5 of 23

DUCT WORK

All duct work, supply and return, must be properly sized
for the design airflow requirement of the equipment.
Air Conditioning Contractors of America (ACCA) is an
excellent guide to proper sizing.  All duct work or
portions thereof not in the conditioned space should be
properly insulated in order to both conserve energy and
prevent condensation or moisture damage.

Refer to Maximum ESP of operation Electric Heat
Table.

Design the duct work according to methods given by the
Air Conditioning Contractors of America (ACCA).
When duct runs through unheated spaces, it should be
insulated with a minimum of one inch of insulation.  Use
insulation with a vapor barrier on the outside of the
insulation.  Flexible joints should be used to connect the
duct work to the equipment in order to keep the noise
transmission to a minimum.

For model series W48, W60 and W70, a 1/4 inch
clearance to combustible material for the first three feet
of duct attached to the outlet air frame is required.  See
Wall Mounting Instructions and Figures for further
details.

Ducts through the walls must be insulated and all joints
taped or sealed to prevent air or moisture entering the
wall cavity.

Some installations may not require any return air duct.  A
metallic return air grille is required with installations not
requiring a return air duct.  The spacing between louvers
on the grille shall not be larger than 5/8 inch.

Any grille that meets with 5/8 inch louver criteria may be
used.  It is recommended that Bard Return Air Grille Kit
RG2 through RG5 or RFG2 through RFG5 be installed
when no return duct is used.  Contact distributor or
factory for ordering information.  If using a return air
filter grille, filters must be of sufficient size to allow a
maximum velocity of 400 fpm.

NOTE: If no return air duct is used, applicable

installation codes may limit this cabinet to
installation only in a single story structure.

CONDENSATE DRAIN

A plastic drain hose extends from the drain pan at the
top of the unit down to the unit base.  There are
openings in the unit base for the drain hose to pass
through.  In the event the drain hose is connected to a
drain system of some type, it must be an open or vented
type system to assure proper drainage.

FILTERS

W48A12, W48L12 & W60A12, W60L12 ONLY

A 1-inch throw away filter is supplied with each unit.
The filter slides into position making it easy to service.
This filter can be serviced from the outside by removing
the service door.  A 1-inch washable filter and a 2-inch
pleated filter are also available as optional accessories.
The internal filter brackets are adjustable to
accommodate the 2-inch filter by bending the metal tabs
holding the 1-inch filter down.  There are two tabs on
each side of the filter.

NOTE:

W48A13, W48L13, W60A13, W60L13  and
W70A13, W70L13 models require the use of a
return air filter grille.

Содержание W48A12

Страница 1: ...D PACKAGE AIR CONDITIONERS MODELS W48A12 W48L12 W60A12 W60L12 W48A13 W48L13 W60A13 W60L13 W70A13 W70L13 Manual 2100 515B Supersedes 2100 515A File Volume III Tab 16 Date 12 15 11 Bard Manufacturing Co...

Страница 2: ...ssure 22 Table 6 Electrical Specifications W A L 22 Table 7 Optional Accessories 23 Table 8 Electric Heat 23 Getting Other Information and Publications 3 Wall Mount General Information Wall Mount Mode...

Страница 3: ...ter and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning...

Страница 4: ...ed as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made See Page 3 for in...

Страница 5: ...ring a return air duct The spacing between louvers on the grille shall not be larger than 5 8 inch Any grille that meets with 5 8 inch louver criteria may be used It is recommended that Bard Return Ai...

Страница 6: ...ot required 2 The unit itself is suitable for 0 inch clearance but the supply air duct flange and the first 3 feet of supply air duct require a minimum of 1 4 inch clearance to combustible material If...

Страница 7: ...View Ventilation Air Supply Air Opening Bracket Installation Return Air Opening Electric Heat Electrical Drain Built In Slope Top 2 Pitch Panel Built In Heater Access Circuit Breaker Disconnect Access...

Страница 8: ...w Filter Access Side Wall Mounting Brackets Air Opening Supply Installation Bracket Ventilation Air Air Opening Return Built In Heat Electric Drain Right Side View Top 2 Pitch Built In Slope Panel Acc...

Страница 9: ...Opening Supply Left Side View Installation Air Opening Return Heat Electric Top 2 Pitch Built In Slope Bracket Panel Access Heater Circuit Breaker Panel Lockable Disconnect Access Entrances Entrances...

Страница 10: ...ide View MIS 2612 Air Opening Supply Electrical Entrances Air Opening Return Heat Electric Top 2 Pitch Built In Slope Panel Access Heater Circuit Breaker Panel Lockable Disconnect Access Entrances Ent...

Страница 11: ...Mounting Brackets Side Wall Bracket Installation Electrical Bottom Filter Access Door 94 87 2 13 7 87 17 94 13 88 53 06 42 70 13 50 33 87 42 43 44 69 47 13 50 62 53 62 10 00 11 00 4 56 3 25 3 31 22 25...

Страница 12: ...ED NOTES RAIN FLASHING FOUR SIDES OF SUPPLY REQUIRED DIMENSIONS TO MAINTAIN IT IS RECOMMENDED THAT A BEAD OF TOP FLASHING AT TIME OF INSTALLATION COMBUSTIBLE MATERIALS THE SIDE MOUNTING FLANGES AND UN...

Страница 13: ...1 3 4 19 1 2 NOTES SUPPLY AIR Wall Opening and Hole Location View Right Side View TOP FLASHING AT TIME OF INSTALLATION SILICONE CAULKING BE PLACED BEHIND IT IS RECOMMENDED THAT A BEAD OF MIS 1444 A T...

Страница 14: ...combustible materials This is required for the first 3 feet of ducting It is important to insure that the 1 4 inch minimum spacing is maintained at all points Failure to do this could result in overhe...

Страница 15: ...1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I A C K E 1 000 B 1 000 I...

Страница 16: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALS...

Страница 17: ...circuit breaker that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high...

Страница 18: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 19: ...reverse rotation for several minutes the compressor s internal protector will trip All three phase compressors are wired identically internally As a result once the correct phasing is determined for a...

Страница 20: ...Lockout Sequence If the low pressure switch opens for more than 120 seconds the compressor contactor will de energize and go into a soft lockout Regardless the state of the low pressure switch the con...

Страница 21: ...l e d o M n o i s n e m i D A 1 L A 8 4 W 1 L A 0 6 W 5 7 1 1 L A 0 7 W 5 7 l e d o M d e t a R M F C d e t a R P S E d e d n e m m o c e R e g n a R w o l f r i A 2 1 A 8 4 W 0 0 4 1 0 2 0 0 4 1 0 0...

Страница 22: ...1 2 9 3 3 2 1 6 1 4 5 2 1 0 4 4 7 2 1 5 6 4 0 3 1 9 8 4 2 3 1 6 1 5 5 3 1 2 4 5 B D g e d 0 8 B W g e d 7 6 e d i S w o L e d i S h g i H 6 2 1 4 3 3 7 2 1 6 5 3 9 2 1 9 7 3 1 3 1 2 0 4 2 3 1 7 2 4 4...

Страница 23: ...C HEAT l e d o M 3 1 A 0 6 W 3 1 A 0 7 W 1 V 0 4 2 1 V 8 0 2 W K s p m A H U T B s p m A H U T B 5 8 0 2 0 5 0 7 1 1 8 1 0 0 8 2 1 0 1 6 1 4 0 3 1 4 3 2 6 3 0 0 6 5 2 W60A12 W60A13 W70A13 W48A12 W48A1...

Отзывы: