DEFROST CYCLE

The defrost cycle is controlled by temperature and time
on the solid state heat pump control.

When the outdoor temperature is in the lower 40°F
temperature range or colder, the outdoor coil
temperature is 32°F or below.  This coil temperature is
sensed by the coil sensor mounted near the bottom of
the outdoor coil.  Once coil temperature reaches 30°F or
below, the coil sends a signal to the control logic of the
heat pump control and the defrost timer will start.

After 30 minutes at 30°F or below, the heat pump
control will place the system in the defrost mode.

During the defrost mode the refrigerant cycle switches
back to the cooling cycle, the outdoor motor stops,
electric heaters are energized, and hot gas passing
through the outdoor coil melts any accumulated frost.
When the temperature rises to approximately 57°F, the
coil sensor will send a signal to the heat pump control
which will return the system to heating operations
automatically.

If some abnormal or temporary condition such as a high
wind causes the heat pump to have a prolonged defrost
cycle, the heat pump control will restore the system to
heating operation automatically after 10 minutes.

There are three settings on the heat pump control – 30, 60
and 90-minute.  Models are shipped wired on the 30-
minute setting for greatest operating economy.  If special
circumstances require a change to another time, remove
wire connected to terminal 30 and reconnect to desired
terminal.  Refer to Figure 21.  The manufacturer’s
recommendation is for 30-minute defrost cycles.

There is a cycle speed up jumper on the control.  This
can be used to reduce the time between defrost cycle
operation without waiting for time to elapse.

Use a small screwdriver or other metallic object, or
another 1/4 inch QC,  to short between the 

SPEEDUP

terminals to accelerate the HPC timer and initiate
defrost.  Be careful not to touch any other terminals with
the instrument used to short the 

SPEEDUP 

terminals.  It

may take up to 10 seconds with the 

SPEEDUP

 terminals

shorted for the speedup to be completed and the defrost
cycle to start.

As soon as the defrost cycle kicks in remove the
shorting instrument from the SPEEDUP terminal.

Otherwise the timing will remain accelerated and run
through the 1-minute maximum defrost length sequence
in a matter of seconds and will automatically terminate
the defrost sequence.

There is an initial defrost jumper (sen jmp) on the
control that can be used at any outdoor ambient during
the heating cycle to simulate a 0° coil temperature.  This
can be used to check defrost operation of the unit
without waiting for the outdoor ambient to fall into the
defrost region.

By placing a jumper across the 

SEN JMP

 terminals (a

1/4 inch QC terminal works best) the defrost sensor
mounted on the outdoor coil is shunted out and will
activate the timing circuit.  This permits the defrost
cycle to be checked out in warmer weather conditions
without the outdoor temperature having to fall into the
defrost region.

In order to terminate the defrost test the 

SEN JMP

jumper must be removed.  If left in place too long the
compressor could stop due to the high pressure control
opening because of high pressure condition created by
operating in the cooling mode with outdoor fan off.
Pressure will rise fairly fast as there is likely no actual
frost on the outdoor coil in this artificial test condition.

There is also a 5-minute compressor time delay function
built into the HPC.  This is to protect the compressor
from short cycling conditions.  In some instances, it is
helpful to the service technician to override or speed up
this timing period, and shorting out the 

SPEEDUP

terminals for a few seconds can do this.

FIGURE  22

LOW PRESSURE CONTROL BYPASS TIMER

Содержание QTEC QH243

Страница 1: ...62 QH422 QH482 QH602 QTEC SERIES PACKAGED HEAT PUMP INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 420H Supersedes 2100 4...

Страница 2: ...2 Air Seal on Bottom of Unit 8 Figure 3 Removal of Unit From Skid 8 Figure 4 Unit on Appliance Cart for Moving 9 Figure 5 Installation With Free Blow Plenum 10 Figure 6 Ducted Application 10 Figure 7...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...0 0 1 4 0 5 1 0 5 1 9 4 0 6 8 6 3 0 5 1 9 4 0 6 8 6 3 0 5 1 9 4 QTEC Series General Information QTEC MODEL NOMENCLATURE QH 36 2 A 10 X X X X X X SPECIAL UNITS L Low Ampacity Circuit REVISION VOLTS PHA...

Страница 5: ...R I C R E K A E R B 2 D L E I F R E W O P E R I W E Z I S 2 D N U O R G E R I W E Z I S 3 M U M I N I M T I U C R I C Y T I C A P M A 1 M U M I X A M L A N R E T X E R O E S U F T I U C R I C R E K A...

Страница 6: ...H Q 6 0 B 9 0 B 5 5 1 B 3 8 0 2 0 3 2 1 1 1 1 6 2 4 4 3 5 3 5 0 4 0 5 0 6 0 6 8 8 6 6 0 1 0 1 0 1 0 1 Z 0 C 2 8 4 H Q 6 0 C 9 0 C 5 5 1 C 3 0 6 4 1 1 1 1 4 1 3 2 7 2 7 2 5 1 5 2 0 3 0 3 4 1 0 1 0 1 0...

Страница 7: ...Manual 2100 420H Page 7 of 34 FIGURE 1 UNIT DIMENSIONS...

Страница 8: ...emoved to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down th...

Страница 9: ...eparate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attache...

Страница 10: ...Manual 2100 420H Page 10 of 34 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM...

Страница 11: ...ither free blow with the use of QPB Plenum Box or a duct supply air system The QPB and QPBHW Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the fro...

Страница 12: ...cated on the bottom right side of the unit The side drain is shipped with a plug installed The side drain requires a water trap for proper drainage See Figure 9 The drain can be routed through the flo...

Страница 13: ...pressure device This indicates that the unit needs to be serviced FIGURE 12 UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL E...

Страница 14: ...to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of ste...

Страница 15: ...mplete current carrying capacity data on the various insulation grades of wiring material All wiring must conform to NEC and all local codes The electrical data lists fuse and wire sizes 75 C copper f...

Страница 16: ...talled ventilation option E terminal or pin 3 of P2 is the emergency heat input This terminal energizes the emergency heat relay R O F S N O I T C E N N O C E G A T L O V W O L L O R T N O C C D D y l...

Страница 17: ...t a e H e g a t s 3 l o o C e g a t s 3 c i n o r t c e l E e l b a m m a r g o r P n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0...

Страница 18: ...16 REMOTE THERMOSTAT WIRING DIAGRAM X THERMOSTAT OPTION NOTE On option X or A the CS2000A1 or other field provided means to control ventilation must be used if any of the motorized ventilation option...

Страница 19: ...4 FIGURE 17 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM A THERMOSTAT OPTION NOTE On option X or A the CS2000A1 or other field provided means to control ventilation must be used if any of the motorized vent...

Страница 20: ...Manual 2100 420H Page 20 of 34 FIGURE 18 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION...

Страница 21: ...sor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compre...

Страница 22: ...side panel g Remove screws that attach the duct work to the unit flanges This unit is equipped with four rollers mounted to the base For ease of pulling unit out from the wall you may want to remove t...

Страница 23: ...t be raised up and the bottom can be pulled toward the front of the unit and removed VENT OPTIONS BAROMETRIC FRESH AIR DAMPER Standard Before starting make sure the power has been turned off The retur...

Страница 24: ...Manual 2100 420H Page 24 of 34 FIGURE 19 FRESH AIR DAMPER REMOVAL MOUNTING SCREW...

Страница 25: ...Manual 2100 420H Page 25 of 34 FIGURE 20 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 26: ...ontrol panel The lockout circuit will hold compressor off line When the system problem is corrected the unit operation can be restored by turning of the main power supply off and then back on or reset...

Страница 27: ...another 1 4 inch QC to short between the SPEEDUP terminals to accelerate the HPC timer and initiate defrost Be careful not to touch any other terminals with the instrument used to short the SPEEDUP t...

Страница 28: ...h t l o r t n o c p m u p t a e h e h t n o 1 L o t C d n a Y o t C m o r f t n e s e r p s i V 4 2 f I l o r t n o c p m u p t a e h e h t e c a l p e r C C t a t n e s e r p s i V 4 2 o n d n a d e...

Страница 29: ...1 9 1 2 6 2 1 9 8 0 2 2 1 8 0 1 8 1 1 2 7 2 4 1 1 5 7 5 0 1 1 0 1 0 7 0 1 4 7 5 3 0 1 0 6 2 0 0 1 4 6 0 7 9 1 8 9 3 9 8 0 0 1 9 9 3 1 8 8 1 7 3 5 8 9 9 6 2 8 1 2 1 0 8 2 3 6 7 7 0 3 2 5 7 0 1 9 2 7 0...

Страница 30: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check...

Страница 31: ...2 0 CONTROL control in cast aluminum can with air vents on the back of the can WITH AN ECM 2 3 CONTROL control containing black potting for water protection in black deep drawn steel case with no ven...

Страница 32: ...with a refrigerant charge resulting in a Super Heat as shown in Table 8 If correct charge is in doubt recover the refrigerant and recharge per the charge on the unit rating plate L E D O M A N O I S N...

Страница 33: ...B W 2 6 e d i S w o L e d i S h g i H 4 7 2 1 2 4 7 5 1 2 5 7 3 3 2 6 7 1 5 2 7 7 9 6 2 8 7 7 8 2 9 7 5 0 3 0 8 3 2 3 1 8 1 4 3 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 9 7 9 1 2 9 7 0 2 2 0 8 9...

Страница 34: ...4 3 9 1 5 4 9 9 1 9 4 5 0 2 4 5 1 1 2 8 5 7 1 2 2 6 2 2 2 7 6 8 2 2 2 6 3 H Q 0 7 e d i S w o L e d i S h g i H 3 1 7 4 1 7 1 3 5 1 1 2 9 5 1 5 2 4 6 1 0 3 1 7 1 4 3 6 7 1 8 3 2 8 1 2 4 8 8 1 6 4 4 9...

Отзывы: