Manual   2100-398
Page  6

FILTERS

A one inch throwaway filter is supplied with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A one inch washable filter and two
inch pleated filter are also available as optional
accessories.  The internal filter brackets are adjustable
to accommodate the two inch filter by loosening two (2)
screws on each bracket assembly and sliding the
brackets apart to the required width and retightening the
four (4) screws.

FRESH AIR INTAKE

All units are built with fresh air inlet slots punched in
the service panel.

If the unit is equipped with a fresh air damper assembly,
the assembly is shipped already attached to the unit.
The damper blade is locked in the closed position.  To
allow the damper to operate, the maximum and
minimum blade position stops must be installed.  See
Figure 2.

All capacity, efficiency and cost of operation
information as required for Department of Energy
“Energyguide” Fact Sheets is based upon the fresh air
blank-off plate in place and is recommended for
maximum energy efficiency.

The blank-off plate is available upon request from the
factory and is installed in place of the fresh air damper
shipped with each unit.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base.  There are
openings in the unit base for the drain hose to pass
through.  In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.

DUCT WORK

All duct work, supply and return, must be properly
sized for the design air flow requirement of the
equipment.  Air Conditioning Contractors of America
(ACCA) is an excellent guide to proper sizing.  All duct
work or portions thereof not in the conditioned space
should be properly insulated in order to both conserve
energy and prevent condensation or moisture damage.

Refer to Table 10 for maximum static pressure
available for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.
Use insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the
first three feet of duct attached to the outlet air frame is
required.  See Wall Mounting Instructions and Figures 3
and 4 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.
A metallic return air grille is required with installations
not requiring a return air duct.  The spacing between
louvers on the grille shall not be larger than 5/8 inch.

Any grille that meets with 5/8 inch louver criteria may
be used.  It is recommended that Bard Return Air Grille
Kit RG2 through RG5 or RFG2 through RFG5 be
installed when no return duct is used.  Contact
distributor or factory for ordering information.  If using
a return air filter grille, filters must be of sufficient size
to allow a maximum velocity of 400 fpm.

NOTE:  If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

MIS-938

FIGURE  2

FRESH AIR DAMPER

BLADE IS LOCKED
CLOSED FOR
SHIPPING.

Содержание WA423

Страница 1: ...OUNTED PACKAGE AIR CONDITIONERS MODELS WA381 WA423 WA484 WA491 WA602 Manual 2100 398 Supersedes File Volume III Tab 16 Date 01 28 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead...

Страница 2: ...Table 9 Maximum EXP Electric Heat Only 17 Table 9A Maximum EXP Electric Heat Only 17 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Moun...

Страница 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC...

Страница 4: ...3 2 6 3 0 0 6 5 2 5 1 5 2 6 0 0 2 1 5 0 4 5 0 0 4 8 3 2 6 3 0 0 2 1 5 2 1 3 0 0 4 8 3 3 7 1 0 0 0 7 4 8 1 3 3 4 0 3 4 1 6 5 7 3 0 0 1 6 4 0 2 2 3 8 0 6 2 8 6 1 2 7 0 0 2 1 5 KW MODEL NUMBER CONTROL MO...

Страница 5: ...y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 8 3 A W 2 4 A W 8 4 A W 9 4 A W 0 6 A W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2...

Страница 6: ...1 8 0 2 0 3 2 1 1 1 2 r o 1 2 r o 1 5 3 5 3 9 5 5 8 0 1 1 0 5 0 5 0 6 0 9 0 1 1 8 8 6 4 2 0 1 0 1 0 1 8 6 A N A N A N 6 5 6 5 A N A N A N 6 2 2 5 A N A N A N 0 6 0 6 A N A N A N 0 3 0 6 A N A N A N 6...

Страница 7: ...sdiction should be consulted before the installation is made See Page 1 for information on codes and standards Size of unit for a proposed installation should be based on heat loss calculation made ac...

Страница 8: ...requirement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insu...

Страница 9: ...l If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required...

Страница 10: ...Manual 2100 398 Page 8 FIGURE 3 MOUNTINGINSTRUCTIONS MIS 416...

Страница 11: ...NING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 in...

Страница 12: ...STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHED...

Страница 13: ...Manual 2100 398 Page 11 FIGURE 7 COMMONWALLMOUNTINGINSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSETINSTALLATION MIS 550...

Страница 14: ...on on three phase scroll compressor start ups WIRING LOW VOLTAGE WIRING 230 208V 1 phase and 3 phase equipment dual primary voltage transformers All equipment leaves the factory wired on 240V tap For...

Страница 15: ...Manual 2100 398 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS 1373A...

Страница 16: ...identically internally As a result once the correct phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminal should maintain prope...

Страница 17: ...e Recycling the wall thermostat resets the manual lockout Low Pressure Switch Bypass and Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de en...

Страница 18: ...ycle TABLE 6 REFRIGERANTCHARGE l e d o M d e t a R w o l f r i A D O 5 9 e r u t a r e p m e T D O 2 8 e r u t a r e p m e T 1 8 3 A W 0 0 1 1 8 4 0 5 6 4 8 4 3 2 4 A W 0 0 4 1 4 5 2 5 6 6 4 6 4 8 4 A...

Страница 19: ...S w o L d e e p S 5 0 A 0 1 A 5 1 A 0 2 A 0 5 0 5 0 5 0 5 0 5 0 5 0 5 5 4 0 5 0 5 0 5 0 5 0 5 0 5 0 5 5 4 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 4 0 0 B 9 0 B 5 1 B 8 1 B 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0 5 0...

Страница 20: ...2 1 8 3 7 2 2 8 0 9 2 3 8 8 0 3 4 8 6 2 3 5 8 6 4 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 8 7 9 1 2 0 8 4 3 2 1 8 9 4 2 3 8 6 6 2 4 8 3 8 2 5 8 0 0 3 6 8 9 1 3 7 8 7 3 3 8 8 8 5 3...

Страница 21: ...r e t a e H X X 5 P O B 5 D A F B 5 D A F M e t a l P f f O k n a l B r e p m a D r i A h s e r F c i r t e m o r a B r e p m a D r i A h s e r F d e z i r o t o M X X X X X X X X X X X X X X X X X X...

Отзывы: