LOW PRESSURE BYPASS TIMER SWITCH
(FACTORY SETTING 120 SECONDS)
ACCUMULATED RUN TIME SELECTOR
(FACTORY SETTING 30 MIN.)
MIS-2684 A
ON
OFF
High Pressure Switch Operation
– The control has a
built-in lockout system that allows the unit to have the
high pressure switch trip up to two times in one hour and
only encounter a “soft” lockout. A “soft” lockout shuts
the compressor off and waits for the pressure switch to
reset, which at that point then allows the compressor to
be restarted as long as the 5-minute short cycle timer has
run out. If the high pressure switch trips a third time
within one hour, the unit is in “hard” lockout indicating
something is wrong and it will not restart itself.
Figure 24