background image

Manual 2100-738A
Page 

24 of 71

10

6

5

4

3

2

1

1
2
3

4

5

6

7

8

9

11
12

Red/Yellow

PLUG #2

PLUG #1

Red/White

Red

Red

Black/White

Black

Black

Blue

Pink

Purple

Purple/White

Yellow

Yellow

W1/E

L

G

D/YO

Part #8403-060

CO2-OUT

5

C

24VAC

Y2

Controller

A

1

W2

2

Y1

3

R

4

O/B

Part #8403-067

6

Temp. and Humidity

CO2 Controller

TEMP-OUT

Orange

Orange

Orange

Yellow

Green

Green

Brown

Brown/White

4115-101 E

FIGURE 16 

Factory-Mounted Thermostat and CO

2

 Vent Control Wiring Diagram

“H” Thermostat Option

Содержание Q-TEC Series

Страница 1: ...Literature Assembly 911 0825 Contains the following 2100 034 F User s Guide 2100 479 Leak Test Evacuation Charging 2100 383 C QWV Installation Instructions 2100 738 A QW S3 Installation Instructions...

Страница 2: ...eries Air Conditioners PH Series Air Source Heat Pumps QA Series Air Conditioners QH Series Air Source Heat Pumps QW Series Water Source Heat Pumps WA WL Series Air Conditioners WH SH Series Air Sourc...

Страница 3: ...s Page 4 5 Heat Pump Air to Air Page 5 6 Heat Pump Water to Air Page 6 Ventilation Page 7 Dehumidification Circuits Page 7 Automatic Control Systems Thermostats Page 7 Humidistats Humidity Controllers...

Страница 4: ...pending upon application and use of the equipment and it is critical to monitor filter condition and establish an acceptable maintenance schedule Failure to do so will increase operating and repair co...

Страница 5: ...ctually entering into the equipment enclosure which should only be done by qualified service technicians See section on Air to Air Heat Pumps for additional information concerning blockage due to heav...

Страница 6: ...e equipped with some amount of electric heat to supplement the heating capacity of the compressor system on an as needed basis This operation is entirely automatic and is controlled by the indoor ther...

Страница 7: ...ats and cools using a compressor for both modes of operation The primary difference is that the system uses water or antifreeze protected water solution instead of an air cooled outdoor heat transfer...

Страница 8: ...ntenance requirements you should be aware of as the user AUTOMATIC CONTROL SYSTEMS THERMOSTATS There are many types of thermostats available to properly control your system and these can vary in featu...

Страница 9: ...ace and that all supply registers and return air grilles are not blocked 5 Make sure that the outdoor coil is not blocked with any foreign matter or otherwise restricted with any growth or other items...

Страница 10: ...lengthy period it is best to adjust the thermostat to a reasonable higher or lower depending upon the season setting rather than turning it completely off Upon return the inside conditions will not be...

Страница 11: ...1 of 11 Manual No 2100 479 Supersedes NEW File Volume I Tab 1 Date 03 08 07 SERVICING PROCEDURE R 410A LEAK TEST EVACUATION CHARGING Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving a...

Страница 12: ...tioning Heat Pump Cooling 9 Low Suction Low Head Pressure 9 High Suction Low Head Pressure 9 Low Suction High Head Pressure 9 High Suction High Head Pressure 9 Heat Pump Heating 9 Low Suction Low Head...

Страница 13: ...tion of the system The valving on the manifold is so arranged that when the valves are closed front seated the center port on the manifold is closed to the gauges and gauge ports With the valves in th...

Страница 14: ...Relieve all pressure from the system down to 0 psig 5 Change the dryer When leaks if any have been repaired system is ready to be evacuated and charged Relieve all pressure from the system down to 0 p...

Страница 15: ...serial plate for the full operating charge PRELIMINARY CHARGING STEPS If the system has been open to the atmosphere the dryer should be replaced and then evacuated Then proceed as follows 1 Attach a d...

Страница 16: ...Manual 2100 479 Page 6 of 11 FIGURE 1 TYPICAL AIR CONDITIONING SYSTEM COOLING CYCLE MIS 369...

