background image

Manual   2100-218
Page    15

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.   Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is powered
whenever compressor is locked out due to HPC or LPC
sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is equal
to 2 minutes plus 10% of Delay on Break (DOB) setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.

SERVICE HINTS

1. Caution homeowner to maintain clean air filters at all

times. Also, not to needlessly close off supply and
return air registers.  This reduces air flow through the
system, which shortens equipment service life as well
as increasing operating costs.

2. Switching to heating cycle at 75° F or higher outside

temperature may cause a nuisance trip of the remote
reset high pressure switch. Turn thermostat off then
on to reset the high pressure switch.

3. Check all power fuses or circuit breakers to be sure

they are the correct rating.

4. Periodic cleaning of the outdoor coil to permit full

and unrestricted airflow circulation is essential.

SEQUENCE OF OPERATION

COOLING

  –  Circuit R-Y makes at thermostat pulling in

compressor contactor, starting the compressor and
outdoor motor. The G (indoor motor) circuit is
automatically completed on any call for cooling operation
or can be energized by manual fan switch on subbase of
constant air circulation.  On all 230 volt units there is a
one minute off delay on the blower motor.  460 volt
models do not have an off delay.  On a call for heating,
circuit R-W1 make at the thermostat pulling in heat
contact for the strip heat and blower operation.  On a call
for second stage heat, R-W2 makes bringing on second
heat contactor, if so equipped.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on the
WA482 and WA602 models covered by this manual and
is optional on the WA421 model.  The compressor
control is an anti-short cycle/lockout timer with high and
low pressure switch monitoring and alarm relay output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit the delay on make period begins which will be 2
minutes plus 10% of the delay on break setting.  When
the delay on make is complete and the high pressure
switch (and low pressure switch if employed) is closed,
the compressor contactor is energized.  Upon shutdown
the delay or break timer starts and prevents restart until
the delay on break and delay on make periods have
expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand with
no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a soft lockout and stay in soft lockout
until the high pressure switch closes and the delay on
break time has expired.   If the high pressure switch opens
again in this same operating cycle the unit will go into
manual lockout condition and the alarm relay circuit will
energize.   Recycling the wall thermostat resets the manual
lockout.

Содержание WA421

Страница 1: ...MOUNTED PACKAGE AIR CONDITIONERS MODELS WA421 WA482 WA602 Manual 2100 218I Supersedes 2100 218H File Volume III Tab 16 Date 04 19 99 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead...

Страница 2: ...Table 9 Maximum EXP Electric Heat Only 18 Table 10 Pressure Table 18 Table 11 Optional Accessories 19 Getting Other Information and Publications 1 Wall Mount General Information 2 Heat Pump Wall Moun...

Страница 3: ...Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Ave N W Washington DC...

Страница 4: ...2 1 3 0 0 4 8 3 3 7 1 0 0 0 7 4 8 1 3 3 4 0 3 4 1 6 5 7 3 0 0 1 6 4 0 2 2 3 8 0 6 2 8 6 1 2 7 0 0 2 1 5 KW MODEL NUMBER CONTROL MODULES See Chart Below VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460...

Страница 5: ...F G I J K L M N O P Q R S T A B C B 2 4 A W 8 4 A W 5 7 0 2 4 2 3 4 2 2 5 7 8 4 8 8 8 9 8 8 9 2 8 8 5 1 8 8 9 2 8 8 3 4 0 1 9 1 6 6 1 3 0 0 0 3 8 6 2 3 4 9 6 2 9 6 4 3 3 4 2 3 7 3 3 8 8 2 4 8 8 3 2 0...

Страница 6: ...A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N A N Z 0 C 0 0 C 1 2 4 A W 9 0 C 5 1 C 3 0 6 4 1 1 1 2 1 7 1 6 2 5 1 0 2 0 3 4 1...

Страница 7: ...l regulations are at a variance with instructions installer should adhere to local codes DUCT WORK All duct work supply and return must be properly sized for the design air flow requirement of the equ...

Страница 8: ...rvice This filter can be serviced from the outside by removing the service door A one inch washable filter and two inch pleated filter are also available as optional accessories The internal filter br...

Страница 9: ...l If a combustible wall use a minimum of 30 1 2 x 10 1 2 dimensions for sizing However it is generally recommended that a 1 inch clearance is used for ease of installation and maintaining the required...

Страница 10: ...Manual 2100 218 Page 8 FIGURE 3 MOUNTING INSTRUCTIONS MIS 416...

Страница 11: ...ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overheating the combustible material and may result in a fire causin...

Страница 12: ...LL STRUCTURE FACTORY SUPPLIED RAIN FLASHING MOUNT ON UNIT BEFORE INSTALLATION SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS ATTACH TO TOP PLATE OF WALL 1 000 CLEARANCE ALL AROUND INTERIOR FINISHE...

Страница 13: ...Manual 2100 218 Page 11 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS FREE AIR FLOW NO DUCT DUCTED SUPPLY RETURN AT UNIT FALSE WALL INSTALLATION CLOSET INSTALLATION MIS 550...

Страница 14: ...See Start Up section for important information on three phase scroll compressor start ups Five 5 wires should be run from thermostat subbase to the 24V terminal board in the unit A five conductor 18 g...

Страница 15: ...Manual 2100 218 Page 13 FIGURE 8 UNIT 24V TERMINAL BOARD MIS 1373...

Страница 16: ...t it can be reconnected to low speed red wire for lower sound level See wiring diagram 50 HZ models must have fan wired on low speed These models are factory wired on low speed START UP IMPORTANT INST...

Страница 17: ...set high pressure switch Turn thermostat off then on to reset the high pressure switch 3 Check all power fuses or circuit breakers to be sure they are the correct rating 4 Periodic cleaning of the out...

Страница 18: ...phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct t...

Страница 19: ...mum unit performance will occur with a refrigerant charge resulting in a suction line temperature 6 from compressor as shown in Table 6 TABLE 7 INDOOR BLOWER PERFORMANCE CFM 230V P S E H n I 2 0 2 8 4...

Страница 20: ...eration on Page 14 TABLE 10 PRESSURE TABLE COOLING Air Temperature Entering Outdoor Coil F l e d o M r i A n r u t e R e r u t a r e p m e T e r u s s e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1...

Страница 21: ...X X X X X X X X X X X 5 V R C 5 M F I E B 5 A V R E W B 5 C V R E W t s u a h x E h t i w r o t a l i t n e V l a i c r e m m o C t s u a h x E h t i w r e z i m o n o c E r o t a l i t n e V y r e v...

Отзывы: