THERMOSTAT INDICATOR LAMPS

The red lamp marked “EM. HT.” comes on and stays on
whenever the system switch is placed in Em. Ht. position.
The green lamp marked “Check” will come on if there is
any problem that prevents the compressor from running
when it is supposed to be.

EMERGENCY HEAT POSITION

The operator of the equipment must manually place the
system switch in this position.  This is done when there is a
known problem with the outdoor section, or when the green
“Check” lamp comes on indicating a problem.

TRANSFORMER TAPS

230/208V, 1 phase and 3 phase equipment employ dual
primary voltage transformers.  All equipment leaves the
factory wired on 240V tap.  For 208V operation, reconnect
from 240V to 208V tap.  The acceptable operating voltage
range for the 240 and 208V taps are:

TAP

 RANGE

 240

253 – 216

 208

220 – 187

NOTE: The voltage should be measured at the field

power connection point in the unit and while the
unit is operating at full load (maximum
amperage operating condition).

COMPRESSOR CUTOFF THERMOSTAT
and OUTDOOR THERMOSTAT WIRING

Heat pump compressor operation at outdoor temperatures
below 0° F are neither desirable not advantageous in terms
of efficiency.  Since most equipment at time of
manufacture is not designated for any specific destination
of the country and most of the equipment is installed in
areas not approaching the lower outdoor temperature
range, the compressor cutoffs are not factory installed.

Outdoor thermostats are available to hold off various
banks of electric heat until needed as determined by
outdoor temperature.  The set point of either type of
thermostat is variable with geographic region and sizing of
the heating equipment to the structure.  Utilization of the
Heating Application Data and the heat loss calculation of
the building are useful in determining the correct set
points.  Refer to Installation Instructions of CMH-14
Outdoor Thermostat Kit for more information.

MIS-1188

FIGURE  10

UNIT 24V TERMINAL BOARD ( 5 THRU 10 KW)

Содержание PH10481

Страница 1: ...H1230 PH11361 PH1236 PH11422 PH1242 PH10481 PH11481 PH1060 INSTALLATION INSTRUCTIONS Copyright 2003 Manual 2100 354B Supersedes 2100 354A File Volume II Tab 11 Date 03 19 03 Bard Manufacturing Company...

Страница 2: ...e 4 Roof Top Application 11 Figure 5 Elevated Mounting Platforms 11 Figure 6 Prefabricated Rood Curb Specifications 12 Figure 7 Field Fabricated Curbing 13 Figure 8 Condensate Drain Trap 14 Figure 9 L...

Страница 3: ...and Summer Air Conditioning Duct Design for Residential ACCA Manual D Winter and Summer Air Conditioning and Equipment Selection FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Conditioning Co...

Страница 4: ...cularly Starting Procedure and any tags and or labels attached to the equipment While these instructions are intended as a general recommended guide they do not supersede any national and or local cod...

Страница 5: ...s s e r p m o C e p y T r o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 s p m A...

Страница 6: ...m o C e p y T r o s s e r p m o C l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 8 0 2 0 3 2 8 0 2 0 3 2 0 6 4 s p m A d a o L d e t a...

Страница 7: ...S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S l l o r c S s t l o V 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 8 0 2 0 3 2 s p m A d a o L d e t a R 5 0 1...

Страница 8: ...N A N S A N S A A A N A N 5 0 A C P 3 H E 1 8 0 2 0 4 2 A N S A N S A N A N A N S A N 0 1 A C P 3 H E 1 8 0 2 0 4 2 A N S A N A N A N A N A N A N A N 5 1 A C P 3 H E 1 8 0 2 0 4 2 A N A N A N S 2 A N...

Страница 9: ...0 5 7 5 2 1 1 5 7 3 0 5 7 5 2 1 1 0 0 8 2 1 0 0 5 0 2 0 0 0 6 2 0 0 4 8 3 0 0 8 2 1 0 0 0 6 2 0 0 4 8 3 1 8 1 8 0 2 8 8 2 3 3 3 2 6 3 6 1 4 1 4 5 5 2 6 1 8 1 8 0 2 2 6 3 6 1 4 1 4 5 5 2 6 0 6 0 3 0 6...

Страница 10: ...m o N s e h c n I g n i n e p O t c u D H e g r a h c s i D r i A n r u t e R A B C J K L M D E F G 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3 2 1 H P 6 3 1 1 H P 6 3 2 1 H P 4 1 4 2 6 1 3 8 4 8 1 8 3 8...

Страница 11: ...of twelve inch elevation is recommended while greater elevation may be required for areas of high snow accumulation Poured concrete steel framework brick cement block etc can be utilized to construct...

Страница 12: ...Manual 2100 354 Page 10 FIGURE 2 SLAB MOUNTING AT GROUND LEVEL Above 32 F Outside Temperature FIGURE 3 AIRFLOW AND SERVICE ACCESS CLEARANCES MIS 1185...

Страница 13: ...Manual 2100 354 Page 11 FIGURE 4 ROOF TOP APPLICATION May also be required for ground level installations MIS 1176 FIGURE 5 ELEVATED MOUNTING PLATFORMS MIS 1183...

Страница 14: ...e d o M s l i a t e D b r u C f o o R A B C D E F G H I J K L 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3 2 1 H P 6 3 1 1 H P 6 3 2 1 H P 6 3 E H R 3 0 0 2 4 0 9 5 7 3 0 8 5 2 0 4 5 2 7 3 5 7 3 8 3 5 7 3...

Страница 15: ...wood curbing Caulk seal all joints weatherproof TABLE 7 DIMENSION X FOR FIELD FABRICATEDCURBING l e d o M t i n U d o o H f o o R l e d o M n o i s n e m i D X 4 2 1 1 H P 4 2 2 1 H P 0 3 1 1 H P 0 3...

Страница 16: ...be piped through a condensate drain trap to a suitable drain C Always mount the unit is such a position that it may be easily reached for servicing and maintenance D Insure that the unit is clear so...

Страница 17: ...els are suitable for connection with copper wire only These instructions must be adhered to Refer to the National Electrical Code for complete current carrying capacity data on the various insulation...

Страница 18: ...h c t i w S n a F t a e H x u A t a e H m E k c e h C s p m a L g n i t a c i d n I 7 1 0 3 0 4 8 9 2 1 1 R 4 7 8 T 9 0 0 4 0 4 8 1 8 1 1 L 4 7 6 Q r e v o e g n a h c l a u n a M b l u b y r u c r e...

Страница 19: ...ion point in the unit and while the unit is operating at full load maximum amperage operating condition COMPRESSOR CUTOFF THERMOSTAT and OUTDOOR THERMOSTAT WIRING Heat pump compressor operation at out...

Страница 20: ...0 6 4 0 3 2 3 1 8 4 2 1 H P 5 1 0 3 2 1 B 1 8 4 2 1 H P 5 1 0 3 2 1 0 6 0 1 H P 0 2 5 1 0 3 2 1 C B 0 6 0 1 H P 8 1 5 1 0 6 4 0 3 2 3 TABLE 11 5 thru 10 KW l e d o M W K s t l o V e s a h P 2 4 2 1 1...

Страница 21: ...sors are wired identically internally As a result once the correct phasing is determined for a specific system or installation connecting properly phased power leads to the same Fusite terminals shoul...

Страница 22: ...nected to terminal 60 and reconnect to desired terminal Refer to Figure 12 The manufacturer s recommendation is for 60 minute defrost cycles There is a cycle speed up jumper on the control This can be...

Страница 23: ...o h s r o n e p o r o f k c e h C g n i d n i w r o t c a t n o c e c a l p e R r o t o m r o o d t u o n a F n u r t o n s e o d g n i t a e h r o g n i l o o c t s o r f e d g n i r u d t p e c x e...

Страница 24: ...0 8 4 0 9 4 0 0 5 5 8 9 6 5 4 8 2 5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 7 4 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4...

Страница 25: ...led on all units so that the system operating pressures can be observed Pressure tables can be found in Tables 16 through 23 in this manual covering all models on both cooling and heating cycles It is...

Страница 26: ...und the circumference to flow braze material completely around the joint Slowly move torch into Area 3 to draw braze material into joint See Figure 14 Do not overheat joint MIS 1179 FIGURE 14 BRAZINGD...

Страница 27: ...k c e h C d e e p s M F C h g i h t a s f f u p r o s t n u H g n i f f u p e c u d e r r e t l i f r o l e n a p g n i v o m e r s e o D n o i t c i t s e r e c u d e R w o l f r i a m u m i x a m e...

Страница 28: ...w s c a i r T r o f k c e h C y a l e r N O T P M Y S E R U D E C O R P E S U A C e s i o n e v i s s e c x E e s i o n r o t o m r o t c u d t e n i b a c e s i o n r i a s i t i f i e n i m r e t e...

Страница 29: ...7 2 3 2 1 8 2 5 2 3 8 1 7 2 5 8 0 9 2 7 8 9 0 3 9 8 8 2 3 1 9 8 4 3 3 9 7 6 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 3 8 0 2 2 5 8 0 4 2 7 8 0 6 2 9 8 0 8 2 1 9 0 0 3 3 9 0 2 3 5 9...

Страница 30: ...7 2 3 2 0 8 9 4 2 1 8 5 6 2 3 8 3 8 2 4 8 0 0 3 5 8 8 1 3 6 8 7 3 3 7 8 6 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 4 2 2 3 8 0 4 2 6 8 8 5 2 7 8 4 7 2 9 8 2 9 2 0 9 1 1 3 1 9...

Страница 31: ...g i H 8 7 3 1 2 0 8 8 2 2 1 8 3 4 2 3 8 0 6 2 4 8 7 7 2 5 8 5 9 2 7 8 5 1 3 8 8 4 3 3 0 9 5 5 3 B D g e d 5 8 B W g e d 2 7 e d i S w o L e d i S h g i H 1 8 0 2 2 3 8 6 3 2 4 8 2 5 2 6 8 9 6 2 7 8 7...

Страница 32: ...h g i H 2 8 8 0 2 4 8 4 2 2 5 8 9 3 2 6 8 6 5 2 7 8 3 7 2 8 8 1 9 2 0 9 8 0 3 0 9 7 2 3 1 9 6 4 3 8 4 2 1 H P B D g e d 5 7 B W g e d 2 6 e d i S w o L e d i S h g i H 2 7 3 0 2 4 7 1 5 2 6 7 0 3 2 7...

Страница 33: ......

Страница 34: ......

Страница 35: ......

Страница 36: ......

Страница 37: ......

Страница 38: ......

Страница 39: ......

Отзывы: