background image

Manual 2100-495A
Page

16 of 21

All units are factory set on High speed and can be field
adjusted for lower speeds if required.

240-Volt Units (Single switch models):

 The speed of

both blowers (intake and exhaust) can be controlled by a
switch located on the left side of the control panel,
behind the WFERV front door.

240-Volt Units (Dual switch models): 

The speed of

each blower (intake and exhaust) can be controlled
independently by two (2) switches located on the left side
of the control panel, behind the WFERV front door.  The
switch located on the upper part of the control panel
controls the intake blower located in the upper assembly.
The switch located on the lower part of the control panel
controls the exhaust blower located in the lower
assembly.  See Figure 6

.

If desired, the intake blower can be set up for one speed
and the exhaust blower set up for another speed if needed
for the specific application.

TABLE  1

VENTILATION  AIR (CFM)

)

M

F

C

(

R

I

A

N

O

I

T

A

L

I

T

N

E

V

l

e

d

o

M

d

e

e

p

S

h

g

i

H

)

k

c

a

l

B

(

d

e

e

p

S

.

d

e

M

)

e

u

l

B

(

d

e

e

p

S

w

o

L

)

d

e

R

(

V

R

E

F

W

0

5

4

0

7

3

0

8

2

ENERGY RECOVERY VENTILATOR
MAINTENANCE

GENERAL INFORMATION

The ability to clean exposed surfaces within air moving
systems is an important design consideration for the
maintenance of system performance and air quality.  The
need for periodic cleaning will be a function of operating
schedule, climate, and contaminants in the indoor air
being exhausted and in the outdoor air being supplied to
the building.  All components exposed to the airstream,
including energy recovery wheels, may require cleaning
in most applications.

Rotary counterflow heat exchanges (heat wheels) with
laminar airflow are “self-cleaning” with respect to dry
particles.  Smaller particles pass through; larger particles
land on the surface and are blown clear as the flow
direction is reversed.  For this reason, the primary need

for cleaning is to remove films of oil-based aerosols that
have condensed on energy transfer surfaces.  Buildup of
material over time may eventually reduce airflow.  Most
importantly, in the case of desiccant coated (enthalpy)
wheels, such films can close off micron sized pores at the
surface of the desiccant material, reducing the efficiency
with which the desiccant can absorb and desorb moisture.

FREQUENCY

In a reasonably clean indoor environment such as a
school, office building, or home, experience shows that
reductions of airflow or loss of sensible (temperature)
effectiveness may not occur for ten or more years.
However, experience also shows that measurable changes
in latent energy (water vapor) transfer can occur in
shorter periods of time in commercial, institutional and
residential applications experiencing moderate occupant
smoking or with cooking facilities.  In applications
experiencing unusually high levels of occupant smoking,
such as smoking lounges, nightclubs, bars and
restaurants, washing of energy transfer surfaces, as
frequently as every six months, may be necessary to
maintain latent transfer efficiency.  Similar washing
cycles may also be appropriate for industrial applications
involving the ventilation of high levels of smoke or oil-
based aerosols such as those found in welding or
machining operations, for example.  In these applications,
latent efficiency losses of as much as 40% or more may
develop over a period of one to three years.

CLEANABILITY AND PERFORMANCE

In order to maintain energy recovery ventilation systems,
energy transfer surfaces must be accessible for washing to
remove oils, grease, tars and dirt that can impede
performance or generate odors.  Washing of the desiccant
surfaces is required to remove contaminate buildups that
can reduce adsorption of water molecules.  The continued
ability of an enthalpy wheel to transfer latent energy
depends upon the permanence of the bond between the
desiccant and the energy transfer surfaces.

Bard wheels feature silica gel desiccant permanently
bonded to the heat exchange surface without adhesives;
the desiccant will not be lost in the washing process.
Proper cleaning of the Bard energy recovery wheel will
restore latent effectiveness to near original performance.

MAINTENANCE PROCEDURES

NOTE: Local conditions can vary and affect the

required time between routine maintenance
procedures, therefore all sites (or specific units
at a site) may not have the same schedule to
maintain acceptable performance.  The
following timetables are recommended and can
be altered based on local experience.

        WARNING

Open circuit breaker to shut all power OFF
before doing this.  Failure to do so could
result in injury or death due to electrical
shock.

Содержание WFERV-A-4

Страница 1: ...V A X WFERV A 4 ENERGY RECOVERY VENTILATOR WITH EXHAUST Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 495A Supersedes 2100 495 File Volume III Tab 19 Date 04 02 08 INSTALLATION INSTRUCTIONS ...

Страница 2: ...igure 9 Operation of Unit with WFERV 14 Figure 10 Thermostat Wiring 18 Figure 11 Terminal Block Location Diagram 19 Figure 12 Hub Assembly with Ball Bearings 20 Tables Table 1 Ventilation Air CFM 16 Model Nomenclature Legend 3 Electrical Specifications 3 General Description 3 General Information 3 Unpacking 3 Performance and Application Data WFERV 4 Basic Installation Field Installation 5 6 Basic ...

Страница 3: ...ality requirements while still maintaining good indoor comfort and humidity control for a variety of applications such as schools classrooms lounges conference rooms beauty salons and others It provides a constant supply of fresh air for control of airborne pollutants including CO2 smoke radon formaldehyde excess moisture virus and bacteria The ventilator incorporates patented rotary heat exchange...

Страница 4: ...6 5 0 0 4 8 0 0 6 3 0 0 0 5 9 0 8 5 7 0 7 5 6 0 6 0 0 8 6 2 0 0 7 7 1 0 0 6 9 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 6 8 0 0 2 8 1 0 0 1 9 0 0 0 1 0 0 0 0 3 9 1 0 0 7 2 1 0 0 9 6 0 0 2 6 0 0 2 6 0 0 2 6 0 0 2 6 0 0 2 6 0 0 2 6 0 0 2 6 0 0 1 3 1 0 0 5 6 0 0 7 0 0 0 0 4 3 2 0 0 5 5 1 0 0 4 8 0 0 5 7 0 0 5 7 0 0 5 7 0 0 5 7 0 0 5 7 0 0 5 7 0 0 5 7 0 0 9 5 1 0 0 0 8 0 0 9 0 0 0 0 1 7 1 0 ...

Страница 5: ...ol panel 9 Remove female plug of low voltage wiring harness from the heat recovery assembly and snap into filter rack Route electrical harness leads through the 7 8 bushing into the low voltage box See Figure 5 10 Connect leads C black W blue and G orange with fork terminal to corresponding points on terminal strip See Figure 7 for 230V units NOTE These 24 volt control wires control the starting a...

Страница 6: ...d See Figure 9 Be sure to insert the top flange of the air intake hood into and through the slot in the service door and between the door and insulation to prevent bowing of the door 18 Close front door 19 Apply Certification label included with Installation Instructions next to unit Serial Plate 20 Assemble exhaust blower enclosure as shown in Figure 2A and install on unit as shown in Figure 4 wi...

Страница 7: ...EMOVE VENT OPTION DOOR MIS 2350 FRONT DOOR VENT OPTION DOOR EXHAUST COVER PLATES FIGURE 2A ASSEMBLY OF EXHAUST BLOWER ENCLOSURE PART NUMBERS COLOR A B C BEIGE 134 248 X 134 244 X 134 243 X GRAY 134 248 4 134 244 4 134 243 4 B A A B C MIS 2461 ...

Страница 8: ...Manual 2100 495A Page 8 of 21 FIGURE 3 FILTER AND EXHAUST PLATE LOCATION FRONT EXHAUST FILL PLATE FILL PLATE FILTER FRONT DOOR REAR EXHAUST SCREW MIS 2345 ...

Страница 9: ...4 INSTALLATION OF EXHAUST BLOWER ASSEMBLY MIS 2353 ASSEMBLY RIGHT SIDE LOWER WFERV FRONT PLATE REMOVE FASTEN ASSEMBLY TO CONDENSER PARTITION WITH 4 SCREWS DO NOT LOCATING HOLES ATTATCH EXHAUST BLOWER ENCLOSER WITH SCREWS PROVIDED AS SHOWN ...

Страница 10: ...Manual 2100 495A Page 10 of 21 FIGURE 5 INSTALLATION OF WFERV ...

Страница 11: ...Manual 2100 495A Page 11 of 21 FIGURE 6 WFERV ASSEMBLY ...

Страница 12: ... 21 FIGURE 7 WIRING 230 VOLT MIS 2356 ON WIRING DIAGRAM 230 VOLT CONTROL BOARD AS SHOWN WIRES TO L1 AND L2 ON BLOWER WIRES CONNECT WIRES INSERTED WITH CONNECT LOW VOLTAGE WIRES TO C W1 AND G AS SHOWN ON WIRING DIAGRAM GROUND WIRE ...

Страница 13: ...Manual 2100 495A Page 13 of 21 FIGURE 8 INSTALLATION OF FRESH AIR INTAKE HOOD ASSEMBLY ...

Страница 14: ...WITH WFERV INSTALLED SUPPLY AIR AIR EXHAUST RETURN AIR TOP FILTER BURNER BOX EXHAUST BLOWER HOOD INTAKE AIR GAS MANIFOLD GAS VALVE INDUCER DRAFT AIR BLOWER BLOWER EXHAUST WERV CASSETTE HOOD INDOOR COMFORT WFERV HOOD INTAKE BLOWER INTAKE AIR FRESH AIR MIS 2369 ...

Страница 15: ...ccupied periods wastes energy decreases the expected life of the WFERV and can result in a large moisture buildup in the structure The WFERV removes 60 to 70 of the moisture in the incoming air not 100 of it Running the WFERV when the structure is unoccupied allows moisture to build up in the structure because there is little or no load Use a control system that in some way can control the system ...

Страница 16: ...cing the efficiency with which the desiccant can absorb and desorb moisture FREQUENCY In a reasonably clean indoor environment such as a school office building or home experience shows that reductions of airflow or loss of sensible temperature effectiveness may not occur for ten or more years However experience also shows that measurable changes in latent energy water vapor transfer can occur in s...

Страница 17: ...ssette out of ventilator 6 Use a shop vacuum with brush attachment to clean both sides of the energy recovery wheels 7 Reverse shop vacuum to use as a blower and blow out any residual dry debris from the wheel NOTE Discoloration and staining of the wheel does not affect its performance Only excessive buildup of foreign material needs to be removed 8 If any belt chirping or squealing noise is prese...

Страница 18: ...Manual 2100 495A Page 18 of 21 FIGURE 10 THERMOSTAT WIRING DIAGRAM ...

Страница 19: ...Manual 2100 495A Page 19 of 21 FIGURE 11 TERMINAL BLOCK LOCATION ...

Страница 20: ...Manual 2100 495A Page 20 of 21 FIGURE 12 HUB ASSEMBLY WITH BALL BEARING ...

Страница 21: ...Manual 2100 495A Page 21 of 21 ...

Отзывы: