Manual 2100-667
Page
13 of 19
PRESS UP AND DOWN
ARROWS TO ENTER
CONFIGURATION MODE
USE ARROWS TO SELECT
SETTING. PUSH MIDDLE
BUTTON TO CHANGE.
CONTROLLER WILL
SHOW SET.
MIS-3763
4-20mA AN (ppm)
Damper (1)
Approc. Blade
Position (2)
4
700
MIN. OCC.
VENTILATION
0
5
750
.6
6
800
1.3
7
850
1.9
8
900
2.5
9
950
3.1
10
1000
3.8
11
1050
4.4
12
1100
5
13
1150
5.6
14
1200
6.3
15
1250
6.9
16
1300
7.5
17
1350
8.1
18
1400
8.8
19
1450
9.4
20
1500
FULLY OPEN
10
Settings Recommended
Default
RON
Not Used
ROF
Not Used
DSP
C
CT
UNI
US
US
COL
700
0
COH
1500
2000
TOL
Not Used
TOH
Not Used
BAR See Instrution with Controller
For High Altitude Installations
CAL
Used for Field Calibration
(1) Damper should be at the required minimum occupied ventilation rate when the
CO
2
control is at 700 ppm. Potentiometer R7 can be adjusted clockwise (CW) to
close it down, or counter clockwise (CCW) to open it to the required setpoint.
(2) Blade as referenced to the Blade Position Label.
JUMPERS MUST BE
POSITIONED AS SHOWN
FOR PROPER OPERATION
NOTE: MENU
JUMPER MUST
BE SET TO "ON"
TO CHANGE ANY
SETTINGS WITH
THE FRONT BUTTONS.
TO LOCK THE CO2
CONTROLLER MOVE
JUMPER TO "OFF" AFTER
IT HAS BEEN CONFIGURED
FIGURE 10
CO
2
Sensor Default and Final Settings
Bard Part #8403-067 CO
2
Controller