background image

Manual  2100-192
Page   5

SHIPPING DAMAGE

Upon receipt of equipment, the carton should be
checked for external signs of shipping damage. If
damage is found, the receiving party must contact the
last carrier immediately, preferably in writing,
requesting inspection by the carrier’s agent.

GENERAL

The equipment covered in this manual is to be installed
by trained, experienced service and installation
technicians.

The refrigerant system is completely assembled and
charged. All internal wiring is complete.

The unit is designed for use with or without duct work.
Flanges are provided for attaching the supply and return
ducts.

These instructions explain the recommended method to
install the air cooled self-contained unit and the
electrical wiring connections to the unit.

These instructions and any instructions packaged with
any separate equipment required to make up the entire
air conditioning system should be carefully read before
beginning the installation. Note particularly “Starting
Procedure” and any tags and/or labels attached to the
equipment.

While these instructions are intended as a general
recommended guide, they do not supersede any national
and/or local codes in any way. Authorities having
jurisdiction should be consulted before the installation is
made. See Page 1 for information on codes and
standards.

Size of unit for a proposed installation should be based
on heat loss calculation made according to methods of
Air Conditioning Contractors of America (ACCA). The
air duct should be installed in accordance with the
Standards of the National Fire Protection Association
for the Installation of Air Conditioning and Ventilating
Systems of Other Than Residence Type, NFPA No.
90A, and Residence Type Warm Air Heating and Air
Conditioning Systems, NFPA No. 90B. Where local
regulations are at a variance with instructions, installer
should adhere to local codes.

DUCT WORK

All duct work, supply and return, must be properly sized
for the design air flow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing. All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

Any grille that meets the 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG-2 through RG-5 or RFG-2 through RFG-5 be
installed when no return duct is used.  Contact
distributor or factory for ordering information.  If using
a return air filter grille, filters must be of sufficient size
to allow a maximum velocity of 400 fpm.

FILTERS

A 1 inch throw away filter is suppled with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A 1 inch washable filter and a 2 inch
pleated filter are also available as optional accessories.
The internal filter brackets are adjustable to
accommodate the 2 inch filter by loosening 2 screws in
each bracket assembly and sliding the brackets apart to
the required width and retightening the 4 screws.

Refer to Table 10 for maximum static pressure available
for duct design.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of 1 inch of insulation. Use
insulation with a vapor barrier on the outside of the
insulation. Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

A 1/4 inch clearance to combustible material for the
first 3 feet of duct attached to the outlet air frame is
required. See Wall Mounting Instructions and Figures 3
and 4 for further details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

        CAUTION

Some installations may not require any return
air duct.  A metallic return air grille is required
with installations not requiring a return air
duct.  The spacing between louvers on the
grille shall not be larger than 5/8 inches.

Содержание WA301

Страница 1: ...CKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 192M Supersedes 2100 192L File Volume III Tab 16 Date 05 13 02 Bard Manufacturing Company Bryan Ohio 43506 Since 1914 Moving ahead just...

Страница 2: ...General 5 Duct Work 5 Filters 5 Fresh Air Intake 6 Condensate Drain 6 Installation Instructions Wall Mounting Information 7 Mounting the Unit 7 Top Outlet Only 7 Wiring Main Power 7 Wiring Low Voltag...

Страница 3: ...ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washing...

Страница 4: ...e latest revision Article 310 for power conductor sizing CAUTION When more than one field power conductor circuit is run through one conduit the conductors must be derated Pay special attention to not...

Страница 5: ...odels only TABLE 2 DIMENSIONS OF BASIC UNIT NOMINAL l e d o M h t d i W W h t p e D D t h g i e H H y l p p u S n r u t e R E F G I J K L M N O P Q R S T A B C B 0 3 A W 6 3 A W 0 0 2 8 3 5 2 1 7 1 3...

Страница 6: ...M A H U T B S P M A H U T B S P M A H U T B 0 5 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 8 0 2 5 6 0 7 1 1 8 1 0 0 8 2 1 0 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 0 0 1 6 1 4 0 3 1 4...

Страница 7: ...rement of the equipment Air Conditioning Contractors of America ACCA is an excellent guide to proper sizing All duct work or portions thereof not in the conditioned space should be properly insulated...

Страница 8: ...drainage FRESH AIR INTAKE All units are built with fresh air inlet slots punched in the service panel If the unit is equipped with the fresh air damper assembly the assembly is shipped already attache...

Страница 9: ...nch diameter flat washers on the lag bolts 7 Secure rain flashing to wall and caulk across entire length of top See Figure 3 8 For additional mounting rigidity the return air and supply air frames or...

Страница 10: ...lor coded thermostat cable is recommended The connection points are shown in Figure 10 TABLE 5 THERMOSTAT WIRE SIZE r e m r o f s n a r T A V A L F e r i W e g u a G m u m i x a M e c n a t s i D t e...

Страница 11: ...it showing 1 4 inch clearance to combustible surfaces FIGURE 4 ELECTRIC HEAT CLEARANCE MIS 277 WARNING WARNING A minimum of 1 4 inch clearance must be maintained between the supply air duct and combus...

Страница 12: ...Page 10 FIGURE 5 WALL MOUNTING INSTRUCTIONS MIS 549 FIGURE 6 WALL MOUNTING INSTRUCTIONS MIS 548 SEE FIGURE 3 MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIONS SEE FIGURE 1 FOR...

Страница 13: ...Manual 2100 192 Page 11 MIS 550 FIGURE 7 COMMON WALL MOUNTING INSTALLATIONS...

Страница 14: ...Manual 2100 192 Page 12 FIGURE 8 LOW VOLTAGE WIRING MIS 1373C...

Страница 15: ...elay On a call for heating circuit R W1 make at the thermostat pulling in heat contact for the strip heat and blower operation On a call for second stage heat R W2 makes bringing on second heat contac...

Страница 16: ...mmediately The lockout timer will go into a soft lockout and stay in soft lockout until the high pressure switch closes and the delay on break time has expired If the high pressure switch opens again...

Страница 17: ...ng in a suction line temperature 6 inches from compressor as shown in Table 8 The suction line temperatures in Table 8 are based upon 80 F dry bulb 67 F wet bulb 50 percent R H temperature and rated a...

Страница 18: ...e r P 5 7 0 8 5 8 0 9 5 9 0 0 1 5 0 1 0 1 1 5 1 1 0 2 1 5 2 1 1 0 3 A W B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 4 7 8 1 2 7 7 2 3 2 9 7 7 4 2 1 8 2 6 2 2 8 7 7 2 4 8 2 9 2 5 8 6 0 3...

Страница 19: ...e t a l P f f O k n a l B X X X X X X 3 D A F B r e p m a D r i A h s e r F c i r t e m o r a B X X X X X X 3 D A F M r e p m a D r i A h s e r F d e z i r o t o M X X X X X X 3 V R C t s u a h x E h...

Отзывы: