background image

Manual 2100-425B
Page

17 of 21

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at

all times.  Also, not to needlessly close off supply
and return air registers.  This reduces airflow
through the system, which shortens equipment
service life as well as increasing operating costs.

2. Check all power fuses or circuit breakers to be sure

they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING – 

Circuit R-Y makes at thermostat pulling

in compressor contactor, starting the compressor and
outdoor motor.  The G (indoor motor) circuit is
automatically completed on any call for cooling
operation or can be energized by manual fan switch on
subbase for constant air circulation.  On all 208/230 volt
models, when G circuit is de-energized the indoor
blower motor will continue to run for one minute.  On a
call for heating, circuit R-W1 make at the thermostat
pulling in heat contact for the strip heat and blower
operation.  On a call for second stage heat, R-W2 makes
bringing on second heat contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on the
models covered by this manual.  The compressor control
is an anti-short cycle/lockout timer with high and low
pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.  When

the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle, the unit will go
into 

manual lockout

 condition and the alarm relay circuit

will energize.  Recycling the wall thermostat resets the
manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls

are inherently automatic reset devices.  The
high pressure switch and low pressure
switch cut out and cut in settings are fixed by
specific air conditioner or heat pump unit
model.  The lockout features, both soft and
manual, are a function of the Compressor
Control Module.

Содержание WA611

Страница 1: ...Supersedes 2100 425A File Volume III Tab 16 Date 08 01 07 Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Models WA611 WA701 B WA701 C WA702 A WA721 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS ...

Страница 2: ...um ESP of Operation Electric Heat Only 20 Table 12 Cooling Pressure 20 Table 13 Optional Accessories 21 Getting Other Information and Publications For more information contact these publishers 3 Wall Mount General Information Air Conditioner Wall Mount Model Nomenclature 4 Shipping Damage 7 General 7 Duct Work 7 Filters 8 Fresh Air Intake 8 Condensate Drain 8 Installation Instructions Wall Mountin...

Страница 3: ...d Manual N Summer Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design for Winter Manual Q and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York...

Страница 4: ...0 0 2 1 5 1 4 5 0 0 4 8 3 2 6 3 0 0 2 1 5 2 1 3 0 0 4 8 3 3 7 1 0 0 0 7 4 0 8 1 3 3 4 0 3 4 1 6 5 7 3 0 0 1 6 4 0 0 2 2 3 8 0 6 2 8 6 1 2 7 0 0 2 1 5 VOLTS PHASE A 230 208 1 B 230 208 60 3 C 460 60 3 KW 00 No KW 0Z No KW w Circuit Breaker or Pull Disconnect 05 5 KW 09 9 KW 10 10 KW 15 15 KW 18 18 KW VENTILATION OPTIONS X Barometric Fresh Air Damper Standard B Blank off Plate M Motorized Fresh Air ...

Страница 5: ...OMINAL t i n U h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q A B C B 1 1 6 A W 0 7 A W 1 2 7 A W 2 4 4 1 2 2 8 7 4 9 8 7 9 8 7 9 2 8 7 5 1 8 7 9 2 8 7 3 4 9 1 8 5 1 4 0 3 6 1 1 1 2 4 7 3 4 3 4 4 2 1 2 4 4 1 3 3 4 8 7 3 3 0 1 All dimensions in inches FIGURE 1 UNIT DIMENSIONS ...

Страница 6: ... N A N 0 1 0 1 A N A N A N 0 1 0 1 Z 0 B 0 0 B 1 0 7 A W 9 0 B 5 1 B 8 1 B 3 8 0 2 0 3 2 1 1 1 1 6 3 6 3 2 5 0 6 0 5 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N Z 0 C 0 0 C 1 0 7 A W 9 0 C 5 1 C 3 0 6 4 1 1 1 7 1 7 1 6 2 5 2 5 2 0 3 2 1 2 1 0 1 2 1 2 1 0 1 A N A N A N A N A N A N...

Страница 7: ...egulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated in order to both con...

Страница 8: ...ped already attached to the unit The damper blade is locked in the closed position to allow the damper to operate the maximum and minium blade position stops must be installed See Figure 2 All capacity efficiency and cost of operation information as required for Department of Energy Energyguide Fact Sheets is based upon the fresh air blank off plate in place and is recommended for maximum energy e...

Страница 9: ...ending on the installed KW of electric heat there may be two field power circuits required If this is the case the unit serial plate will so indicate All models are suitable only for connection with copper wire Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions must be adhered to Refer to the National Electrical Code NEC for complete current carrying capac...

Страница 10: ...y Opening Return Opening Wall Bracket Wall Mounting Hole Pattern Front view of wall with unit removed 1 4 clearance on all 4 sides of supply air duct is required from combustible materials Supply Air Duct Return Air Opening Wall Circuit breaker access door Heater access panel Note It is recommended that a bead of silicone caulking be placed behind the side mounting flanges and under top flashing a...

Страница 11: ... h T s e r u t a e F e t a n i m o d e r P 7 5 0 3 0 4 8 3 5 1 1 D 0 2 2 5 H T t a e H e g a t s 1 l o o C e g a t s 1 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m m a r g o r P n o N c i n o r t c e l E r e v o e g n a h c l a u n a M r o o t u A 0 6 0 3 0 4 8 5 4...

Страница 12: ... 2100 425B Page 12 of 21 FIGURE 4 WALL MOUNTINGINSTRUCTIONS FIGURE 5 WALL MOUNTINGINSTRUCTIONS SEEFIGURE3 MOUNTINGINSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FORACTUALDIMENSIONS SEE FIGURE 1 FOR DUCTDIMENSIONS ...

Страница 13: ...Manual 2100 425B Page 13 of 21 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS ...

Страница 14: ...bustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in fire Side section view of supply air duct for wall mounted unit showing 1 4 inch clearance to combustible surfaces ...

Страница 15: ...Manual 2100 425B Page 15 of 21 FIGURE 8 LOW VOLTAGE WIRING ...

Страница 16: ...oper rotation must be made any time a compressor is change or rewired If improper rotation is corrected at this time there will be no negative impact on the durability of the compressor However reverse operation for over one hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal prote...

Страница 17: ...ployed is closed the compressor contactor is energized Upon shutdown the delay or break timer starts and prevents restart until the delay on break and delay on make periods have expired During routine operation of the unit with no power interruptions the compressor will operate on demand with no delay High Pressure Switch and Lockout Sequence If the high pressure switch opens the compressor contac...

Страница 18: ... can be found later in the manual covering all models It is imperative to match the correct pressure table to the unit by model number ADJUSTMENTS Adjustable Delay on Make and Delay on Break Timer The potentiometer is used to select Delay on Break time from 30 seconds to 5 minutes Delay on Make DOM timing on power up and after power interruptions is equal to 2 minutes plus 10 of Delay on Break DOB...

Страница 19: ...d shroud assembly out the left side of the unit 6 Service motor fan as needed 7 Reverse steps to reinstall TABLE 7 FAN BLADE DIMENSIONS l e d o M A n o i s n e m i D 1 1 6 A W 0 7 A W 5 2 1 1 2 7 A W 5 7 TABLE 8 SUCTION LINE TEMPERATURES s l e d o M d e t a R w o l f r i A F 5 9 p m e T D O F 2 8 p m e T D O 1 1 6 A W 0 5 3 1 4 5 2 5 0 6 7 5 0 7 A W 0 0 8 1 0 6 8 5 8 5 6 5 1 2 7 A W 0 0 8 1 1 6 9 ...

Страница 20: ... W 2 7 e d i S w o L e d i S h g i H 6 7 8 2 2 6 7 2 4 2 7 7 7 5 2 8 7 2 7 2 9 7 9 8 2 0 8 6 0 3 1 8 4 2 3 2 8 4 4 3 3 8 4 6 3 C B 1 0 7 A W B D 5 7 B W 2 6 e d i S w o L e d i S h g i H 2 6 4 1 2 3 6 0 3 2 4 6 7 4 2 5 6 5 6 2 6 6 0 8 2 7 6 9 9 2 8 6 6 1 3 9 6 3 3 3 0 7 1 5 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 6 0 2 2 8 6 6 3 2 9 6 4 5 2 0 7 1 7 2 1 7 7 8 2 2 7 6 0 3 3 7 4 2 3 4 7 2 4...

Страница 21: ...5 0 A W H E e g a k c a P r e t a e H X 5 0 A 1 6 A W H E e g a k c a P r e t a e H X 0 1 A 1 6 A W H E e g a k c a P r e t a e H X 8 0 A 1 6 A W H E e g a k c a P r e t a e H X 9 0 B 1 6 A W H E e g a k c a P r e t a e H X 5 P O B e t a l P f f O k n a l B X X X X X X X 5 D A F B r e p m a D r i A h s e r F c i r t e m o r a B X X X X X X X 5 D A F M r e p m a D r i A h s e r F d e z i r o t o M ...

Отзывы: