GENERAL
This unit is equipped with a variable speed ECM motor.
The motor is designed to maintain rated airflow up to
the maximum static allowed.
It is important that the
blower motor plugs are not plugged in or unplugged
while the power is on. Failure to remove power prior
to unplugging or plugging in the motor could result in
motor failure.
CAUTION
Do not plug in or unplug blower motor connectors
while the power is on. Failure to do so may result
in motor failure.
FIGURE 16
TABLE 4
Wall Thermostats and Controls
MIS-1285
Thermostat
Predominant Features
8403-067
Carbon Dioxide Sensor with LCD for Sensor Readings
8403-060
(1120-445)
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover
CSB9E-THO
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover with Humidity Control
BacNet MS/TP or Ethernet Connection
CSB9E-THOC
3 stage Cool; 3 stage Heat
Programmable/Non-Programmable Electronic
HP or Conventional
Auto or Manual changeover with CO
2
& Humidity Control
BacNet MS/TP or Ethernet Connection
“F”
terminal of pin 5 of P2 is the
ventilation input
.
This terminal energizes any factory installed ventilation
option.
NOTE:
For total and proper control using DDC, a total
of 7 controlled outputs are required (6 if no
ventilation system is installed). For proper
system operation under Emergency Heat
conditions where the compressor needs to
be deactivated, the B-W2-E outputs need to
be energized. Removing the Y (compressor)
signal alone turns the compressor off, but does
not activate the additional circuitry embedded
in the heat pump for proper and complete
operation.
Содержание Q-TEC Q24H3DA
Страница 6: ...Manual 2100 653 Page 6 of 44 FIGURE 1 Unit Dimensions...
Страница 9: ...Manual 2100 653 Page 9 of 44 FIGURE 6 Ducted Application FIGURE 5 Installation with Duct Free Plenum...
Страница 13: ...Manual 2100 653 Page 13 of 44 MIS 2469 DRAIN BOX WALL SLEEVE OVERFLOW TUBE CAULK AROUND TUBE FIGURE 12A...
Страница 15: ...Manual 2100 653 Page 15 of 44 REMOVE KNOCK OUT FOR INDOOR DRAIN HOSE CONNECTOR MIS 2471 FIGURE 12C If Used...
Страница 31: ...Manual 2100 653 Page 31 of 44 FIGURE 22 Fresh Air Damper Removal Mounting Screw...