Manual 2100-604A 

Page 

6 of 28

Clearances Required for Service Access

and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

W18H, W24H, W30H, W36H

15"

20"

W42H, W48H, W60H

20"

20"

Minimum Clearances Required to

Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST 3'

CABINET

W18H, W24H

0"

0"

W30H, W36H

1/4"

0"

W42H, W48H, W60H

1/4"

0"

INSTALLATION

        WARNING

Failure to provide the 1/4" clearance between 

the supply duct and a combustible surface 

for the first 3ʹ of duct can result in fire causing 

damage, injury or death.

WALL MOUNTING INFORMATION

1.  Two holes for the supply and return air openings 

must be cut through the wall as shown in Figure 3.

2.  On wood frame walls, the wall construction must 

be strong and rigid enough to carry the weight of 
the unit without transmitting any unit vibration.

3.  Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installed unit.

MOUNTING THE UNIT

1.  These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides.  A bottom mounting bracket, attached 
to skid for shipping, is provided for ease of 
installation, but is not required.

2.  The unit itself is suitable for 0" clearance, but the 

supply air duct flange and the first 3' of supply 
air duct require a minimum of 1/4" clearance to 
combustible material for model series W30, W36, 
W42, W48 and W60.  However, it is generally 
recommended that a 1" clearance is used for 
ease of installation and maintaining the required 
clearance to combustible material.  See Figure 3 
for details on opening sizes.

3.  Locate and mark lag bolt locations and bottom 

mounting bracket location (see Figure 3).

4.  Mount bottom mounting bracket.

5.  Hook top rain flashing, attached to front-right of 

supply flange for shipping, under back bend of top.

 6.  Position unit in opening and secure with 5/16" lag 

bolts; use 7/8" diameter flat washers on the lag 
bolts.

7.  Secure rain flashing to wall and caulk across entire 

length of top (see Figure 3).

8.  For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction).  Be sure to 
observe required clearance if combustible wall.

9.  On side-by-side installations, maintain a minimum 

of 20" clearance on right side to allow access to 
control panel and heat strips, and to allow proper 
airflow to the outdoor coil.  Additional clearance 
may be required to meet local or national codes.

NOTE:

 

Refer to Figures 2 – 7 for dimensions and   

 

various mounting configurations.

Содержание W18H2-A

Страница 1: ...6H2 B W36H2 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 604A Supersedes 2100 604 Date 2 1 16 W42H2 A W42H2 B W42H2 C W48H2 A W48H2 B W48H2 C W60H2 A W60H2 B W60H2 C...

Страница 2: ...25 Tables 7 Maximum ESP Electric Heat Only 26 Table 8 Electric Heat 26 Table 9 Optional Accessories 27 Table 10 Vent and Control Options 28 Getting Other Information and Publications 3 Wall Mount Gene...

Страница 3: ...ummer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...for information on codes and standards Size of unit for a proposed installation should be based on heat loss gain calculation made according to methods of Air Conditioning Contractors of America ACCA...

Страница 5: ...ugh RG 5W or RFG 2W through RFG 5W be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient si...

Страница 6: ...self is suitable for 0 clearance but the supply air duct flange and the first 3 of supply air duct require a minimum of 1 4 clearance to combustible material for model series W30 W36 W42 W48 and W60 H...

Страница 7: ...Optional top outlet factory installed only for W30H and W36H models only FIGURE 2 All dimensions are in inches Dimensional drawings are not to scale W H RIGHT UNIT Dimensions of Basic Unit for Archite...

Страница 8: ...ING ENTIRE LENGTH OF TOP TOP WALL OF CAULKING ALONG PANEL FOAM AIR SEAL WALL STRUCTURE NOTES RAIN FLASHING HEATER ACCESS TOP FLASHING AT TIME OF INSTALLATION THE SIDE MOUNTING FLANGES AND UNDER SILICO...

Страница 9: ...CLEARANCE ON ALL RAIN FLASHING COMBUSTIBLE MATERIALS DUCT TOP FLASHING AT TIME OF INSTALLATION 1 4 MIN CLEARANCE FROM REQUIRED DIMENSIONS TO MAINTAIN OPENING ENTIRE LENGTH OF TOP MATERIALS NOTES OF CA...

Страница 10: ...4 32 12 5 1 2 2 NOTES WALL STRUCTURE 1 SUPPLY AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNT...

Страница 11: ...ombustible materials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the c...

Страница 12: ...UPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR ACTUAL DIME...

Страница 13: ...WALL OPENING W GRILLE SUPPLY DUCT MAYBE LOCATED IN AN ATTIC OR BELOW CEILING RAFTERS AS SHOWN CEILING RAIN RETURN AIR SLEEVE WALL SUPPLY AIR DUCT RAFTERS RAFTERS RETURN AIR OPENING W GRILLE RAIN FALSE...

Страница 14: ...er that is to be used with the equipment The correct size must be used for proper circuit protection and also to assure that there will be no nuisance tripping due to the momentary high starting curre...

Страница 15: ...iple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be...

Страница 16: ...es the compressor s internal protector will trip All three phase ZP compressors are wired identically internally As a result once the correct phasing is determined for a specific system or installatio...

Страница 17: ...cycle the outdoor motor stops electric heaters are energized and hot gas passing through the outdoor coil melts any accumulated frost When the temperature rises to approximately 57 F the coil temperat...

Страница 18: ...ls for a few seconds can do this Low Pressure Switch Bypass Operation The control has a selectable SW1 low pressure switch bypass set up to ignore the low pressure switch input during the first 30 60...

Страница 19: ...ansformer is bad or the unit wiring is incorrect 10 Check for Compressor output signal Is there 24 volts AC between CC C Yes go to Step 12 No go to Step 13 11 No Y compressor input signal Check thermo...

Страница 20: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Страница 21: ...h this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information shou...

Страница 22: ...573 85 DB 72 WB Low Side High Side 136 349 138 373 140 398 142 423 144 450 146 477 149 505 151 534 153 563 156 593 W42H2 75 DB 62 WB Low Side High Side 127 354 130 372 132 392 134 413 135 437 136 461...

Страница 23: ...H2 B00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2 C00 C0Z C06 460 3 1 1 11 21 15 25 14 10 14 10 W30H2 A00 A0Z A05 A10 230 208 1 1 1 1 or 2 24 50 76 35 50 80 8 8 4 10 10 8 50 26 50 30 8 10 10 1...

Страница 24: ...A Ckt B Ckt A Ckt B W24H2DA00 A0Z A04 A08 230 208 1 1 1 1 or 2 24 44 65 25 50 70 10 8 6 10 10 8 44 21 45 25 8 10 10 10 W24H2DB00 B0Z B06 230 208 3 1 1 17 35 20 40 12 8 12 10 W24H2DC00 C0Z C06 460 3 1...

Страница 25: ...High Speed Low Speed High Speed Low Speed Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil Dry Coil Wet Coil 0 1 2 3 4 5 10...

Страница 26: ...W24H B00 B06 50 50 W24H C00 C06 50 50 Model Front Outlet Top Outlet Low Speed High Speed Low Speed High Speed W30H W36H A00 A05 A10 A15 50 40 35 35 50 50 40 40 50 40 25 NA 50 50 40 NA W30H W36H B00 B...

Страница 27: ...EHWH36 A05 X EHWH36 A10 X EHWH36 A15 X EHWH03 B06 X EHW36H B06 X EHWH03 B09 X X EHW30H B15 X EHWC03A C06 X X EHWH42 A05 X X EHWH42 A10 X X EHWH42 A15 X X EHWH 04 A20 X X EHWH05 B06 X X EHWH05 B09 X X...

Страница 28: ...3 Commercial Ventilator Power Return X ECONWMS E3B Economizer X ERVF A3 Energy Recovery Ventilator 230 Volt X ERVF C3 Energy Recovery Ventilator 460 Volt X BFAD 5 Barometric Fresh Air Damper Standard...

Отзывы: