Page 69
6.4.3.3 Unit #1 Economizer
The override status box displays the current override condition of the Unit #1 Economizer. It will
read “Yes” if the output has been overridden on or off.
The output value box displays the current condition of the Unit #1 Economizer. It will read either
on or off.
To override the Unit #1 Economizer on click the Output Verify Action button. Select the
“Override Output ON” item and click OK. The override status box will display yes and the Output status
will display ON.
To override the Unit #1 Economizer off click the Output Verify Action button. Select the
“Override Output OFF” item and click OK. The override status box will display yes and the Output
status will display OFF.
To clear an override, click the Output Verify Action button. Select “Clear RAM Override Flag,
6.4.3.4 Unit #1 Heater
The override status box displays the current override condition of the Unit #1 Heater. It will read
“Yes” if the output has been overridden on or off.
The output value box displays the current condition of the Unit #1 Heater. It will read either ON
or OFF.
To override the Unit #1 Heater on click the Output Verify Action button. Select the “Override
Output ON” item and click OK. The override status box will display yes and the Output status will
display ON.
To override the Unit #1 Heater off click the Output Verify Action button. Select the “Override
Output OFF” item and click OK. The override status box will display yes and the Output status will
display OFF.
To clear an override, click the Output Verify Action button. Select “Clear RAM Override Flag,
Содержание TCS22 Series
Страница 14: ...2100 444 003A Page 8 Figure 1 Front Cover...
Страница 15: ...2100 444 003A Page 9 Figure 2 Control Location...
Страница 21: ...2100 444 003A Page 15 Figure 4 External Wiring...
Страница 22: ...2100 444 003A Page 16 Figure 5 Internal Wiring Figure 6 Power...
Страница 23: ...2100 444 003A Page 17 Backup System...
Страница 86: ...2100 444 003A Page 80 6 4 9 DIAL OUT TAB...