background image

Manual

2100-423C

Page

15 of 21

START UP

IMPORTANT INSTALLER NOTE

For improved start up performance, wash the indoor coil
with a dish detergent.

CRANKCASE HEATERS

WH242 units are provided with compressor crankcase
heat.

These models have an insertion well-type heater located
in the lower section of the compressor housing.  This is
a self-regulating type heater that draws only enough
power to maintain the compressor at a safe temperature.

Some form of crankcase heat is essential to prevent
liquid refrigerant from migrating to the compressor
causing oil pump out on compressor start up and
possible valve failure due to compressing a liquid.

The decal in Figure 10 is affixed to all outdoor units
detailing start up procedure.  

This is very important.

Please read carefully.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at

all times.  Also, not to needlessly close off supply
and return air registers.  This reduces air flow
through the system which shortens equipment
service life as well as increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch.  Turn thermostat off, then
on, to reset the high pressure switch.

3. The heat pump wall thermostats perform multiple

functions.  Be sure that all function switches are
correctly set for the desired operating mode before
trying to diagnose any reported service problems.

4. Check all power fuses or circuit breakers to be sure

they are the correct rating.

5. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING –  

Circuit R-Y makes at thermostat pulling

in compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.

FIGURE  10

HEATING

 – a 24V solenoid coil on reversing valve

controls heating cycle operation.  Two thermostat
options, one allowing “Auto” changeover from cycle to
cycle, and the other constantly energizing solenoid coil
during heating season and thus eliminating pressure
equalization noise except during defrost, are to be used.
On “Auto” option, a circuit is completed from R-W1
and R-Y on each heating “ON” cycle energizing
reversing valve solenoid and pulling in compressor
contactor starting compressor and outdoor motor.  R-G
also make starting indoor blower motor.  Heat Pump
heating cycle now in operation.  The second option has
no “Auto” changeover position, but instead energizes
the reversing valve solenoid constantly whenever the
system switch on subbase is placed in “Heat” position,
the “B” terminal being constantly energized from R.  A
thermostat demand for heat completes R-Y circuit
pulling in compressor contactor starting compressor and
outdoor motor.  R-G also make starting indoor blower
motor.

IMPORTANT

THESE PROCEDURES MUST BE
FOLLOWED AT INITIAL START UP AND AT
ANY TIME POWER HAS BEEN REMOVED

FOR 12 HOURS OR LONGER.

TO PREVENT COMPRESSOR DAMAGE WHICH
MAY RESULT FROM THE PRESENCE OF LIQUID
REFRIGERANT IN THE COMPRESSOR
CRANKCASE:

1. MAKE CERTAIN THE ROOM THERMOSTAT IS IN

THE “OFF” POSITION. (THE COMPRESSOR IS
NOT TO OPERATE.)

2. APPLY POWER BY CLOSING THE SYSTEM

DISCONNECT SWITCH.  THIS ENERGIZES THE
COMPRESSOR HEATER WHICH EVAPORATES
THE LIQUID REFRIGERANT IN THE
CRANKCASE.

3. ALLOW 4 HOURS OR 60 MINUTES PER POUND

OF REFRIGERANT IN THE SYSTEM AS NOTED
ON THE UNIT RATING PLATE, WHICHEVER IS
GREATER.

4. AFTER PROPERLY ELAPSED TIME THE

THERMOSTAT MAY BE SET TO OPERATE THE
COMPRESSOR.

5. EXCEPT AS REQUIRED FOR SAFETY WHILE

SERVICING  — 

DO NOT OPEN SYSTEM

DISCONNECT SWITCH.

                                                                 

7961-061

Содержание WH184

Страница 1: ...PACKAGE HEAT PUMP Models WH184 WH242 INSTALLATION INSTRUCTIONS Manual 2100 423C Supersedes 2100 423B File Volume III Tab 17 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Mo...

Страница 2: ...eat Hold Off Wiring 14 Figure 10 Start Up Procedure Decal 15 Figure 11 Defrost Control Board 16 Figure 12 Fan Blade Setting 19 Start Up Important Installer Note 15 Crankcase Heaters 15 Service Hints 1...

Страница 3: ...nter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditionin...

Страница 4: ...ered in this manual is to be installed by trained experienced service and installation technicians The refrigerant system is completely assembled and charged All internal wiring is complete The unit i...

Страница 5: ...Manual 2100 423C Page 5 of 21 FIGURE 1 UNIT DIMENSIONS...

Страница 6: ...to note 89 of table 310 regarding Ampacity Adjustment Factors when more than 3 are in a raceway TABLE 2 ELECTRICALSPECIFICATIONS T I U C R I C E L G N I S l e d o M d e t a R s t l o V d n a e s a h...

Страница 7: ...NSATE DRAIN A plastic drain hose extends from the drain pan at the top of the unit down to the unit base There are openings in the unit base for the drain hose to pass through In the event the drain h...

Страница 8: ...as shown in Figure 3 2 Locate and mark lag bolt locations and bottom mounting bracket location if desired See Figure 3 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend...

Страница 9: ...Manual 2100 423C Page 9 of 21 FIGURE 3 MOUNTING INSTRUCTIONS...

Страница 10: ...Manual 2100 423C Page 10 of 21 FIGURE 5 WALL MOUNTING INSTRUCTIONS FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS...

Страница 11: ...Manual 2100 423C Page 11 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 12: ...orm to NEC and all local codes The electrical data lists fuse and wire sizes 75 C copper for all models including the most commonly used heater sizes Also shown are the number of field power circuits...

Страница 13: ...ecific destination of the country and are installed in areas not approaching the lower outdoor temperature range outdoor thermostats are not factory installed as standard equipment but are offered as...

Страница 14: ...s desirable to disable the operation of the electric heat until outdoor temperatures have reached a certain design point This won t allow the electric heat to come on as second stage heating unless th...

Страница 15: ...motor The G indoor motor circuit is automatically completed on any call for cooling operation or can be energized by manual fan switch on subbase for constant air circulation FIGURE 10 HEATING a 24V...

Страница 16: ...re is a cycle speed up jumper on the control This can be used to reduce the time between defrost cycle operation without waiting for time to elapse Use a small screwdriver or other metallic object or...

Страница 17: ...c p m u p t a e h n o y a l e r n a f s s o r c a k c e h C l o r t n o c p m u p t a e h e c a l p e R e v i t c e f e d r o t o M r o t o m e c a l p e R g n i d n i w r o t o m d e t r o h s r o n...

Страница 18: ...898 17434 16984 16547 16122 15710 15310 14921 14544 14177 13820 13474 13137 12810 12492 12183 11883 11591 11307 11031 10762 75 0 76 0 77 0 78 0 79 0 80 0 81 0 82 0 83 0 84 0 85 0 86 0 87 0 88 0 89 0 9...

Страница 19: ...Table 7 The suction line temperatures in Table 7 are based upon 80 F dry bulb 67 F wet bulb 50 R H temperature and rated airflow across the evaporator during cooling cycle FIGURE 12 FAN BLADE SETTING...

Страница 20: ...e d i S w o L e d i S h g i H 2 8 0 0 2 4 8 4 1 2 5 8 9 2 2 7 8 5 4 2 8 8 2 6 2 9 8 9 7 2 1 9 7 9 2 1 9 6 1 3 2 9 5 3 3 2 4 2 H W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 5 7 6 1 2 6...

Страница 21: ...r o t a l i t n e V m o o r s s a l C t s u a h x E h t i w r e z i m o n o c E r o t a l i t n e V y r e v o c e R y g r e n E X X X X X X X X X X X X X X X X X X X X X X X 3 H M C 7 H M C 9 H M C 4...

Отзывы: