Bard T36S1-A Скачать руководство пользователя страница 6

Manual 2100-547J 

Page 

6 of 26

INSTALLATION

Wall Mounting Information

1.  Two holes for the supply and return air openings 

must be cut through the wall as shown in Figure 3 
on page 8.

2.  On wood frame walls, the wall construction must 

be strong and rigid enough to carry the weight of 
the unit without transmitting any unit vibration.

3.  Concrete block walls must be thoroughly inspected 

to insure that they are capable of carrying the 
weight of the installed unit.

Mounting the Unit

1.  These units are secured by wall mounting brackets 

which secure the unit to the outside wall surface at 
both sides. A bottom mounting bracket, attached 
to skid for shipping, is provided for ease of 
installation, but is not required.

2.  The unit itself is suitable for 0" clearance, but the 

supply air duct flange and the first 3' of supply 
air duct require a minimum of 1/4" clearance to 
combustible material. However, it is generally 
recommended that a 1" clearance is used for 
ease of installation and maintaining the required 
clearance to combustible material. See Figure 3 
(page 8) for details on opening sizes.

3.  Locate and mark lag bolt locations and bottom 

mounting bracket location. See Figure 3.

4.  Mount bottom mounting bracket.
5.  Hook top rain flashing, attached to front-right of 

supply flange for shipping, under back bend of top.

6.  Position unit in opening and secure with 5/16" lag 

bolts; use 7/8" diameter flat washers on the lag bolts.

7.  Secure rain flashing to wall and caulk across entire 

length of top. See Figure 3.

8.  For additional mounting rigidity, the return air 

and supply air frames or collars can be drilled 
and screwed or welded to the structural wall itself 
(depending upon wall construction). Be sure to 
observe required clearance if combustible wall.

Placement

1.  On side-by-side installations, maintain a minimum 

of 20" clearance on right side to allow access to 
control panel and heat strips, and to allow proper 
airflow to the outdoor coil. Additional clearance 
may be required to meet local or national codes.

2.  Care should be taken to ensure that the 

recirculation and obstruction of condenser 
discharge air does not occur. Recirculation of 
condenser discharge air can be from either a 
single unit or multiple units. Any object such 
as shrubbery, a building or a large object can 
cause obstructions to the condenser discharge 
air. Recirculation or reduced airflow caused by 
obstructions will result in reduced capacity, 
possible unit pressure safety lockouts and reduced 
unit service life.

 

For units with a blow-through condenser, such as 
the T**S 11EER units, it is recommended there 
be a minimum distance of 15' between the front of 
the unit and any barrier or 20' between the fronts 
of two opposing (facing) units.

Required Steps after Final Placement 

(T48S & T60S Units Only)

The compressor is secured to the unit base for 
shipping. Although unit will perform as designed 
with the compressor secured in place, there may be 
noticeable additional noise and vibration. To obtain 
the lowest noise and vibration levels, remove the 

        WARNING

Failure to provide the 1/4" clearance between 
the supply duct and a combustible surface 

for the first 3ʹ of duct can result in fire causing 

damage, injury or death.

        WARNING

Failure to bolt the unit to the wall could result 
in the unit falling, causing injury or death! 
Follow all mounting instructions.

Clearances Required for Service Access

and Adequate Condenser Airflow

MODELS

LEFT SIDE

RIGHT SIDE

T36S, T42S, T48S, T60S

20"

20"

Minimum Clearances Required to

Combustible Materials

MODELS

SUPPLY AIR DUCT

FIRST 3'

CABINET

T36S, T42S, T48S, T60S

Содержание T36S1-A

Страница 1: ...B T36S1 C T42S1 A T42S1 B T42S1 C T48S1 A T48S1 B T48S1 C T60S1 A T60S1 B T60S1 C Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 547J Supersedes 2100 547I Date 5 14 21 T...

Страница 2: ...le 7 Indoor Blower Performance 23 Table 8 Dehumidification Relay Logic Board 26 Getting Other Information and Publications 3 Wall Mount General Information 4 Wall Mount Model Nomenclature 4 Shipping D...

Страница 3: ...itioning ACCA Manual J Duct Design for Residential Winter and Summer Air Conditioning and Equipment Selection ACCA Manual D For more information contact these publishers ACCA Air Conditioning Contract...

Страница 4: ...ion made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Association for the Inst...

Страница 5: ...hrough RFG5 be installed when no return duct is used Contact distributor or factory for ordering information If using a return air filter grille filters must be of sufficient size to allow a maximum v...

Страница 6: ...ction Be sure to observe required clearance if combustible wall Placement 1 On side by side installations maintain a minimum of 20 clearance on right side to allow access to control panel and heat str...

Страница 7: ...g brackets after the unit is in its final operating location Remove the side grille to gain access to the compressor shipping brackets The brackets are located on the compressor double isolation base...

Страница 8: ...Y AIR IT IS RECOMMENDED THAT A BEAD OF OPENING Right Side View RAIN FLASHING SILICONE CAULKING BE PLACED BEHIND RECOMMENDED 1 CLEARANCE FROM THE SIDE MOUNTING FLANGES AND UNDER TOP FLASHING AT TIME OF...

Страница 9: ...rials This is required for the first 3 of ducting It is important to insure that the 1 4 minimum spacing is maintained at all points Failure to do this could result in overheating the combustible mate...

Страница 10: ...IR FACTORY SUPPLIED RAIN FLASHING SUPPLY AIR MIS 548 A SIDE VIEW I A C K E 1 000 B 1 000 SUPPLY DUCT OVER FRAME INTERIOR FINISHED WALL ALL AROUND DUCT FRAMING MATERIAL EXTERIOR FINISH WALL OPENING FOR...

Страница 11: ...best unit performance and efficiency Review duct grille or return duct work Avoid using restrictive duct work to Unit Mount Return Grille Fixed Blade Wall wall Outside Wall Ducted Installations Adjus...

Страница 12: ...under the disconnect access panel straight out This tab will now line up with the slot in the door When shut a padlock may be placed through the hole in the tab preventing entry See Three Phase Scroll...

Страница 13: ...ple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be u...

Страница 14: ...reverse operation for over 1 hour may have a negative impact on the bearing due to oil pump out NOTE If compressor is allowed to run in reverse rotation for several minutes the compressor s internal...

Страница 15: ...com en SCCA07H See the replacement parts manual for replacement core part numbers Defrost Cycle The defrost cycle is controlled by temperature and time on the solid state heat pump control When the o...

Страница 16: ...there is likely no actual frost on the outdoor coil in this artificial test condition There is also a 5 minute compressor time delay function built into the HPC This is to protect the compressor from...

Страница 17: ...Heat pump control defective Check for 24 V between RV C and B C 1 Check circuit control wiring 2 Replace heat pump control Reversing valve solenoid coil defective Check for open or shorted coil Replac...

Страница 18: ...16 0 144374 22 0 43554 60 0 15310 98 0 6098 15 0 139576 23 0 42295 61 0 14921 99 0 5961 14 0 134956 24 0 41077 62 0 14544 100 0 5827 13 0 130506 25 0 39898 63 0 14177 101 0 5697 12 0 126219 26 0 3875...

Страница 19: ...ng with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this informatio...

Страница 20: ...548 85 deg DB 72 deg WB Low SIde High Side 144 337 146 360 147 384 148 408 149 434 151 459 153 485 154 511 156 539 159 567 T48S 75 deg DB 62 deg WB Low SIde High Side 137 326 138 339 139 356 140 375 1...

Страница 21: ...r 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 6 10 10 10 10 10 10 10 10 10 10 T60S1 B00 B0Z B09 B15 B18 230 208 60 3 1...

Страница 22: ...or 2 1 or 2 1 or 2 45 71 97 97 113 60 80 100 100 125 8 4 3 3 2 10 8 8 8 6 45 45 45 45 26 52 52 52 26 50 50 50 50 30 60 60 60 30 8 8 8 8 10 6 6 6 10 10 10 10 10 10 10 10 10 10 T60S1DB00 B0Z DB09 DB15 D...

Страница 23: ...inches WC shown is with 2 thick disposable filter Blower only CFM is the total air being circulated during continuous fan mode Airflow remains constant Blower only CFM reduces during continuous fan m...

Страница 24: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Страница 25: ...site side of the connector plug and gently pulling the plug out of the connector socket in the control DO NOT PULL ON THE WIRES GRIP THE PLUG ONLY 6 The control module is now completely detached from...

Страница 26: ...ied X X X X X X X X Y Y1 B G 2nd Heating Unoccupied X X X X X X X Y Y1 B G O1 2nd Heating Occupied X X X X X X X X X Y Y1 B G O1 W3 2nd Heat Dehum Occupied X X X X X X X X X X X Y Y1 B G W3 2nd Heat D...

Отзывы: