background image

Manual   2100-193
Page   18

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed. Pressure tables can be found on Page 22
covering all models. It is imperative to match the correct
pressure table to the unit by model number.

DEFROST CYCLE

The defrost cycle is controlled by temperature and time
on the solid state heat pump control.  See Figure 14.

When the outdoor temperature is in the lower 40° F
temperature range or colder, the outdoor coil
temperature is 32° F or below.  This coil temperature is
sensed by the coil sensor mounted near the bottom of
the outdoor coil.  Once coil temperature reaches 30° F
or below, the coil sends a signal to the control logic of
the heat pump control and the defrost timer will start.

After 30 minutes at 30° F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode, the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57° F, the
coil sensor will send a signal to the heat pump control
which will return the system to heating operations
automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

There are three settings on the heat pump control – 30
minute, 60 minute, and 90 minute.  Models are shipped
wired on the 30 minute setting for greatest operating

economy.  If special circumstances require a change to
another time, remove wire connected to terminal 30 and
reconnect to desired terminal.  Refer to Figure 10.  The
manufucturer’s recommendation is for 3 minute defrost
cycles.

There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another 1/4 inch QC, to short between the SPEEDUP
terminals to accedlerate the HPC timer and initiate
defrost.

Be careful not to touch any other terminals with the
instrument used to short the SPEEDUP terminals.  It
may take up to 10 seconds with the SPEEDUP terminals
shorted for  the speedup to be completed and the defrost
cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminals.
Otherwise the timing will remain accelerated and run
through the 1 minute maximum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initiate defrost jumper (sen jump) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a  0° coil temperature.
This can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the SEN JMP terminals (a 1/
4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test
the SEN JMP jumper must be
removed.  If left in place too long the
compressor could stop due to the high
pressure control opening because of
high pressure condition created by
operating in the cooling mode with
outdoor fan off.   Pressure will rise
fairly fast as there is likely no actual
frost on the outdoor coil in this
artificial test condition.

There is also a 5 minute compressor time
delay function built into the HPC.  This
is to protect the compressor from short
cycling conditions.  In some instances it
is helpful to the service technician to
override or speed up this timing period,
and shorting out the SPEEDUP terminals
for a few seconds can do this.

FIGURE  14

DEFROST CONTROL BOARD

MIS-1528

Содержание WH301

Страница 1: ...L MOUNTED PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Manual No 2100 193K Supersedes 2100 193J File Volume III Tab 17 Date 05 13 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just as planned Copyright 2002 ...

Страница 2: ...Table 12 Maximum ESP of Operation Electric Heat Only 21 Table 13 Cooling Pressures 22 Table 14 Heating Pressures 22 Table 15 Optional Accessories 23 Start Up Important Installer Note 17 Crankcase Heaters 17 Service Hints 17 Sequence of Operation 17 Pressure Service Ports 18 Defrost Cycle 18 Troubleshooting Solid State Heat Pump Control Troubleshooting Procedures 19 Checking Temperature Sensor Outs...

Страница 3: ... ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036 Telephone 212 642 4900 Fax 212 302 1286 ASHRAE American Soc...

Страница 4: ...the supply and return ducts These instructions explain the recommended method to install the air cooled self contained unit and the electrical wiring connections to the unit These instructions and any instructions packaged with any separate equipment required to make up the entire heat pump system should be carefully read before beginning the installation Note particularly Starting Procedure and a...

Страница 5: ...T B A U T B A U T B A U T B A U T B 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 5 1 5 2 6 0 0 2 1 5 1 4 5 0 0 4 8 3 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 5 7 4 0 2 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 2 7 5 7 4 0 2 9 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 7 1 2 0 0 6 0 3 7 8 1 0 3 0 3 2 8 0 1 0 0 7 0 3 5 ...

Страница 6: ...odels only TABLE 2 DIMENSIONS OF BASIC UNIT Nominal l e d o M h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 0 3 H W 6 3 H W 0 0 2 8 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 7 2 8 8 3 1 8 8 7 2 0 0 0 4 0 5 8 1 5 7 5 2 3 9 7 1 5 7 6 2 5 7 8 2 5 2 9 2 0 0 7 2 5 7 2 9 1 9 3 5 7 2 2 4 1 9 9 1 4 0 0 2 1 0 0 5 ...

Страница 7: ...o e s u F t i u c r i C r e k a e r B k d l e i F r e w o P e r i W e z i S k d n u o r G e r i W e z i S m m u m i n i M t i u c r i C y t i c a p m A j m u m i x a M e s u F l a n r e t x E t i u c r i C r o r e k a e r B k r e w o P d l e i F e z i S e r i W k d n u o r G e z i S e r i W A T K C B T K C A T K C B T K C A T K C B T K C A T K C B T K C Z 0 A 0 0 A 1 0 3 H W 5 0 A l 0 1 A 1 8 0 2 ...

Страница 8: ...filter are also available as optional accessories The internal filter brackets are adjustable to accommodate the two inch filter by loosening two 2 screws in each bracket assembly and sliding the brackets apart to the required width and retightening the four 4 screws Refer to Table 12 for maximum static pressure available for duct design Design the duct work according to methods given by the Air C...

Страница 9: ...cation See Figure 3 4 Mount bottom mounting bracket if used 5 Hook top rain flashing under back bend of top Top rain flashing is shipped secured to the back of the unit on the right side 6 Position unit in opening and secure with 5 16 lag bolts use 7 8 inch diameter flat washers on the lag bolts 7 Secure rain flashing to wall and caulk across entire length of top See Figure 3 8 For additional moun...

Страница 10: ...Manual 2100 193 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 311 ...

Страница 11: ...ARANCE WARNING A minimum of 1 4 clearance must be maintained between the supply air duct and combustible materials This is required for the fist three 3 feet of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire MIS 277 ...

Страница 12: ...Manual 2100 193 Page 10 FIGURE 5 ATTACHING TOP OUTLET AIRFRAMES TO UNIT MIS 481 FIGURE 6 UNIT WITH TOP OUTLET MOUNTED UNDER OVERHANG MIS 482 ...

Страница 13: ...93 Page 11 FIGURE 7 WALL MOUNTINGINSTRUCTIONS MIS 549 FIGURE 8 WALL MOUNTINGINSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR DUCT DIMENSIONS ...

Страница 14: ...Manual 2100 193 Page 12 MIS 550 FIGURE 9 COMMONWALL MOUNTINGINSTALLATIONS ...

Страница 15: ...uisance tripping due to the momentary high starting current of the compressor motor The disconnect access door on this unit may be locked to prevent unauthorized access to the disconnect To convert for the locking capability bend the tab located in the bottom left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the doo...

Страница 16: ...Manual 2100 193 Page 14 FIGURE 10 LOW VOLTAGE WIRING ...

Страница 17: ...ture range the compressor cutoffs are not factory installed Outdoor thermostats are available to hold off various banks of electric heat until needed as determined by outdoor temperature The set point of either type of thermostat is variable with geographic region and sizing of the heating equipment to the structure Utilization of the Heating Application Data and the heat loss calculation of the b...

Страница 18: ...head pressure etc that will prevent compressor from operating will cause green lamp to activate This is a signal to the operator of the equipment to place system in emergency heat position j No automatic changeover position must manually place in heat or cool Reversing valve remains energized at all times system switch is in heat position except during defrost cycle No pressure equalization noise ...

Страница 19: ...door motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation START UP HEATING A 24V solenoid coil on reversing valve controls heating cycle operation Two thermostat options one allowing Auto changeover from cycle to cycle and the other constantly energizing solenoid coil during he...

Страница 20: ...ol This can be used to reduce the time between defrost cycle operation without waiting for time to elapse Use a small screwdriver or other metallic object or another 1 4 inch QC to short between the SPEEDUP terminals to accedlerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument used to short the SPEEDUP terminals It may take up to 10 seconds with...

Страница 21: ...o h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F n u r t o n s e o d g n i t a e h r o g n i l o o c t s o r f e d g n i r u d t p e c x e e v i t c e f e d r o t o M d e t r o h s r o n e p o r o f k c e h C g n i d n i w r o t o m r o t o m e c a l p e R e v i t c e f e d r o t i c a p a c r o t o M k c e h C g n i t a r r o t i c a p ...

Страница 22: ... 8 3 0 9 3 0 0 4 0 1 4 0 2 4 0 3 4 0 4 4 0 5 4 0 6 4 0 7 4 0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4 7 5 3 3 4 3 6 2 3 3 2 7 1 3 0 4 8 0 3 6 8 9 9 2 7 5 1 9 2 5 5 3 8 2 7 7 5 7 2 3 2 8 6 2 2 9 0 6 2 3 8 3 5 2 6 9 6 4 2 0 3 0 4 2 4 8 3 3 2 8 5...

Страница 23: ... H W 1 0 3 H W d e e p S w o L d e e p S h g i H l i o C y r D l i o C t e W l i o C y r D l i o C t e W 0 0 5 9 5 3 9 5 9 3 1 5 1 3 1 1 0 3 9 5 1 9 0 4 3 1 0 7 2 1 2 0 1 9 5 8 8 5 8 2 1 0 9 1 1 3 5 5 8 0 3 8 5 0 2 1 0 0 1 1 4 0 0 8 5 5 7 0 1 1 1 0 0 0 1 5 5 0 0 1 0 7 8 6 TABLE 12 MAXIMUM ESP OF OPERATION ELECTRIC HEAT ONLY l e d o M t e l t u O t n o r F t e l t u O p o T w o L d e e p S h g i H ...

Страница 24: ... 9 9 7 2 3 9 4 9 2 5 9 8 0 3 7 9 3 2 3 8 9 8 3 3 0 0 1 3 5 3 1 0 1 8 6 3 1 6 3 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 9 6 0 1 2 1 7 6 2 2 3 7 2 4 2 5 7 7 5 2 6 7 3 7 2 8 7 0 9 2 0 8 6 0 3 2 8 3 2 3 3 8 9 3 3 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 3 7 6 1 2 6 7 2 3 2 8 7 8 4 2 0 8 4 6 2 2 8 1 8 2 4 8 7 9 2 5 8 4 1 3 7 8 1 3 3 9 8 8 4 3 B D g e d 5 8 B W g e...

Страница 25: ...l P f f O k n a l B X X X X X X 3 D A F B r e p m a D r i A h s e r F c i r t e m o r a B X X X X X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X 3 V R C t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C X X X X X X 3 M F I E t s u a h x E h t i w r e z i m o n o c E X X X X X X A 3 A V R E W r o t a l i t n e V y r e v o c e R y g r e n E X X X X A 3 C V R E W ...

Отзывы: