6. Install exhaust blower assembly in exhaust
opening as shown in Figure 4 and secure with
four (4) screws. Position 4-pin connector so it is
accessible.
7. Install ventilator into the unit to the left side.
Once the ventilator is fully inserted, slide the
ventilator to the right until it is tight against the
back of the control panel (see Figure 5).
IMPORTANT NOTE:
Position front lip of ventilator
over front grille and on top of condenser partition
(see Figure 5 inset). This is important to insure
proper drainage of any water entering damper
assembly.
8. Remove access panel and plug in exhaust blower
as shown in Figure 5. Replace access panel.
9. Remove outer and inner control panel covers.
Ensure all power is OFF prior to opening the
control panel.
FIGURE 4
Install Exhaust Blower Assembly
(LINE UP WITH EXISTING
INSTALL FILL PLATE
HOLES IN CONDENSER
PARTITION)
INSERT LOWER BLOWER
ASSEMBLY THROUGH
FILL PLATE WITH 45° MITERED
CORNER FACING CONDENSER
AND ATTACH USING (4) SCREWS
EXHAUST HOODS FACE
LEFT SIDE OF UNIT
MIS-3746
MIS-3746
EXHAUST HOOD FACES
LEFT SIDE OF UNIT