Manual 2100-703
Page
9 of 40
Width
(W)
Depth
(D)
Height
(H)
Supply
Return
A
B
C
B
E
F
G
I
J
K
L
M
N
O
P
Q
R
S
T
W18HB
W24HB
33.300 17.125
74.563
7.88 19.88 11.88 19.88 35.00 10.88 29.75 20.56 30.75 32.06 33.25 31.00 2.63 34.13 26.06 10.55 4.19 12.00
9.00
W30HB
W36HB
38.200 17.125
74.563
7.88 27.88 13.88 27.88 40.00 10.88 29.75 17.93 30.75 32.75 33.25 31.00 2.75 39.13 26.75 9.14
4.19 12.00
9.00
3"
Side View
High Voltage
Cond.
Electrical
Drain
Inlet
Air
Panel
Access
Heater
4° Pitch
Rain Hood
Built In
(Lockable)
Access Panel
Disconnect
Entrance
Electrical
Low Voltage
Entrance
C. Breaker/
Hood for CRV and
ECON models
only
1.250
H
D
J
C
2.13
A
I
K
7.00
MIS-3796
Electric
Heat
Ventilation Air
Front View
Air Outlet
Condenser
Filter Access Panel
Standard
flush vent
door for non-
ERV/CRV
Econ.
models
1
F
G
W
5.88
Supply Air Opening
Shipping
Location
Return Air Opening
Entrances
Electrical
Optional
(Built In)
Brackets
Mounting
Side Wall
Top Rain
Flashing
Bottom Installation
Bracket
Back View
T
O
E
R
S
S
S
S
S
M
.44
N
Q
B
P
L
All dimensions are in inches. Dimensional drawings are not to scale.
TABLE 1
Clearance Required for Service Access and
Adequate Condenser Airflow
Model
Left
Side
Right
Side
W18H
W24H
W30H
W36H
15"
20"
TABLE 2
Minimum Clearances Required
to Combustible Materials
Model
Supply Air Duct (1st 3')
Cabinet
W18H
W24H
0"
0"
W30H
W36H
1/4"
0"
1. Follow all national, state, and local codes and regulations regarding the installation of heating and cooling equipment regarding Single
Packaged Vertical Units (SPVU) including electrical access clearances.
2. Field ventilation installation with the unit installed requires 40" on the left or right side of the unit.
3. Bard recommends a minimum of 10' between the unit front condenser air outlet and solid objects including fences, walls, bushes and
other airflow obstructions.
4. Bard recommends a minimum of 15' between the condenser air outlets of two units that are facing each other.
5. Bard recommends a minimum clearance of 4" under the unit cabinet for condenser defrost drain age during heat pump operation.
FIGURE 2
Unit Dimensions