background image

Manual

2100-522B

Page

29 of 38

All three phase scroll compressors used in the Q-T

EC

series are wired identically internally.  As a result, once
the correct phasing is determined for a specific system
or installation, connecting properly phased power leads
to the same Fusite terminal should maintain proper
rotation direction.  The direction of rotation of the
motor may be changed by reversing any two line
connections to the unit.

COMPRESSOR CONTROL MODULE

The compressor control module is standard on all
models covered by this manual.  The compressor
control is an anti-short cycle/lockout timer with high
and low pressure switch monitoring and alarm relay
output.

Adjustable Delay On Make And Break Timer

On initial power up or any time power is interrupted to
the unit, the 

delay on make

 period begins, which will be

2 minutes plus 10% of the 

delay on break

 setting.

When the delay on make is complete and the high
pressure switch (and low pressure switch if employed)
is closed, the compressor contactor is energized.

Upon shutdown the delay or break timer starts and
prevents restart until the delay on break and delay on
make periods have expired.

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

High Pressure Switch and Lockout Sequence

If the high pressure switch opens, the compressor
contactor will de-energize immediately.  The lockout
timer will go into a 

soft lockout

 and stay in soft lockout

until the high pressure switch closes and the delay on
break time has expired.  If the high pressure switch
opens again in this same operating cycle the unit will
go into 

manual lockout

 condition and the alarm relay

circuit will energize.  Recycling the wall thermostat
resets the manual lockout.

Low Pressure Switch, Bypass, and Lockout
Sequence

If the low pressure switch opens for more than 120
seconds, the compressor contactor will de-energize and
go into a soft lockout.  Regardless the state of the low
pressure switch, the contactor will reenergize after the
delay on make time delay has expired.  If the low
pressure switch remains open, or opens again for longer
than 120 seconds the unit will go into manual lockout
condition and the alarm relay circuit will energize.
Recycling the wall thermostat resets the manual
lockout.

Alarm Relay Output

Alarm terminal is output connection for applications
where alarm relay is employed.  This terminal is
powered whenever compressor is locked out due to HPC
or LPC sequences as described.

NOTE: Both high and low pressure switch controls are

inherently automatic reset devices.  The high
pressure switch and low pressure switch cut out
and cut in settings are fixed by specific air
conditioner or heat pump unit model.  The
lockout features, both soft and manual, are a
function of the Compressor Control Module.

ADJUSTMENTS

Adjustable Delay on Make and Delay on Break
Timer

The potentiometer is used to select Delay on Break time
from 30 seconds to 5 minutes.  Delay on Make (DOM)
timing on power-up and after power interruptions is
equal to 2 minutes plus 10% of Delay on Break (DOB)
setting:

0.5 minute (30 seconds)

DOB = 123 second DOM

1.0 minute (60 seconds)

DOB = 126 second DOM

2.0 minute (120 seconds) DOB = 132 second DOM
3.0 minute (180 seconds) DOB = 138 second DOM
4.0 minute (240 seconds) DOB = 144 second DOM
5.0 minute (300 seconds) DOB = 150 second DOM

During routine operation of the unit with no power
interruptions the compressor will operate on demand
with no delay.

Typical Settings for Dual Unit Installation:

Unit 1:  DOB set at 2 minutes, and DOM is 132 seconds

Unit 2:  DOB set at 4 minutes, and DOM is 144 seconds

SERVICE HINTS

1. Caution user to maintain clean air filters at all

times.  Also, not to needlessly close off supply air
registers.  This may reduce airflow through the
system, which shortens equipment service life as
well as increasing operating costs and noise
levels.

2. Check all power fuses or circuit breakers to be

sure they are the correct rating.

3. Periodic cleaning of the outdoor coil to permit

full and unrestricted airflow circulation is
essential.

Содержание Q24A1 Installationair conditioner

Страница 1: ...g Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 522B Supersedes 2100 522A File Vol II Tab 14 Date 12 15 11 Models Q24A1 Q30A1 Q36A1 Q42A1 Q48A1 Q60A1 Q TEC SERIES PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS ...

Страница 2: ...lt In Electric Heat Table 5 Table 2 Electrical Specifications 6 Table 3 Operating Voltage Range 20 Table 4 Wall Thermostats 22 Table 5 Fan Blade Dimensions 37 Table 6 Indoor Blower Performance 37 Table 7 Cooling Pressure 38 Getting Other Information and Publications For more information contact these publishers 3 Q TEC General Information Q TEC Model Nomenclature 4 Shipping Damage 8 Unit Removal F...