Страница 17: ...Manual 2100 479 Page 7 of 11 FIGURE 2 TYPICAL HEAT PUMP SYSTEM COOLING CYCLE MIS 368...

Страница 18: ...ed refrigerant flow it may be necessary to place refrigerant drum in a pan of warm water not greater than 130 F Remember to either consider the total weight of the pan of water or remove the drum for...

Страница 19: ...ing device etc 6 Low charge 7 Low ambient entering air temperature Low entering water temperature to water coil HIGH SUCTION LOW HEAD PRESSURE 1 Defective or broken valves 2 IPRV valve open 3 Defectiv...

Страница 20: ...r o s s e r p m o c m e t s y s e b u t p a c e r u t a r e p m e t e c a p S h g i h o o t Power Failure Blown Fuses or Tripped Circuit Breakers Faulty Wiring Loose Terminals Low Voltage Single 1PH...

Страница 21: ...l n o p u d l i u b e c I l i o c D O f o g n i d o o l f t n a r e g i r f e r d i u q i L r o s s e r p m o c o t k c a b D I n o t a e h y r a i l i x u A f f o r e w o l b s t s o c g n i t a r e...

Страница 22: ......

Страница 23: ...9 MIS 1608 INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual 2100 383C Supersedes 2100 383B Date 10 8 15 QW SERIES WALL SLEEVE Models QWVS42 QWVS42 19...

Страница 24: ...nstallation Wood Framed Walls 4 Installation Masonry Construction Walls 6 Installation Through Window Opening 9 Figures Figure 1 Wood Framed Installation 4 Figure 2 Application of Sealant to Flanges 5...

Страница 25: ...ng Systems QW Installation Instruction Manual Bard 2100 381 For more information contact these publishers ACCA Air Conditioning Contractors of America 1712 New Hampshire Avenue NW Washington DC 20009...

Страница 26: ...ral recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdiction should be consulted before the installation is made INSTALLATION WOOD FRAMED WALL...

Страница 27: ...Manual 2100 383C Page 5 of 9 FIGURE 2 Application of Sealant to Flanges SEAL ALL 4 FLANGES MIS 1609 A SEAL ALL NOTCHES IN ALL 4 CORNERS 17 23 32...

Страница 28: ...e 4 There are two brackets supplied with the sleeve for attachment to the unit Position these brackets to FIGURE 3 Masonry Construction Installation 33 000 29 750 35 250 MIS 1612 NOTE OPENING DIMENSIO...

Страница 29: ...e wall All four mounting flanges must be fastened with two fasteners each to the outside wall The gaps between the side top and bottom flanges must be sealed to the wall On the inside of the building...

Страница 30: ...SHOWN WITHOUT OUTSIDE GRILLE SPACER FOR GRILLE CLEARANCE SPACER TO MAINTAIN THE 32 750 RELATIONSHIP BETWEEN WALL SLEEVE AND UNIT OPENING THIS DIMENSION MUST REMAIN CONSTANT WHEN FABRICATING UNIT AND...

Страница 31: ...into the opening from the outside of the building The bottom of the sleeve must be level from side to side and the sleeve must be square in the opening A slope is built into the bottom of the sleeve...

Страница 32: ......

Страница 33: ...NS Bard Manufacturing Company Inc Bryan Ohio 43506 www bardhvac com Manual No 2100 738A Supersedes 2100 738 Date 1 29 20 QW SERIES GEOTHERMAL R 410A STAGED CAPACITY PACKAGED HEAT PUMP Models QW2S3DA Q...

Страница 34: ...orts 32 Piping Access to Unit 32 System Start Up 32 Sequence of Operation Cooling 37 Heating 37 Geothermal Logic Control 37 Modulating Water Line Control 38 iSeries Smart Actuator 39 Dehumidification...

Страница 35: ...uator Temperature Adjustment 40 Figure 31 Cooling Mode and Dehumidification Mode Circuit Diagrams 41 Figure 32 Water Temperature and Pressure Test Procedure 52 Figure 33 Piping Diagram 54 Figure 34 Cl...

Страница 36: ...or Ground Source IGSHPA Heat Pump Systems Soil and Rock Classification for the Design IGSHPA of Ground Coupled Heat Pump Systems Ground Source Installation Standards IGSHPA Closed Loop Geothermal Syst...

Страница 37: ...uble O ring fittings back corners of unit 5 Single Grundfos UPS26 99 FC pump isolation valves both ends piped with copper to double O ring fittings back corners of unit VOLTS PHASE A 230 208 60 1 B 23...

Страница 38: ...x2 ENERGY RECOVERY VENTILATOR ERV Voltage 230 208 60 1 230 208 60 1 ERV Full Load Amps 2 2 2 2 SHIPPING WEIGHT LBS 475 lb 475 lb Specifications 4 and 5 Ton MODELS QW4S3 A QW4S3 B QW4S3 C QW5S3 A QW5S3...

Страница 39: ...es Model RATED VOLTS Hz PHASE NO FIELD POWER CIRCUITS MINIMUM CIRCUIT AMPACITY MAXIMUM EXTERNAL FUSE OR CIRCUIT BREAKER FIELD POWER WIRE SIZE GROUND WIRE SIZE QW2S3DA0Z QW2S3DB0Z QW2S3DC0Z 230 208 60...

Страница 40: ...ATION DORFC PUMP ACCESS FOR FLUID CONNECTION FOR FROM BACK OF UNIT OPTIONAL HIGH VOLTAGE ELECTRICAL ENTRANCE FLUID CONNECTION FACTORY CONNECTED CONDENSATE DRAIN CONNECTION 3 4 PVC MALE ADAPTER 4 625 6...

Страница 41: ...not be slid through the door then the unit will have to be put on a cart and tipped down to roll through the door It is recommended that an appliance cart be used with a strap to hold the unit on the...

Страница 42: ...d or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local codes in any way Authorities having jurisdict...

Страница 43: ...TARY OR TOGGLE DISCONNECT ELECTRICAL ACCESS BLOW PLENUM BOX TOP SIDE AND LOCKING COVER LOW VOLTAGE OPTIONAL FREE ELECTRICAL ENTRANCE TOP REAR SIDE VENTILATION PERMANENT HIGH VOLTAGE QW2S QW3S 42 000 Q...

Страница 44: ...N MINIMUM A INSTALLATION HEIGHT 9 FT MINIMUM REQUIRED UNIT HEIGHT 7 FT 6 IN 10 INSTALLATION HEIGHT 8 FT 9 IN MINIMUM REQUIRED MINIMUM 12 IN TO DUCT BOTTOM 2 IN MINIMUM FROM DUCT FLANGE FLOOR MIS 2741...

Страница 45: ...above the unit to the ceiling This extends 20 above the unit for a total height above the floor of 10 7 8 The unit is equipped with a variable speed indoor blower motor which increases in speed with a...

Страница 46: ...e wall If the drain is to be routed through an unconditioned space it must be protected from freezing The drain line must be able to be removed from the unit if it is necessary to remove the unit from...

Страница 47: ...that the mist eliminator be inspected annually and serviced as required The mist eliminator can be inspected from the outside of the building by looking through the outdoor grille The mist eliminator...

Страница 48: ...there is a power connector for the lower blower assembly To Figure 9 Removal of the Q TEC Energy Recovery Ventilator FRONT FILL MOUNTING SCREWS LOWER BLOWER ASSEMBLY POWER CONNECTOR POWER CONNECTORS...

Страница 49: ...connections are to be within the confines of this bracket See Figure 1 on page 8 for cabinet openings and location of fluid coil connection points 2 Position the unit in front of the wall mounting br...

Страница 50: ...of 71 FIGURE 11 Unit Mounting without Ventilation Wall Sleeve BRACKET WALL MOUNTING BASE TRIM SIDE TRIM CUT TO LENGTH 41 ADJUSTABLE SIDE TRIM EXTENSION KIT ORDERED SEPARATELY SIDE TRIM EXTENSION MIS 2...

Страница 51: ...Manual 2100 738A Page 19 of 71 FIGURE 12 Component Location WIRE ENTRANCE SIDE FIELD TERMINAL BLOCK REMOTE THERMOSTAT INDOOR DUAL BLOWERS CONTROL BOX CIRCUIT BREAKER PANEL MIS 2745...

Страница 52: ...ment leaves the factory wired on 240V tap For 208V operation reconnect from 240V to 208V tap The acceptable operating voltage range for the 240 and 208V taps are as noted in Table 2 The standard Clima...

Страница 53: ...or ventilation during occupied programming conditions and feeds through Pin 5 of Plug P2 The W2 terminal is the auxiliary heat signal and feeds through Pin 9 of Plug P2 The W1 E terminal is the emerge...

Страница 54: ...Temp and Humidity Part 8403 060 C 4115 102 E A W2 Y1 R Y2 Temp and Humidity Controller D YO Orange Orange Yellow Green Brown Brown White Red White PLUG 2 PLUG 1 Red Red Yellow Black White 1 Terminal...

Страница 55: ...ermostat Wiring Diagram D Thermostat Option PLUG 2 Purple White D YO Pink Black White Red White Brown Blue Yellow Orange Brown White Purple Red Yellow Temp and Humidity Controller Part 8403 060 L W1 E...

Страница 56: ...Pink Purple Purple White Yellow Yellow W1 E L G D YO Part 8403 060 CO2 OUT 5 C 24VAC Y2 Controller A 1 W2 2 Y1 3 R 4 O B Part 8403 067 6 Temp and Humidity CO2 Controller TEMP OUT Orange Orange Orange...

Страница 57: ...d Yellow Red White PLUG 2 Black Black White 2 1 2 Black FOR DEHUMIDIFICATION MODELS EQUIPPED WITH FACTORY HOT GAS REHEAT CONNECT SIGNAL FOR HUMIDISTAT TO PURPLE WHITE WIRE FOR ENERGY RECOVERY VENTILAT...

Страница 58: ...ink Purple White Purple OR CS9BE THO Black White COMPLETESTAT TEMPERATURE HUMIDITY AND OCCUPANCY CONTROLLER BARD PART CS9B THO 4115 108 Orange Yellow Brown Brown White Red White Red White 7 Red White...

Страница 59: ...urple White Purple OR CS9BE THOC Black White COMPLETESTAT TEMPERATURE HUMIDITY OCCUPENCY AND CO2 CONTROLLER BARD PART CS9B THOC 4115 109 Orange Yellow Brown Brown White Red White Red White Red White R...

Страница 60: ...over the valve s locking posts see Figure 21 Once the actuator is flush with valve body turn actuator clockwise and lock into position 4 To ensure the actuator will function correctly at start up ther...

Страница 61: ...w to help accommodate room comfort during dehumidification High Pressure Switch This unit is equipped with a high pressure switch that will stop the compressor in the event of abnormal high pressure o...

Страница 62: ...th three phase scroll compressors are equipped with a three phase line monitor to prevent compressor damage due to phase reversal The phase monitor in this unit is equipped with two LEDs If the Y sign...

Страница 63: ...gh Altitude Installations CAL Used for Field Calibration 1 Damper should be fully closed at 700 ppm if not Potentiometer R7 can be adjusted clockwise CW to close it If it is fully closed at 700 ppm or...

Страница 64: ...to and from the coaxial water coil is intended to enter exit the unit through the rectangular hole See Figures 1 page 8 8A page 14 24 and 25 page 34 The connections on the water coil are a double O r...

Страница 65: ...HIPPED WITH UNIT CEILING SIDE TRIM PIECES SHIPPED WITH UNIT IF THE WALL THICKNESS IS LESS THAN 14 BUT GREATER THAN 8 A SIDE TRIM EXTENSION KIT QSTX42 IS REQUIRED REFER FLUID ACCESS FROM SLEEVE TOP OF...

Страница 66: ...without Ventilation Wall Sleeve 23 1 2 8 1 2 66 1 2 4 LEFT BRACKET REMOVED FOR FLOOR FLUID ACCESS FROM FLOOR FLUID ACCESS FROM TOP CLARITY WALL BRACKET OPENING IN REAR OF UNIT 3 x 8 BACK OF UNIT MIS...

Страница 67: ...1 291 59 304 67 317 75 330 82 343 90 356 98 369 106 382 115 394 125 405 134 417 143 429 153 441 162 453 172 465 Model Return Air Temperature Pressure PART LOAD COOLING Fluid Temperature Entering Water...

Страница 68: ...QW5S QPBX48 10 V Platinum Vinyl QPBX48 10 4 Gray Paint QPBX48 10 X Beige Paint Use with QPB48 or QPBS48 adjusts to ceilings up to 10 5 Cabinet Extensions for Ducted Applications Unit Compatibility QC...

Страница 69: ...or factory run in processes SEQUENCE OF OPERATION Alarm Output The L terminal has 24 volts applied when a hard lockout occurs This can be used to drive a fault light or low voltage relay NOTE Both hig...

Страница 70: ...that all faults have been cleared If faults have been cleared the controller restarts the unit If a second fault occurs the controller will lockout the unit until the control is reset by breaking Y s...

Страница 71: ...usly mentioned the iSeries Smart Actuator operates the valve to maintain a fixed setpoint The setpoint temperature is set using the setpoint dial located on top of the actuator The setpoint range avai...

Страница 72: ...dehumidification mode can be achieved using waste heat from the refrigeration cycle to achieve the reheat process while at the same time large amounts of moisture can be extracted from the passing air...

Страница 73: ...DIAGRAM WATER 4 WAY WATER EXPANSION VALVE WATER HEAT PUMP DEHUMIDIFICATION VALVE HEAT PUMP COOLING MODE CIRCUIT DIAGRAM CHECK EXPANSION VALVE FILTER VALVE 4 WAY DRIER 4 WAY WATER EXPANSION VALVE BULB...

Страница 74: ...8 5 64 00 59 9 57 2 70 25 0 16 2 8 8 8 3 64 80 59 7 57 1 75 24 8 16 3 8 5 8 0 65 73 59 4 57 0 80 24 7 16 4 8 3 7 8 66 40 59 4 57 1 85 24 5 16 5 8 0 7 5 67 35 59 5 57 3 90 24 3 16 6 7 7 7 3 68 31 59 6...

Страница 75: ...3 3 100 0 9 2 3 3 2 3 0 77 8 63 8 65 75 DB 65 5 WB 11 2 4 3 6 9 6 5 69 7 60 8 70 9 6 3 2 6 4 6 0 71 1 61 5 75 8 1 2 1 6 0 5 7 72 4 61 9 80 6 7 1 0 5 7 5 4 73 8 62 8 85 5 3 0 0 5 3 5 0 75 0 63 4 90 4 0...

Страница 76: ...7 54 9 70 37 3 23 4 13 9 13 1 62 73 56 9 55 1 75 35 9 22 8 13 1 12 4 63 51 57 1 55 2 80 35 3 22 5 12 8 12 1 63 74 57 5 55 7 85 34 1 22 0 12 1 11 4 64 52 58 0 56 1 90 32 8 21 4 11 4 10 8 65 24 58 6 56...

Страница 77: ...65 75 DB 65 5 WB 16 0 3 1 12 9 12 2 71 6 59 5 70 16 3 3 6 12 7 12 0 71 1 59 4 75 15 7 3 4 12 3 11 6 71 2 59 4 80 14 7 2 6 12 1 11 4 72 2 60 0 85 12 8 1 1 11 7 11 0 73 8 60 8 90 10 3 1 0 11 3 10 7 76...

Страница 78: ...1 58 88 54 6 53 0 70 50 8 30 1 20 7 19 5 59 25 55 3 53 5 75 49 4 29 7 19 7 18 6 60 12 55 2 53 3 80 49 1 29 4 19 7 18 6 59 88 55 9 54 1 85 48 3 29 1 19 2 18 1 60 25 55 9 54 1 90 47 6 29 0 18 6 17 5 60...

Страница 79: ...64 2 65 75 DB 65 5 WB 27 1 7 3 19 8 18 7 68 4 56 9 70 24 8 5 4 19 4 18 3 70 1 57 8 75 21 7 3 3 18 4 17 4 71 9 58 7 80 18 9 1 0 17 9 16 9 74 1 59 8 85 15 3 1 5 16 8 15 8 76 4 61 0 90 11 1 4 2 15 3 14 4...

Страница 80: ...3 59 38 55 1 53 3 70 59 2 34 9 24 3 22 9 58 95 55 7 53 7 75 57 3 34 1 23 2 21 9 59 51 56 0 53 9 80 56 6 33 8 22 8 21 5 59 72 56 4 54 3 85 55 7 33 9 21 8 20 6 60 86 56 5 54 5 90 55 0 34 6 20 4 19 2 62...

Страница 81: ...1 83 5 64 2 65 75 DB 65 5 WB 28 3 6 6 21 7 20 5 70 2 58 4 70 25 7 4 6 21 1 19 9 71 6 59 0 75 22 6 2 4 20 2 19 1 73 1 59 6 80 19 6 0 0 19 6 18 5 75 0 60 6 85 16 2 2 7 18 9 17 8 77 1 61 6 90 12 5 5 7 18...

Страница 82: ...d X X X X X Y1 Y2 G A Full Load Heat Pump Occupied X X X X X X X Y1 Y2 G D Full Load Heat Pump Dehum Unoccupied X X X X X Y1 Y2 G D A Full Load Heat Pump Dehum Occupied X X X X X X X Y1 Y2 G W2 Part L...

Страница 83: ...tor keeps the operating costs of the system to a minimum However the performance of the circulator must be closely matched with the pressure of head loss of the entire system in order to provide the r...

Страница 84: ...trapped air or a restriction in the piping circuit 8 Start the unit in cooling mode by moving the thermostat switch to cool Fan should be set for AUTO 9 Check the system refrigerant pressures against...

Страница 85: ...n button located on the top of the iSeries Smart Actuator several times to make sure the water valve is loose and not seized before operation This simple step will provide assurance the 3 way water va...

Страница 86: ...tant Flow Valve 7 provides correct flow of water to the unit regardless of variations in water pressure Observe the water flow direction indicated by the arrow on the side of the valve body Table 7 sh...

Страница 87: ...top 5 Fully open the manual inlet and outlet valves 6 Check water flow A Connect a water flow meter to the drain cock between the constant flow valve and the solenoid valve Run a hose from the flow me...

Страница 88: ...acid water generally not the case with ground water of galvanic reaction between dissimilar metals in the presence of water By using plastic plumbing or dielectric unions galvanic reaction is elimina...

Страница 89: ...pump suspended in the dry well casing Jet pumps and other types of suction pumps normally consume more electrical energy than similarly sized submersible pumps Pipe the unit the same as a water well s...

Страница 90: ...of 71 FIGURE 35 Water Well System 12 to 15 LAKE or POND WATER LEVEL GRAVEL FILL WELL CAP ELECTRICAL LINE PITLESS ADAPTER TO PRESSURE TANK SUBMERSIBLE PUMP PERFORATED PLASTIC CASING DROP PIPE WATER SU...

Страница 91: ...ture In milder climates a flooded tower concept is often used This concept involves adding makeup water to the cooling tower sump to maintain the desired loop temperature Units are equipped with doubl...

Страница 92: ...Manual 2100 738A Page 60 of 71 FIGURE 36 Water Source Heat Pump Cooling Cycle...

Страница 93: ...Manual 2100 738A Page 61 of 71 FIGURE 37 Water Source Heat Pump Heating Cycle...

Страница 94: ...through a 5 minute delay on break plus random start sequence If no fault is found on next run cycle compressor will continue operation If fault reoccurs hard lockout will be initiated and the fault si...

Страница 95: ...fault by observing the LED status light code and follow standard testing procedures to confirm the problem The LED status code and error can be diagnosed by following the light sequences in the multi...

Страница 96: ...46 10 0 118108 28 0 36583 66 0 13137 104 0 5326 9 0 114272 29 0 35548 67 0 12810 105 0 5208 8 0 110575 30 0 34545 68 0 12492 106 0 5094 7 0 107010 31 0 33574 69 0 12183 107 0 4982 6 0 103574 32 0 3263...

Страница 97: ...g a truth table is suppled below see Table 16 See page 38 for the modulating water line control sequence of operation FIGURE 40 Modulating Water Line Control Board MIS 4140 C R CONTROL BOARD Y Y0 SU S...

Страница 98: ...nd listen for another click as the solenoid returns to its original position 3 If clicks can t be heard shut off power remove the control circuit molded plug from the compressor and measure the soleno...

Страница 99: ...it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down Chec...

Страница 100: ...rol module is now completely detached from the motor Verify with a standard ohmmeter that the resistance from each motor lead in the motor plug just removed to the motor shell is 100K ohms Refer to Fi...

Страница 101: ...Motor Winding Defective Air Volume Low Air Filters Dirty Undersized or Restricted Ductwork Auxillary Heat Upstream of Coil Compressor Will Not Run No Power at Contactor Compressor Will Not Run Power...

Страница 102: ...Describe ________________________________________________________________ Type of Antifreeze________________ of Antifreeze __________ Freezepoint F _________ Piping Material ____________ Diameter of...

Страница 103: ..._______ __________ __________ 14 Wet Bulb Supply Air Temp F __________ __________ __________ __________ 15 Return Static Pressure WC __________ __________ __________ __________ 16 Supply Static Pressu...

Страница 104: ...ure Assembly 911 0825 Contains the following 7960 356 D Installation Instruction 7960 359 H Installation Instructions 7960 438 B Installation Instructions 2110 1558 Replacement Parts Manual 7960 420 W...

Страница 105: ......

Страница 106: ...sleeve flanges on the outside wall 5 Locate the four mounting holes in the Outdoor Louver Grille They can be seen by looking under the louvers 6 The Outdoor Louver Grille fastens through the same hol...

Страница 107: ......

Страница 108: ...nge as shown in Figure 1 The outside of the plenum box should be flush with the outside of the unit 4 Re install the center screw in each top side of the Q TECTM unit These screws will go through the...

Страница 109: ...art Number QPBS42 V 7051 035 7051 046 QPBS42 X 7051 035 7051 046 QPBS42 X 8 7051 073 7051 046 QPBS42 1 7051 035 7051 046 QPBS42 4 7051 035 7051 046 QPBS42 4 8 7051 073 7051 046 QPBS48 V 7051 045 7051...

Страница 110: ...for a maximum trim height of 112 inches 9 Hold the side angles against the side of the cabinet extension and slide up to the ceiling Make sure the angle is centered on the side Mark the holes on the...

Страница 111: ......

Страница 112: ...xploded View 8 Usage List 9 Description Page Blower Assembly Components Exploded View 10 Usage List 11 Pump Module Components Exploded View 12 Usage List 13 Optional Climate Control Components Explode...

Страница 113: ...Manual 2110 1558 Page 2 of 23 CABINET COMPONENTS 32 17 1 2 3 4 5 6 8 9 10 11 12 13 14 16 7 18 19 20 21 22 23 24 30 31 33 34 35 38 36 37 39 40 41 42 SEXP 652 15 29 28 43 25 26...

Страница 114: ...dels Water Coil Hold Down 460V Models X X X X 21 140 276 Lower Roller Support 2 2 22 140 280 Upper Roller Support 2 2 23 23 S127 384 X S127 379 X Lower Base Assembly Lower Base Assembly X X 24 141 368...

Страница 115: ...Manual 2110 1558 Page 4 of 23 FUNCTIONAL COMPONENTS 29 30 6 10 2 26 3 4 7 5 9 12 14 31 8 18 28 20 19 27 1 21 22 23 17 32 24 11 13 25 15 30 16 33 34 SEXP 1018 35 36...

Страница 116: ...Grille for Beige Buckeye Gray Units Return Air Grille for Vinyl Units X X X X X X X X X X X X X X X X X X X X X X X X 15 15 7004 035 7004 025 Air Filter 2 Pleated 16 x 20 x 2 Air Filter 2 Pleated 16...

Страница 117: ...Manual 2110 1558 Page 6 of 23 CONTROL PANEL COMPONENTS SEXP 1015 10 5 6 9 20 16 14 17 18 2 1 12 11 13 4 8 7 15...

Страница 118: ...it Breaker Box Partition X X X X 8 117 421 Control Panel X X X X 9 8201 140 Compressor Control Module X X X X 10 3000 1349 Wire Assembly Vent Control X X X X 11 11 11 11 8552 086 8552 035 8552 095 855...

Страница 119: ...Manual 2110 1558 Page 8 of 23 CONTROL PANEL COMPONENTS 21 19 20 5 6 14 15 3 7 12 16 13 9 4 2 11 1 10 17 18 8 SEXP 1016...

Страница 120: ...X X 8 117 421 Control Panel X X X X X X X X 9 8201 140 Compressor Control Module X X X X X X X X 10 3000 1349 Wire Assembly Vent Control X X X X X X X X 11 8201 126 3 Phase Line Monitor X X X X X X X...

Страница 121: ...Manual 2110 1558 Page 10 of 23 BLOWER ASSEMBLY COMPONENTS SEXP 1017 5 7 2 9 11 9 8 3 6 4 9 11 9 14 12 13 1 10 10 8...

Страница 122: ...60 0198 C8106 052 0199 C8107 017 0200 C8107 017 0201 Programmed Motor Control Only Programmed Motor Control Only Programmed Motor Control Only Programmed Motor Control Only X X X X 5 113 380 Blower Mo...

Страница 123: ...Manual 2110 1558 Page 12 of 23 PUMP MODULE COMPONENTS RELAY ASSEMBLY SEXP 574 5 1 PUMP ASSEMBLY 3 2 4...

Страница 124: ...C 1 1 1 8300 008 8300 007 8300 009 Circulating Pump UPS15 42F Circulating Pump UP26 64F Circulating Pump UPS26 99FC X X X X X X 2 141 346 Water Pump Bracket X X X X 3 113 399 Pump Relay Bracket X X X...

Страница 125: ...Manual 2110 1558 Page 14 of 23 OPTIONAL CLIMATE CONTROLS SEXP 560 3 2 1...

Страница 126: ...erial number of the unit for which parts are being ordered NS Not Shown 1 1 1 1 S127 313 S127 308 S127 372 S127 409 Thermostat Plate Thermostat Plate Thermostat Plate CO2 Plate X X X X 2 8403 060 Elec...

Страница 127: ...Manual 2110 1558 Page 16 of 23 OPTIONAL CLIMATE CONTROLS 1 3 2 4 SEXP 639 5...

Страница 128: ...n S 1 117 325 Control Panel X 2 8201 130 Relay SPDT Pilot Duty 2 3 S910 1820 Condensate Overflow Assembly X 4 8403 068 Siemens DDC Interface X 5 3000 1414 Wire Harness X NS 4115 106 Wiring Diagram X N...

Страница 129: ...Manual 2110 1558 Page 18 of 23 OPTIONAL CLIMATE CONTROLS 6 4 2 3 1 5 SEXP 646...

Страница 130: ...ption Option C 1 117 328 Control Panel X 2 117 329 Low Voltage Control Box X 3 8607 029 Low Voltage Terminal Strip X 4 910 1822 Condensate Overflow Assembly X 5 8201 130 Relay SPDT Pilot Duty 2 6 3000...

Страница 131: ...Manual 2110 1558 Page 20 of 23 OPTIONAL CLIMATE CONTROLS SEXP 645 4 3 2 5 6 1...

Страница 132: ...CS9B THO CS9B THOC CS9BE THO CS9BE THOC CompleteStat TEMP HUM OCC CompleteStat TEMP HUM OCC CO2 CompleteStat TEMP HUM OCC with BACnet CompleteStat TEMP HUM OCC CO2 with BACnet X X X X 3 3000 1416 Wir...

Страница 133: ...Manual 2110 1558 Page 22 of 23 11 8 9 12 2 5 10 4 6 7 1 3 SEXP 377 WALL SLEEVE CABINET COMPONENTS...

Страница 134: ...over X 2 121 350 X Top Partition X 3 105 1103 X Angle 2 4 110 073 X Left Side X 5 110 074 X Top X 6 7003 056 Mist Eliminator 2 7 111 076 X Air Deflector X 8 121 349 X Partition X 9 110 072 X Right Sid...

Страница 135: ......

Страница 136: ...ting environment is exposed to airborne saline particles typically 5 miles from coast line must have corrosion protection or warrenty claims will be declined on corrosion based cabinet and part failur...

Страница 137: ...rts Must be registered at www wallmountwarranty com within 90 days of installation for the 10 year parts coverage to be in effect Factory coated coils have a 5 year warranty in corrosive environments...

Отзывы: