background image

Manual

2100-488

Page

19 of 26

DEFROST CYCLE

The defrost cycle is controlled by temperature and time
on the solid state heat pump control.  See Figure 11.

When the outdoor temperature is in the lower 40°F
temperature range or colder, the outdoor coil
temperature is 32°F or below.  This coil temperature is
sensed by the coil temperature sensor mounted near the
bottom of the outdoor coil.  Once coil temperature
reaches 30°F or below, the coil temperature sensor
sends a signal to the control logic of the heat pump
control and the defrost timer will start.

After 60 minutes at 30°F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57°F, the
coil temperature sensor will send a signal to the heat
pump control which will return the system to heating
operations automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

The heat pump defrost control board has an option of
30, 60 or 90-minute setting.  All models are shipped
from the factory on the 60-minute pin.  If special
circumstances require a change to another time, remove
the wire from the 60-minute terminal and reconnect to
the desired terminal.  The manufacturer's
recommendation is for 60-minute defrost cycles.  Refer
to Figure 11.

There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the 

SPEEDUP

terminals to accelerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the 

SPEEDUP

 terminals.  It

may take up to 10 seconds with the 

SPEEDUP

 terminals

shorted for  the speedup to be completed and the defrost
cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.

Otherwise the timing will remain accelerated and run
through the 1-minute minimum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a 0° coil temperature.  This
can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a

1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the 

SEN JMP

jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control
opening because of  high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay function
built into the HPC.  This is to protect the compressor from
short cycling conditions.  In some instances it is helpful to
the service technician to override or speed up this timing

period, and shorting out the 

SPEEDUP

 terminals

for a few seconds can do this.

FIGURE  11

DEFROST CONTROL BOARD

Содержание WH423D

Страница 1: ...MOUNTED PACKAGE HEAT PUMPS MODELS WH423D WH484D WH604D INSTALLATION INSTRUCTIONS Manual 2100 488 Supersedes NEW File Volume III Tab 17 Date 01 04 08 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned ...

Страница 2: ... 22 Pressure Tables 23 24 Optional Accessories 24 Figures Figure 1 Unit Dimensions 5 Figure 2 Blower Damper Assembly 8 Figure 3 Mounting Instructions 10 Figure 4 Electric Heat Clearance 10 Figure 5 Wall Mounting Instructions 11 Figure 6 Wall Mounting Instructions 11 Figure 7 Common Wall Mounting Installations 12 Figure 8 Hot Gas Reheat During Dehumidification with CS2000A 14 Figure 9 Hot Gas Rehea...

Страница 3: ...inter and Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Q Duct System Design for Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 1003...

Страница 4: ... 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 CONTROL MODULES NOTE For 0 KW and circuit breakers 230 208V or pull disconnects 460V applications insert 0Z in the KW field of model number MODEL NUMBER CAPACITY 42 3 Ton 48 4 Ton 60 5 Ton REVISION COIL OPTIONS X Standard 1 Phenolic Coated Evaporator 2 Phenolic Coated Condenser 3 Phenolic Coated Evaporator and Condenser OUTLET OPTIONS X Front Standard COLOR OPTIONS X...

Страница 5: ...Manual 2100 488 Page 5 of 26 FIGURE 1 UNIT DIMENSIONS ...

Страница 6: ... o 1 4 3 0 6 6 8 0 5 0 7 0 9 8 6 3 0 1 8 8 A N 4 3 4 3 A N 6 2 2 5 A N 0 5 0 5 A N 0 3 0 6 A N 8 8 A N 0 1 6 A N 0 1 0 1 A N 0 1 0 1 Z 0 B 0 0 B D 3 2 4 H W 6 0 B 3 9 0 B 3 8 0 2 0 3 2 1 1 1 6 2 4 4 3 5 5 3 0 5 0 6 8 8 6 0 1 0 1 0 1 A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N Z 0 C 0 0 C D 3 2 4 H W 6 0 C 3 9 0 C 3 0 6 4 1 1 1 3 1 3 2 7 2 0 2 5 2...

Страница 7: ... of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent condensation or moisture damage Any grille that meets the 5 8 inch louver criteria may be used It is recommended that Bard Return Air Grille Kit RG 2 through RG 5 or RFG 2 through RFG 5 be installed when no ...

Страница 8: ... as required for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy efficiency The blank off plate is available upon request from the factory and is installed in place of the fresh air damper shipped with each unit CONDENSATE DRAIN A plastic drain hose extends from the drain pan at the top of the unit down to the ...

Страница 9: ...pening would then be 32 x 12 See Figures 3 4 and 7 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain flashing under back bend of top Top rain flashing is shipped secured to the right side of the back 6 Position unit in opening and secure with 5 16 lag bolts use 7 8 inch diameter flat washers on the lag...

Страница 10: ... Side view of wall with unit installed DIM A DIM B DIM C DIM D DIM E Required dimensions to maintain 1 4 min clearance from combustible materials 30 1 2 10 1 2 6 1 4 1 1 4 29 3 4 Required dimensions to maintain 1 clearance from combustible materials 32 12 5 1 2 2 29 DIMENSION CHART DIM A DIM B DIM C DIM D DIM E Required dimensions to maintain 1 4 min clearance from combustible materials 30 1 2 10 ...

Страница 11: ...100 488 Page 11 of 26 FIGURE 5 WALL MOUNTINGINSTRUCTIONS FIGURE 6 WALL MOUNTINGINSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS ...

Страница 12: ...Manual 2100 488 Page 12 of 26 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS ...

Страница 13: ...tage range for the 240 and 208V taps are NOTE The voltage should be measured at the field power connection point in the unit and while the unit is operating at full load maximum amperage operating condition LOW VOLTAGE CONNECTIONS These units use a grounded 24 volt AC low voltage circuit The R terminal is the hot terminal and the C terminal is grounded G terminal is the fan input Y terminal is the...

Страница 14: ...Manual 2100 488 Page 14 of 26 FIGURE 8 WHXXXDX HOT GAS REHEAT DURING DEHUMIDIFICATION WITH CS2000A ENERGY MONITOR FULL TIME DEHUMIDIFICATION ...

Страница 15: ...AS REHEAT DURING DEHUMIDIFICATION WITH CS2000A ENERGY MONITOR AND 8403 060 THERMOSTAT WITH BUILT IN HUMIDISTAT FULL TIME DEHUMIDIFICATION IMPORTANT NOTE Only the thermostats as shown in Table 4 will work with this equipment The thermostats must be matched and the correct operation can be assured only by proper selection and application of these parts ...

Страница 16: ... 5 5 3 2 e g u a g 0 2 e g u a g 8 1 e g u a g 6 1 e g u a g 4 1 e g u a g 2 1 5 4 0 6 0 0 1 0 6 1 0 5 2 IMPORTANT Only the thermostats shown in this Manual have been tested with this equipment for proper operation Proper unit operation with thermostats not listed in this Manual cannot be assured You assume responsibility for proper operation of the unit when using thermostats other than those lis...

Страница 17: ...ee the Phase Monitor later in this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out FIGURE 10 START UP LABEL NOTE If compressor is a...

Страница 18: ...fer to Figure 13 HEATING SEQUENCE On a call for heating the compressor and reversing valve of the unit are energized to provide heat pump heating If the room temperature falls below the 2nd stage heating set point backup electric heat is energized Heat pump heating is only available when the timer is energized If heating is energized any call for dehumidification is ignored If dehumidification is ...

Страница 19: ...ewdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals It may take up to 10 seconds with the SPEEDUP terminals shorted for the speedup to be completed and the defrost cycle to start As soon as the defrost cycle...

Страница 20: ...o c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n e p o r o f k c e h C e v i t c e f e d r o t i c a p a c r o t o M r o t i c a p a c e c a l p e R r o t i c a p a c d e t r o h s r o n e p o r o f k c e h C g n i t a r r o t i c a p a c k c e h ...

Страница 21: ...8139 85371 82699 80121 77632 75230 72910 70670 68507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0 35 0 36 0 37 0 38 0 39 0 40 0 41 0 42 0 43 0 44 0 45 0 46 0 47 0 48 0 49 0 50 0 51 0 52 0 53 0 54 0 55 0 56 0 57 0 58 0 59 0 60 0 61 0 62 0 63 0 64 0 65 0 66 0 67 0 68 0 69 0 70 0 71 0 72 0 73 0 ...

Страница 22: ... 4 0 6 H W 5 7 1 TABLE 9 INDOORBLOWERPERFORMANCE CFM 230V P S E H n i 2 O D 4 8 4 H W D 3 2 4 H W D 4 0 6 H W V 0 3 2 w o L V 0 3 2 h g i H V 0 3 2 w o L V 0 3 2 h g i H l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W l i o C y r D l i o C t e W 0 1 2 3 0 5 6 1 0 5 5 1 0 5 4 1 0 5 3 1 0 0 6 1 0 0 5 1 0 0 4 1 0 0 3 1 5 8 8 1 0 7 7 1 5 3 6 1 0 0 5 1 0 0 8 1 5 6 6 ...

Страница 23: ... H 2 7 1 1 2 3 7 6 2 2 5 7 1 4 2 6 7 6 5 2 8 7 2 7 2 9 7 8 8 2 0 8 4 0 3 2 8 1 2 3 4 8 7 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 7 7 6 1 2 8 7 2 3 2 0 8 7 4 2 1 8 3 6 2 3 8 9 7 2 5 8 5 9 2 6 8 2 1 3 8 8 9 2 3 0 9 6 4 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 0 8 4 2 2 1 8 0 4 2 3 8 6 5 2 4 8 2 7 2 6 8 9 8 2 8 8 5 0 3 9 8 3 2 3 1 9 1 4 3 3 9 8 5 3 D 4 8 4 H W...

Страница 24: ...0 A 2 4 H W H E s e g a k c a P r e t a e H X 0 1 A 2 4 H W H E s e g a k c a P r e t a e H X 6 0 C 2 4 H W H E s e g a k c a P r e t a e H X 5 0 A 4 0 H W H E s e g a k c a P r e t a e H X X 0 1 A 4 0 H W H E s e g a k c a P r e t a e H X X 9 0 B 4 0 H W H E s e g a k c a P r e t a e H X X X 9 0 C 4 0 H W H E s e g a k c a P r e t a e H X X X 5 P O B e t a l P f f O k n a l B X X X X X X X X X 5 ...

Страница 25: ... n i t a e H e g a t S t s 1 d e i p u c c O X X X X X X g n i t a e H e g a t S t s 1 m u h e D w X X X X X X X X X g n i t a e H e g a t S d n 2 d e i p u c c o n U X X X X X X X X X g n i t a e H e g a t S d n 2 d e i p u c c O X X X X X X X X X X X g n i t a e H e g a t S d n 2 m u h e D w X X X X X X X X X X t a e H y c n e g r e m E d e i p u c c o n U X X X X X X X t a e H y c n e g r e m E...

Страница 26: ...Manual 2100 488 Page 26 of 26 FIGURE 13 BARD HEAT PUMP COOLING MODE CIRCUITDIAGRAM FIGURE 14 BARDHEATPUMPDEHUMIDIFICATIONMODE CIRCUITDIAGRAM ...

Отзывы: