background image

Manual   2100-403
Page    7

INSTALLATION  INSTRUCTIONS

WALL MOUNTING INFORMATION

1. Two holes, for the supply and return air openings,

must be cut through the wall as shown in Figure 2.

2. On wood-frame walls, the wall construction must be

strong and rigid enough to carry the weight of the unit
without transmitting any unit vibration. See Figures 4
and 5.

3.  Concrete block walls must be thoroughly inspected

to insure that they are capable of carrying the weight
of the installing unit. See Figure 4.

MOUNTING THE UNIT

1. These units are secured by wall mounting brackets

which secure the unit to the outside wall surface at
both sides. A bottom mounting bracket is provided for
ease of installation, but it is not required.

2. The unit itself is suitable for “0” inch clearance, but

the supply air duct flange and the first 3 feet of supply
air duct require a minimum of 1/4 inch clearance to
combustible material. If a combustible wall, use a
minimum of 30-1/2" x 10-1/2" dimensions for sizing.
However, it is generally recommended that a 1 inch
clearance is used for ease of installation and
maintaining the required clearance to combustible
material. The supply air opening would then be 32" x
12". See Figures 2, 4 and 7 for details.

3. Locate and mark lag bolt locations and bottom

mounting bracket location. See Figure 4.

4. Mount bottom mounting bracket.

5. Hook top rain flashing under back bend of top. Top

rain flashing is shipped secured to the right side of the
back.

6. Position unit in opening and secure with 5/16 lag

bolts; use 7/8 inch diameter flat washers on the lag
bolts.

7. Secure rain flashing to wall and caulk across entire

length of top. See Figure 2.

8. For additional mounting rigidity, the return air and

supply air frames or collars can be drilled and
screwed or welded to the structural wall itself
(depending upon wall construction). Be sure to
observe required clearance if combustible wall.

9. On side by side installations, maintain a minimum of

20 inches clearance on right side to allow access to
heat strips and control panel, and to allow proper
airflow to the outdoor coil. Additional clearance may
be required to meet local or national codes.

TYPICAL INSTALLATIONS

See Figure 6 for common ways to install the wall-
mount unit.

         WARNING

Fire hazard can result if 1/4 inch clearance to
combustible materials for supply air duct is not
maintained. See Figure 2.

         WARNING

Failure to provide the 1/4 inch clearance
between the supply duct and a combustible
surface for the first 3 feet of duct can result in
fire.                                                    

Содержание WH421D Series

Страница 1: ...T PUMPS MODELS WH421D WH483D WH602D INSTALLATION INSTRUCTIONS Manual 2100 403A Supersedes 2100 403 File Volume III Tab 17 Date 09 01 03 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Movin...

Страница 2: ...vs Resistance of Temperature Sensor 20 Fan Blade Dimensions 21 Removal of Fan Shroud 21 Refrigerant Charge 21 Pressure Tables 22 23 Optional Accessories 23 Figures Figure 1 Unit Dimensions 3 Figure 2...

Страница 3: ...r and Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Q Duct System Design for Winter and Summer Air Conditioning For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...6 3 0 0 6 5 2 CONTROL MODULES See Chart Below NOTE For 0 KW and circuit breakers 230 208 V or pull disconnects 460 V applications insert 0Z in the KW field of model number MODEL NUMBER CAPACITY 42 3 1...

Страница 5: ...Manual 2100 403 Page 3 FIGURE 1 UNIT DIMENSIONS MIS 411...

Страница 6: ...1 4 3 0 6 6 8 0 5 0 7 0 9 8 6 3 0 1 8 8 A N 4 3 4 3 A N 6 2 2 5 A N 0 5 0 5 A N 0 3 0 6 A N 8 8 A N 0 1 6 A N 0 1 0 1 A N 0 1 0 1 Z 0 B 0 0 B D 1 2 4 H W 6 0 B 3 9 0 B 3 8 0 2 0 3 2 1 1 1 6 2 4 4 3 5...

Страница 7: ...rs of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both conserve energy and prevent conde...

Страница 8: ...r drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with the fresh air damper assembly the assembly is shipped already attac...

Страница 9: ...pening would then be 32 x 12 See Figures 2 4 and 7 for details 3 Locate and mark lag bolt locations and bottom mounting bracket location See Figure 4 4 Mount bottom mounting bracket 5 Hook top rain fl...

Страница 10: ...nch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in fire FIGURE 4 ELECTRIC HEAT CLEARANCE Side section view of sup...

Страница 11: ...3 Page 9 FIGURE 5 WALL MOUNTINGINSTRUCTIONS FIGURE 6 WALL MOUNTINGINSTRUCTIONS MIS 548 MIS 549 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DU...

Страница 12: ...Manual 2100 403 Page 10 FIGURE 7 COMMONWALL MOUNTINGINSTALLATIONS MIS 550...

Страница 13: ...e operating voltage range for the 240 and 208V taps are Nine 9 wires should be run from thermostat subbase to the 24V terminal board in the unit A nine conductor 18 gauge copper color coded thermostat...

Страница 14: ...hermostat and subbase must be matched and the correct operation can be assured only by proper selection and application of these parts MIS 1561 NC C C R NC C AREA OCCUPIED PWR HVAC H600A 6 5 4 3 C G R...

Страница 15: ...ons as shown in Table 4 will work with this equipment The thermostat and subbase must be matched and the correct operation can be assured only be proper selection and application of these parts MIS 15...

Страница 16: ...c that will prevent compressor for operating will cause red lamp to activate This is a signal to the operator of the equipment to place system in emergency heat position TABLE 3 THERMOSTAT WIRE SIZE r...

Страница 17: ...Monitor on page 15 of this manual Verification of proper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impac...

Страница 18: ...call for dehumidification the compressor and three way valve of the unit are energized to provide dehumidification Dehumidification mode will continue until the humidistat is satisfied If the room te...

Страница 19: ...erminal The manufacturer s recommendation is for 60 minute defrost cycles Refer to Figure 11 There is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle o...

Страница 20: ...Manual 2100 403 Page 18 FIGURE 11 DEFROST CONTROL BOARD...

Страница 21: ...e h C g n i d n i w r o t o m r o t o m e c a l p e R r o t i c a p a c r o t o M e v i t c e f e d k c e h C g n t a r r o t i c a p a c k c e h C r o t i c a p a c d e t r o h s r o n e p o r o f r...

Страница 22: ...85371 82699 80121 77632 75230 72910 70670 68507 66418 64399 62449 60565 58745 56985 55284 53640 52051 50514 49028 47590 46200 44855 43554 42295 41077 25 0 26 0 27 0 28 0 29 0 30 0 31 0 32 0 33 0 34 0...

Страница 23: ...s shown in the Table 7 TABLE 7 SUCTION LINE TEMPERATURES l e d o M d e t a R w o l f r i A D O F 5 9 e r u t a r e p m e T D O F 2 8 e r u t a r e p m e T 1 2 4 H W 3 8 4 H W 2 0 6 H W 0 0 4 1 0 5 5 1...

Страница 24: ...7 5 0 2 5 7 0 2 2 7 7 5 3 2 8 7 1 5 2 9 7 6 6 2 0 8 2 8 2 0 8 7 9 2 1 8 3 1 3 2 8 9 2 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 9 7 0 1 2 0 8 6 2 2 2 8 1 4 2 3 8 7 5 2 4 8 3 7 2 5 8...

Страница 25: ...9 3 1 3 5 0 A 2 4 H W H E s e g a k c a P r e t a e H X 0 1 A 2 4 H W H E s e g a k c a P r e t a e H X 6 0 C 2 4 H W H E s e g a k c a P r e t a e H X 5 0 A 4 0 H W H E s e g a k c a P r e t a e H X...

Отзывы: