Bard Wall-Mounts are designed to provide optional ventilation packages to meet all of your ventilation and indoor air quality requirements.   All
units are equipped with a blank off plate as the standard ventilation package.  All ventilation packages can be built-in at the factory, or field-
installed at a later date.

ENERGY RECOVERY VENTILATOR

BLANK OFF PLATE - BOP

STANDARD

A blank off plate is installed on the inside of the service door.  It covers the air inlet openings which restricts any
outside air from entering the unit.  The blank off plate should be utilized in applications where outside air is not

required to be mixed with the conditioned air.

MOTORIZED FRESH AIR DAMPER - MFAD

       OPTIONAL

The motorized fresh air damper is internally mounted behind the service door and allows outside ventilation air,
up to 25% of the total airflow rating of the unit, to be introduced through the air inlet openings and to be mixed
with the conditioned air.  The two position damper can be fully open or closed.  The damper blade is powered
open by a 24VAC motor with spring return on power loss.  The damper can be controlled by indoor blower
operation or can be field connected to be managed based on building occupancy.

COMMERCIAL ROOM VENTILATOR - CRVMP

OPTIONAL

The built-in commercial room ventilator is internally mounted behind the service door and allows outside
ventilation air, up to 50% of the total airflow rating of the unit, to be introduced through the air inlet openings.
It includes a built-in exhaust air damper with integral bug screen.  Automatic control is integrated to maintain
desired ventilation air at the various supply airflows.

The commercial room ventilator (CRV) is a simple and innovative approach to improving the indoor air quality by
providing fresh air intake and exhaust capability through the CRV.  The damper can be easily adjusted to control
the amount of fresh air supplied into the building.  The CRV can be controlled by indoor blower operation or field
controlled based on room occupancy.  The CRV is power open - spring return on power loss.  Complies with
ANSI/ASHRAE Standard 62.1 “Ventilation for Acceptable Indoor Air Quality.”

ECONOMIZER - ECONWM-Series

OPTIONAL

The built-in economizer system is internally mounted behind the service door and allows outdoor air to be
introduced through the air inlet openings.  The amount of outdoor air varies in response to the system controls and
settings defined by the end user.  It includes a built-in exhaust air damper.  The economizer is designed to provide
“free cooling” when outside air conditions are cool and dry enough to satisfy cooling requirements without running
the compressor.  This in turn provides lower operating costs, while extending the life of the compressor.

ECONWMT Equipment Building versions have extended 11" air intake hood to deliver up to 100% of cooling rated airflow.

ECONWMS Standard versions have 3" air intake hood to deliver up to 75% of cooling rated airflow.

Standard Features:

Fully modulating

Honeywell Direct Drive Hi-Torque Actuator

No linkage required

Simple single blade design

Positive shut-off with non-stick gaskets

Electronic DB and/or Enthalpy sensors depending upon version

Honeywell JADE electronic economizer module with precision settings and diagnostics

DB or Enthalpy economizer versions available

WALL-MOUNT ENERGY RECOVERY VENTILATOR - ERVF

OPTIONAL

The wall-mount energy recovery ventilator (ERV) is a highly innovative approach to meeting indoor air quality
ventilation requirements as established by ANSI/ASHRAE Standard 62.1.  The ERV allows from 200 to 450 CFM
(depending upon model) of fresh air and exhaust through the unit while maintaining superior indoor comfort and
humidity levels.  In most cases this can be accomplished without increasing equipment sizing or operating costs.
Heat transfer efficiency is up to 67% during summer and 75% during winter conditions.

The ERV consists of a unique “rotary energy recovery cassette” that provides effective sensible and latent heat
transfer capabilities during summer and winter conditions.  Various control schemes are addressed including
limiting ventilation during building occupancy only.

The ERV is designed to be internally mounted behind the service door in the WA/LS model wall-mount units.  It
can be built-in at the factory or field installed as an option.  ERVF-*5 can be independently adjusted for intake and
exhaust rates.

COMMERCIAL ROOM VENTILATOR

Ventilation System Packages

Motorized Fresh Air Damper

NOTE:

  This vent system is intake only without built-in exhaust capability.  Building will likely require separate field

installed barometric relief or mechanical exhaust elsewhere within the conditioned space.  Other building systems will
govern actual amount of intake air.

Economizer

Содержание WA3S

Страница 1: ...ressure controls Alarm output for alarm relay Liquid Line Filter Drier Standard on all units Protects system against moisture High Low Pressure Switches are Auto Reset Standard on all units Built in lock out circuit resets from the room thermostat Provides commercial quality protection to the compressor Engineered Features THE WALL MOUNT STEP CAPACITY AIR CONDITIONERS Integrated Part Load Value IP...

Страница 2: ...0 4 5 3 0 0 4 5 3 0 0 4 5 3 0 0 0 6 4 0 0 0 6 4 0 0 0 6 4 0 0 5 6 5 0 0 5 6 5 0 0 5 6 5 y t i c a p a C g n i t a e H e l b a T t a e H c i r t c e l E e e S z H 0 6 g n i t a R l a c i r t c e l E 1 8 0 2 0 3 2 3 8 0 2 0 3 2 3 0 6 4 1 8 0 2 0 3 2 3 8 0 2 0 3 2 3 0 6 4 1 8 0 2 0 3 2 3 8 0 2 0 3 2 3 0 6 4 e g n a R e g a t l o V g n i t a r e p O 3 5 2 7 9 1 3 5 2 7 9 1 6 0 5 4 1 4 3 5 2 7 9 1 3 5 ...

Страница 3: ...service door and allows outdoor air to be introduced through the air inlet openings The amount of outdoor air varies in response to the system controls and settings defined by the end user It includes a built in exhaust air damper The economizer is designed to provide free cooling when outside air conditions are cool and dry enough to satisfy cooling requirements without running the compressor Thi...

Страница 4: ... 5 30 Vent Position Ventilation Airflow CFM Stage 2 Operation Blower Only Stage 1 Operation 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30 Vent Position Ventilation Airflow CFM Stage 2 Operation Stage 1 Operation Blower Only 0 100 200 300 400 500 600 700 800 900 1000 0 2 5 5 7 5 10 12 5 15 17 5 20 22 5 25 27 5 30 Vent Position Ventilation Airflow CFM Stag...

Страница 5: ... 6 5 7 0 6 0 9 0 0 4 9 0 0 4 0 0 6 8 4 0 6 8 4 0 6 5 2 3 6 5 2 3 0 0 6 0 9 2 7 0 9 2 7 0 8 3 7 4 8 3 7 4 0 5 7 0 6 5 7 0 6 0 9 0 0 4 9 0 0 4 0 0 6 8 4 0 6 8 4 0 6 5 2 3 6 5 2 3 0 5 8 0 8 0 9 5 1 3 0 6 8 4 0 3 7 6 2 3 3 5 0 2 9 5 1 3 4 7 3 7 1 5 2 3 6 2 0 5 0 4 5 7 2 2 2 4 7 3 7 1 2 7 6 2 1 0 7 4 1 0 6 0 1 2 0 4 2 3 0 2 8 7 1 0 1 1 4 1 0 7 1 2 9 3 9 1 1 5 7 5 6 4 1 2 0 6 8 4 5 0 6 6 1 2 5 9 3 1 9 5...

Страница 6: ...1 1 1 9 2 9 2 8 3 6 5 0 4 0 4 0 4 0 6 0 1 0 1 8 6 0 1 0 1 0 1 0 1 3 S 4 A W 2 S 4 L W Z 0 C 6 0 C 9 0 C 5 1 C 3 0 6 4 1 1 1 1 5 1 6 1 1 2 0 3 0 2 0 2 5 2 0 3 2 1 2 1 0 1 0 1 2 1 2 1 0 1 0 1 3 S 5 A W 2 S 5 L W Z 0 A 5 0 A 8 0 A 0 1 A 5 1 A 0 2 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 2 r o 1 3 r o 1 4 4 4 4 3 5 3 6 9 8 5 1 1 0 5 0 5 0 6 0 7 0 9 0 2 1 8 8 6 6 3 2 0 1 0 1 0 1 8 8 6 4 4 4 4 4 4 6 2 2 5 2 5 6 2 ...

Страница 7: ...9 7 2 1 0 6 0 6 4 4 1 8 7 4 0 2 0 5 4 5 2 1 9 5 3 5 1 0 6 2 7 8 7 4 0 2 2 5 5 9 6 0 4 8 8 1 0 8 0 8 3 3 3 4 0 3 7 2 0 0 6 8 8 2 8 7 4 0 2 0 9 0 9 7 1 2 7 1 7 0 3 5 7 6 7 8 1 8 3 0 3 2 0 9 8 0 1 7 1 7 0 3 8 2 8 4 0 1 0 6 2 8 2 0 0 1 0 0 1 7 1 4 0 3 1 4 3 0 5 7 1 6 3 8 9 5 5 2 0 5 1 0 5 1 5 2 6 1 6 3 5 9 1 1 5 5 2 1 1 1 4 5 2 1 3 6 9 3 8 3 0 5 1 0 8 1 5 9 1 1 5 0 8 3 1 3 7 1 9 9 0 7 4 0 0 2 0 0 2 3 ...

Страница 8: ...OW SUPPLY AIR PLENUM WMICF5 ISOLATION CURB WAPR11 RETURN AIR ACCOUSTICAL PLENUM Patent Pending MIS 2284 A 9 7 8 1 1 2 13 3 4 42 1 4 3 3 4 1 1 2 3 3 4 1 1 2 3 8 29 7 8 18 1 2 Free Blow Acoustical Plenum WAPFB51 s e i r o s s e c c A n o i t a l l a t s n I l a n o i t p O n o i t p i r c s e D l e d o M r o l o C g n i p p i h S s b L t h g i e W r i A n r u t e R m u n e l P l a c i t s u o c A X ...

Страница 9: ...turn Air Silencer Blower Only Operation 40 1 38 9 38 4 34 5 32 8 28 2 Compressor Stage 1 Operation 52 0 41 4 50 9 41 2 40 5 39 0 Compressor Stage 2 Operation 53 7 44 0 52 9 44 3 42 0 40 5 Compressor Stage 2 with ERV High Speed Operation 55 0 46 2 54 0 44 8 Indoor Integrated dBA 45 4 40 4 44 0 37 8 35 8 33 0 Compressor Stage 2 Outdoor Sound Level 65 0 65 0 65 0 65 0 65 0 65 0 Note 1 dBA is sound pr...

Страница 10: ... 9 3 0 0 3 0 5 0 0 5 9 3 2 7 5 8 g n i l o o C l a t o T g n i l o o C e l b i s n e S 5 7 3 9 7 5 2 4 6 4 0 5 6 7 7 5 7 8 5 4 0 5 9 5 7 0 5 3 5 4 5 2 2 4 7 5 2 8 4 4 5 2 5 2 7 5 7 2 4 4 0 0 8 0 7 0 5 7 3 4 5 7 2 9 6 5 7 2 3 4 0 5 7 7 6 0 0 8 2 4 5 2 2 6 6 5 2 3 2 4 0 0 7 4 6 0 5 8 1 4 0 5 2 2 6 0 0 1 1 4 5 7 7 9 5 5 2 3 0 4 5 2 3 7 5 5 7 5 9 3 0 5 8 4 5 0 0 8 8 3 l e d o M B W B D 2 y t i c a p a...

Страница 11: ...od Disconnect Access Panel C Breaker High Voltage Electrical Drain Side View I J D A C H 2 13 K 11 Economizer Air Intake Hood Brackets Shipping Location Supply Air Opening Return Air Opening Electrical Optional Built In Entrances Mounting Side Wall Top Rain Flashing Bottom Installation Bracket Back View M L O E R S S S S S T N Q B P 44 1 MIS 3210 Electric Heat Air Outlet Front View Filter Access P...

Страница 12: ...tor Condenser SUPPLY AIR OUTLET X Front Standard CAPACITY 3S 3 Ton 4S 4 Ton 5S 5 Ton KW VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 REVISION WA 3 WL 2 FILTER OPTIONS P 2 inch Pleated MERV 8 VENTILATION OPTIONS See Chart Below STD Standard equipment for these specified models 1 HPC High pressure control is auto reset Always used with compressor control module CCM which is included See note...

Отзывы: