6: ...of unit for a proposed installation should be based on heat loss calculation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance w...

Страница 7: ...e Kit RG2 through RG5 or RFG2 through RFG5 be installed when no return duct is used RFG filter is not included must order separately Contact distributor or factory for ordering information If using a...

Страница 8: ...pen or vented type system to assure proper drainage FIGURE 3 CONDENSATE DRAINS CONDENSATE DRAIN CONDENSER A hole is provided in the unit base to accept a Drain Connection Kit 8620 160 This allows conn...

Страница 9: ...2 x 12 See Figures 4 and 5 for details WARNING Failure to provide the 1 4 inch clearance between the supply duct and a combustible surface for the first 3 feet of duct can result in fire causing prope...

Страница 10: ...ng at time of installation MIS 796 A Top flashing detail view Attach supplied rain flashing Apply caulk between flashing and wall Foam air seal Seal with bead of caulking along entire length of top Su...

Страница 11: ...is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Страница 12: ...Manual 2100 480 Page 12 of 24 FIGURE 6 WALL MOUNTING INSTRUCTIONS FIGURE 7 WALL MOUNTING INSTRUCTIONS SEE FIGURE 4 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 13: ...Manual 2100 480 Page 13 of 24 FIGURE 8 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...isconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See...

Страница 15: ...f the heating equipment to the individual structure Utilization of the heating Application Data and the heat loss calculation of the building are useful in determining the correct set points Temperatu...

Страница 16: ...ulling in second stage heat when coming off set back conditions OPTIONAL COMPRESSOR CUTOFF THERMOSTAT See Figures 10 and 11 Heat pump compressor operation at outdoor temperatures below 0 F are neither...

Страница 17: ...a e h e g a t s 2 l o o c e g a t s 2 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 0 6 0 3 0 4 8 5 4 4 0 2 1 1 t a e H e g a t s 3 l o o C e g a t s 3...

Страница 18: ...ng See the Phase Monitor section later in this manual Verification of proper rotation must be made any time a compressor is changed or rewired If improper rotation is corrected at this time there will...

Страница 19: ...now in operation The second option has no Auto changeover position but instead energizes the reversing valve solenoid constantly whenever the system switch on subbase is placed in Heat position the B...

Страница 20: ...waiting for the outdoor ambient to fall into the defrost region FIGURE 15 DEFROST CONTROL BOARD By placing a jumper across the SEN JMP terminals a 1 4 inch QC terminal works best the defrost sensor m...

Страница 21: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Страница 22: ...507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0...

Страница 23: ...w o L 5 0 A 8 0 A 0 1 A 0 2 A 3 3 3 3 3 3 3 3 9 0 B 3 3 9 0 C 3 3 Rated CFM and ESP on high speed tap TABLE 8 RATED CFM RATED ESP l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n...

Страница 24: ...i S h g i H 2 7 1 9 1 4 7 8 0 2 5 7 5 2 2 7 7 2 4 2 8 7 1 6 2 0 8 9 7 2 1 8 8 9 2 1 8 8 1 3 2 8 8 3 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 5 7 8 9 1 7 7 5 1 2 8 7 3 3 2 0 8 0 5 2...

Отзывы: