FIGURE 4
Electric Heat Clearance
J30A, J30L, J36A, J36L, J42A, J42L, J48A, J48L, J60A, J60L, J72A, J72L
WARNING
A
minimum
of 1/4" clearance must be maintained between the
supply air duct and combustible materials. This is required for the
first 3' of ducting.
It is important to insure that the 1/4" minimum spacing is maintained
at all points.
Failure to do this could result in overheating the combustible
material and may result in a fire causing damage, injury or death.
NOTE 1:
SIDE SECTION VIEW OF SUPPLY AIR
DUCT FOR WALL MOUNTED UNIT SHOWING 1/4"
CLEARANCE TO COMBUSTIBLE SURFACES.