Страница 3: ...mmer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue Washington DC 20009 Telephone 202 483 9370 Fax 202 234 4721 ANSI American National Standards Institute 11 West Street 13th Floor New York NY 10036...

Страница 4: ...Economizer Not available on dehumidification versions P Commercial Ventilator Motorized w Exhaust Power Return V Commercial Ventilator Motorized w Exhaust Spring Return R Energy Recovery Ventilator w Independent Intake Exhaust Control REVISION VOLTS PHASE A 230 208 60 1 B 230 208 60 3 C 460 60 3 CLIMATE CONTROL2 STANDARD UNITS DEHUMIDIFICATION UNITS X None 2 X None 2 A Electronic Non Prog E Electr...

Страница 5: ...0 2 1 V 0 4 2 1 V 8 0 2 3 V 0 8 4 W K H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B H U T B 0 5 0 8 3 6 1 0 9 2 2 1 0 8 3 6 1 0 9 2 2 1 0 6 0 0 5 0 2 0 6 3 5 1 0 0 5 0 2 0 6 3 5 1 0 0 5 0 2 0 0 5 0 2 0 0 5 0 2 0 6 3 5 1 0 0 5 0 2 0 9 0 0 7 0 3 0 0 0 3 2 0 0 7 0 3 0 0 0 3 2 0 0 7 0 3 0 0 7 0 3 0 0 7 0 3 0 0 0 ...

Страница 6: ...1 A 0 3 Q 5 0 A 0 1 A 1 8 0 2 0 3 2 1 1 1 5 2 2 3 7 5 5 3 5 3 0 6 8 8 6 0 1 0 1 0 1 Z 0 B 1 A 0 3 Q 6 0 B 9 0 B 2 1 B 3 8 0 2 0 3 2 1 1 1 1 8 1 5 2 4 3 3 4 5 2 5 2 5 3 5 4 0 1 0 1 8 6 0 1 0 1 0 1 0 1 Z 0 C 1 A 0 3 Q 6 0 C 9 0 C 2 1 C 3 0 6 4 1 1 1 1 1 1 4 1 8 1 3 2 5 1 5 1 0 2 5 2 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A 1 A 6 3 Q 5 0 A 0 1 A 5 1 A 1 8 0 2 0 3 2 1 1 1 2 r o 1 9 2 4 3 8 5 4 8 5 4 5 4 ...

Страница 7: ...Manual 2100 522B Page 7 of 38 FIGURE 1 UNIT DIMENSIONS ...

Страница 8: ...removed to provide a place to hold the unit The unit can be slid forward on the skid until the front wheels hang over the edge of the skid See Figure 3 B The unit can be tipped forward and slid down the edge of the skid until the front wheels touch the ground See Figure 3 C The wheels will not roll They are shipped from the factory locked so they will not roll The back of the skid will have to be ...

Страница 9: ...instructions and any instructions packaged with any separate equipment required to make up the entire air conditioning system should be carefully read before beginning the installation Note particularly Start Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in an...

Страница 10: ...Manual 2100 522B Page 10 of 38 FIGURE 6 DUCTEDAPPLICATION FIGURE 5 INSTALLATION WITH FREE BLOW PLENUM ...

Страница 11: ...lly adjustable louvers on the front discharge grille For hot water coil option a QPBHWxx F for free blow or QPBHWxx D for ducted airflow is used When used with a ducted supply a QCX Cabinet Extension can be used to conceal the duct work above the unit to the ceiling This extends 20 above the unit for a total height above the floor of 10 7 8 The unit is equipped with a variable speed indoor blower ...

Страница 12: ...m the wall When the side drain is used the plug must be removed and installed in the rear drain outlet The rear drain can be used with wall thickness of up to 10 inches where a water trap can be installed between the unit and the interior wall See Figure 10 The trap cannot extend beyond the edge of the unit or it will interfere with the wall mounting bracket The drain can be routed through the flo...

Страница 13: ... REAR DRAIN TOP VIEW WALL MAXIMUM 10 FOR REAR DRAIN COUPLINGS NOT SHOWN BUT RECOMMENDED FOR EASE OF REMOVABILITY FOR SERVICE SLEEVE DRAIN LINE WALL BRACKET UNIT FIGURE 10 STANDARD REAR DRAIN FIGURE 9 OPTIONAL SIDE DRAIN SIDE VIEW INSTALLATION Q TEC UNIT ...

Страница 14: ...Manual 2100 522B Page 14 of 38 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A ...

Страница 15: ...4 PLASTIC PIPE NIPPLE HORIZONTAL TO FLOOR TIGHTEN THREADS SO TEE IS THREADS APPLY TEFLON TAPE TO REAR DRAIN CONNECTION IN Q Tec PRODUCT 1 2 SLIP X 1 2 SLIP X 3 4 NPT TEE SUPPLIED WITH DRAIN BOX KIT PLUG INSTALLED IN SIDE Q Tec DRAIN MIS 2470 FIGURE 12B IMPORTANT ...

Страница 16: ...Manual 2100 522B Page 16 of 38 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used ...

Страница 17: ...DRAIN PAN MOVE HOSE FROM ATTACHMENT IN LOWER DRAIN PAN AND SLIDE ONTO DRAIN BOX BARB FITTING SECURING WITH SUPPLIED CLAMP IF OUTDOOR PAN IS BYPASSED WILL REDUCE RISK OF ALGAE GROWTH IN THE OUTDOOR PAN BUT AT A SLIGHT COOLING PERFORMANCE REDUCTION OF 2 3 FIGURE 12D ...

Страница 18: ...lle FIGURE 13A UNIT MOUNTING BOTTOM TRIM PIECE BOTTOM TRIM EXTENSION MOUNTING BRACKET SIDE TRIM 2 PCS SIDE TRIM 2 PCS CABINET SIDE PANEL ENLARGED VIEW OF MOUNTING BRACKET SHOWING SLEEVE TO CABINET ATTACHMENT MOUNTING BRACKET 8 SCREW PROVIDED LIGHT COLOR WALL SLEEVE 10 HEX HEAD SCREW PROVIDED FIGURE 13B UNIT MOUNTING ...

Страница 19: ...heck both sides of the unit as it is being rolled to keep it centered in the sleeve Also check the alignment to the mounting brackets This unit must be level from side to side If adjustments are necessary shim up under the rollers with sheets of steel or any substance that is not affected by moisture 5 Make sure the gasket on the rear of the unit is touching the sleeve across the top and down both...

Страница 20: ...ith copper wire Each unit and or wiring diagram will be marked Use Copper Conductors Only These instructions MUST BE adhered to Refer to the National Electrical Code NEC for complete current carrying capacity data on the various insulation grades of wiring material All wiring must conform to NEC and all local codes The electrical data lists fuse and wire sizes 75 C copper for all models including ...

Страница 21: ... and the C terminal is grounded G terminal or pin 6 of P2 is the fan input If the climate control option is abandoned and connections are made directly to P2 pin 6 of P2 must be energized for proper operation Y1 terminal or pin 7 of P2 is the compressor input W1 terminal or pin 8 of P2 is the fist stage heat R terminal or pin 10 of P2 is 24 VAC hot C terminal or pin 11 of P2 is 24 VAC grounded L t...

Страница 22: ...n o N e l b a m m a r g o r P l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 8 5 0 3 0 4 8 1 5 1 1 D 0 2 2 5 H T t a e H e g a t s 2 l o o C e g a t s 2 e l b a m m a r g o r P n o N c i n o r t c e l E l a n o i t n e v n o C r o P H r e v o e g n a h c l a u n a M r o o t u A 6 5 0 3 0 4 8 8 0 0 1 A 2 3 2 7 C r o f D C L h t i w r o s n e S e d i x o i D n o b r a C ...

Страница 23: ...rized ventilation options are installed 1 Y2 W1 R C W2 Y1 E 1 2 G Y2 A Y1 W2 C R W1 E 1 G Y2 Y W2 C R W 2 3 4 5 6 7 8 9 11 12 10 F Rc G 2 3 BROWN PURPLE RED WHITE BLUE YELLOW TERMINAL BLOCK 8403 060 1 8403 058 BLACK WHITE BROWN WHITE MIS 2693 ON 15KW MODELS REMOVE JUMPER FOR 2 STAGE ELECTRIC HEAT OPERATION FACTORY INSTALLED JUMPER TH5220D1151 PLUG 2 LOW VOLTAGE FIELD WIRED ORANGE 2 X THERMOSTAT OP...

Страница 24: ...tion X or A the CS2000A or other field provided means to control ventilation must be used if any of the motorized ventilation options are installed W1 E 3 Purple L Orange Red White Blue 9 G 6 5 Black White 10 11 8 4102 069 4 R Y1 Plug 2 C W2 1 Yellow 2 12 Brown 7 Y2 Brown White 8403 060 A THERMOSTAT OPTION Pink ...

Страница 25: ...8 FIGURE 19 UNIT MOUNTED THERMOSTAT WIRING DIAGRAM D THERMOSTAT OPTION W1 E 8403 060 D THERMOSTAT OPTION Y2 12 Plug 2 Brown G Purple Orange C Blue 9 10 6 5 Black White A 3 11 8 4102 070 4 R Y1 7 Red White W2 1 Yellow 2 Brown White ...

Страница 26: ...log Part 8201 062 W1 E Y2 Orange Red White Red Black Blue 9 10 6 Part 8403 060 5 Black White G 3 11 8 4102 071 R Y1 Plug 2 C W2 1 Yellow 12 Purple Brown 7 A Out Part 8403 056 Controller Brown White 2 4 Black White Red White Orange Green Brown Yellow Red White Black White CO2 Controller Temp and Humidity Relay Orange Brown White ...

Страница 27: ...tiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system may be used after leaks have occurred and then top off the charge by utilizing the pressure charts on the inner control panel cover as a guideline REMEMBER When adding R 410A refrigerant it must come out of...

Страница 28: ...revent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y signal is present at the phase monitor and phases are correct the green LED will light and the compressor contactor is allowed to energize If phases are reversed the red fault LED will be lit and compressor operation is inhibited If a fault condition occurs reverse two of the supply lea...

Страница 29: ... lockout Regardless the state of the low pressure switch the contactor will reenergize after the delay on make time delay has expired If the low pressure switch remains open or opens again for longer than 120 seconds the unit will go into manual lockout condition and the alarm relay circuit will energize Recycling the wall thermostat resets the manual lockout Alarm Relay Output Alarm terminal is o...

Страница 30: ...he mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator can be serviced from the outside by using a vacuum cleaner The outdoor grille must be removed Use the vacuum to remove dirt and debris from the surface of the mist eliminator If additional cleaning is requi...

Страница 31: ... the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed The mist eliminator can be seen through the opening in the back of the unit The mist eliminator must be raised up and the bottom can be pulled toward the front of the unit and removed Q TEC ENERGY RECOVERY VENTILATOR Option Before starting make sure that the power has been turned o...

Страница 32: ...Manual 2100 522B Page 32 of 38 FIGURE 21 FRESH AIR DAMPER REMOVAL MOUNTING SCREW ...

Страница 33: ...Manual 2100 522B Page 33 of 38 FIGURE 22 QERV REMOVAL MOUNTING SCREWS FRONT FILL LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS ...

Страница 34: ...0 ppm See Figure 23 PRESSURE SERVICE PORTS High and low pressure service ports are installed on all units so that the system operating pressures can be observed Pressure curves can be found later in the manual covering all models on both cooling and heating cycles It is imperative to match the correct pressure curve to the unit by model number Upper and lower service doors must be attached to obta...

Страница 35: ... it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Check filter Use low pressure drop filter Check correct duct restrictions Symptom Cause Procedure Noisy blower or cabinet Check for loose blower housing panels etc High static creating high blower speed C...

Страница 36: ...n Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted into the socket in the control Carefully insert the plug and press it into the socket until it latches A SLIGHT CLICK WILL BE HEARD WHEN PROPERLY INSERTED Finish installing the replacement control pe...

Страница 37: ...rigerant listed on the serial plate AHRI capacity and efficiency ratings were determined by testing with this refrigerant charge quantity The following pressure tables show nominal pressures for the units Since many installation specific situations can affect the pressure readings this information should only be used by certified technicians as a guide for evaluating proper system performance They...

Страница 38: ... 1 4 5 4 6 3 1 1 8 4 7 3 1 8 0 5 9 3 1 4 3 5 0 4 1 1 6 5 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 0 2 1 6 5 3 6 2 1 3 8 3 2 3 1 1 1 4 7 3 1 9 3 4 1 4 1 0 4 4 5 4 1 3 9 4 7 4 1 1 2 5 9 4 1 8 4 5 0 5 1 5 7 5 B D 5 8 B W 2 7 e d i S w o L e d i S h g i H 4 2 1 8 6 3 0 3 1 6 9 3 7 3 1 5 2 4 2 4 1 4 5 4 6 4 1 2 8 4 0 5 1 0 1 5 2 5 1 9 3 5 4 5 1 7 6 5 5 5 1 5 9 5 1 A 2 4 Q B D 5 7 B W 2 6 e d i S w...

Отзывы: