Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to
HPC or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds) DOB = 123 second  DOM
1.0 minute (60 seconds) DOB = 126 second  DOM
2.0 minute (120 seconds) DOB = 132 second  DOM
3.0 minute (180 seconds) DOB = 138 second  DOM
4.0 minute (240 seconds) DOB = 144 second  DOM
5.0 minute (300 seconds) DOB = 150 second  DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

PRESSURE SERVICE PORTS

High and low pressure service ports are installed on all
units so that the system operating pressures can be
observed.  Pressure tables can be found later in the
manual covering all models.  It is imperative to match
the correct pressure table to the unit by model number.

COMPRESSOR CONTROL MODULE

The compressor control module is optional on the
models covered by this manual.  The compressor
control is an anti-short cycle/lockout timer with high
and low pressure switch monitoring and alarm relay
output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit, the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.

When the delay on make is complete and the high
pressure switch (and low pressure switch if employed)
is closed, the compressor contactor is energized.  Upon
shutdown, the delay or break timer starts and prevents
restart until the delay on break and delay on make
periods have expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle, the unit will
go into 

manual lockout

 condition and the alarm relay

circuit will energize.  Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual
lockout.

Содержание WA253 Series

Страница 1: ...WA253 WALL MOUNTED PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Manual No 2100 406A Supersedes 2100 406 File Volume III Tab 16 Date 07 25 06 Bard Manufacturing Company Inc Bryan Ohio 43506 Sinc...

Страница 2: ...Removal of Fan Shroud 15 Refrigerant Charge 15 Cooling Pressures 16 Optional Accessories 16 Figures Figure 1 Unit Dimensions 5 Figure 2 Fresh Air Damper Assembly 7 Figure 3 Mounting Instructions 8 Fi...

Страница 3: ...er and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning...

Страница 4: ...protection of field wiring conductors 2 Based on 75 C copper wire All wiring must conform to NEC and all local codes 3 These Minimum Circuit Ampacity values are to be used for sizing the field power...

Страница 5: ...t e R E F G I J K L M N O P Q R S T A B C B 2 5 2 A W 0 0 3 3 3 5 2 1 7 1 3 6 5 0 7 8 8 7 8 8 9 1 8 8 1 1 8 8 9 1 0 0 5 3 0 5 8 1 5 7 5 2 6 5 0 2 5 7 6 2 6 0 8 2 5 2 9 2 0 0 7 2 3 6 2 3 1 4 3 6 0 2 2...

Страница 6: ...8 1 0 0 8 2 1 8 3 3 3 0 0 3 7 2 8 8 2 5 7 4 0 2 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 6 4 4 1 0 0 5 0 2 5 2 1 0 6 3 5 1 Size of unit for a proposed installation should be based on heat loss calculation...

Страница 7: ...r Grille Kit RG 2 through RG 5 or RFG 2 through RFG 5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must...

Страница 8: ...red See Figure 3 INSTALLATION INSTRUCTIONS 3 Mount bottom mounting bracket if used 4 Hook top rain flashing under back bend of top Top rain flashing is shipped attached to the back of the unit on the...

Страница 9: ...ual 2100 406A Page 9 of 16 FIGURE 4 WALL MOUNTING INSTRUCTIONS SEE FIGURE 3 MOUNTING INSTRUCTIONS FOR OPENING SIZES FIGURE 5 WALL MOUNTING INSTRUCTIONS SEE UNIT DIMENSIONS FIGURE 1 FOR ACTUAL DIMENSIO...

Страница 10: ...Manual 2100 406A Page 10 of 16 FIGURE 6 COMMON WALL MOUNTING INSTALLATIONS...

Страница 11: ...bottom left hand corner of the disconnect opening under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole...

Страница 12: ...Manual 2100 406A Page 12 of 16 FIGURE 7 LOW VOLTAGE WIRING DIAGRAM...

Страница 13: ...tion pressure drops and discharge pressure rises when the compressor is energized Reverse rotation also results in an elevated sound level over that with correct rotations as well as substantially red...

Страница 14: ...NTROL MODULE The compressor control module is optional on the models covered by this manual The compressor control is an anti short cycle lockout timer with high and low pressure switch monitoring and...

Страница 15: ...6 inches from compressor as shown in Table 6 The suction line temperatures shown in Table 6 are based upon 80 F dry bulb 67 F wet bulb 50 percent R H temperature and rated airflow across the evaporato...

Страница 16: ...e d i S h g i H 2 7 2 1 2 3 7 4 2 2 5 7 9 3 2 6 7 4 5 2 8 7 9 6 2 9 7 7 8 2 9 7 5 0 3 1 8 4 2 3 2 8 4 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 7 7 7 1 2 8 7 0 3 2 0 8 5 4 2 1 8 0 6 2 3 8 6 7...

Отзывы: