background image

Manual 2100-597
Page

48 of 52

TROUBLESHOOTING INDOOR ECM™ BLOWER MOTORS

CAUTION:

Disconnect power from unit before removing or replacing
connectors, or servicing motor.  To avoid electric shock
from the motor’s capacitors, disconnect power and wait at
least 5 minutes before opening motor.

Symptom

Cause/Procedure

Motor rocks slightly

• 

This is normal start-up for ECM

when starting

Motor won’t start

• 

Check blower turns by hand

• No movement

• Check power at motor
• Check low voltage (24 Vac R to C) at motor
• Check low voltage connections
  (G, Y, W, R, C) at motor
• Check for unseated pins in connectors on
   motor harness
• Test with a temporary jumper between R - G
• Check motor for tight shaft
• Perform motor/control replacement check
• 

Perform Moisture Check

• Motor rocks,

• Check for loose or compliant motor mount

  but won’t start

• Make sure blower wheel is tight on shaft
• Perform motor/control replacement check

Motor oscillates up

• It is normal for motor to oscillate with no

load 

& down while being

  on shaft

tested off of blower

Motor starts, but
runs erratically

• Varies up and down

• Check line voltage for variation or “sag”

  or intermittent

• Check low voltage connections
  (G, Y, W, R, C) at motor, unseated pins in
  motor harness connectors
• Check “Bk” for erratic CFM command (in
   variable-speed applications)
• Check out system controls, Thermostat
• 

Perform Moisture Check

• “Hunts” or “puffs” at

• Does removing panel or filter reduce

  high CFM (speed)

  “puffing”?
 - Reduce restriction
 - Reduce max airflow

• Stays at low CFM

• Check low voltage (Thermostat) wires and

  despite system call

  connections

  for cool or heat CFM

• Verify fan is not in delay mode; wait until
   delay complete
• “R” missing/not connected at motor
• Perform motor/control replacement check

• Stays at high CFM

• “R” missing/not connected at motor
• Is fan in delay mode? - wait until delay time
  complete
• Perform motor/control replacement check

• Blower won’t shut off

• Current leakage from controls into G, Y or W?
  Check for Triac switched thermostat or solid-
  state relay

Excessive noise

• Determine if it’s air noise, cabinet, duct or
  motor noise; interview customer, if necessary

• Air noise

• High static creating high blower speed?
 - Is airflow set properly?
 - Does removing filter cause blower to slow
   down?  Check filter
 - Use low-pressure drop filter
 - Check/correct duct restrictions

Symptom

Cause/Procedure

• Noisy blower or cabinet

• 

Check for loose blower housing, panels, etc.

• High static creating high blower speed?

  - Check for air whistling through seams in
     ducts, cabinets or panels
  - Check for cabinet/duct deformation

• “Hunts” or “puffs” at

• 

Does removing panel or filter reduce

   high CFM (speed)

   “puffing”?
  - Reduce restriction
  - Reduce max. airflow

Evidence of Moisture

• Motor failure or

• Replace motor and 

Perform Moisture Check

  malfunction has occurred

  

and moisture is present

• Evidence of moisture

• 

Perform Moisture Check

  present inside air mover

Do

Don’t

• Check out motor, controls,

• 

Automatically assume the motor is bad.

  wiring and connections
  thoroughly before replacing
  motor
• Orient connectors down so • Locate connectors above 7 and 4 o’clock
  water can’t get in

   positions

 - Install “drip loops”
• Use authorized motor and

• Replace one motor or control model # with

  model #’s for replacement    another (unless an authorized replacement)
• Keep static pressure to a

• Use high pressure drop filters some have 

½"

  

minimum:

   H20 drop!

 - Recommend high

• Use restricted returns

   efficiency, low static filters
 - Recommend keeping filters
   clean.
 - Design ductwork for min.
   static, max. comfort
 - Look for and recommend
   ductwork improvement,
   where necessary

• Size the equipment wisely

• Oversize system, then compensate with low

    airflow

• Check orientation before

• Plug in power connector backwards

  inserting motor connectors

• Force plugs

Moisture Check

• Connectors are oriented “down” (or as recommended by equipment
  manufacturer)
• Arrange harness with “drip loop” under motor
• Is condensate drain plugged?
• Check for low airflow (too much latent capacity)
• Check for undercharged condition
• Check and plug leaks in return ducts, cabinet

Comfort Check

• Check proper airflow settings
• Low static pressure for lowest noise
• Set low continuous-fan CFM
• Use humidistat and 2-speed cooling units
• Use zoning controls designed for ECM that regulate CFM
• Thermostat in bad location?

Содержание I-TEC I30A1D

Страница 1: ...I42A1D I48A1D I60A1D I TEC SERIES PACKAGED AIR CONDITIONER INSTALLATION INSTRUCTIONS Bard Manufacturing Company Inc Bryan Ohio 43506 Since 1914 Moving ahead just as planned Manual 2100 597 Supersedes...

Страница 2: ...tor 48 49 Fan Blade Setting Dimensions 50 Refrigerant Charge 50 Figures Figure 1 Unit Dimensions 7 Figure 2A Unit on Lift 8 Figure 2B Unit Side 8 Wall Mounting Bracket Location 9 Bracket Wall Sect Vie...

Страница 3: ...mer Manual N Air Conditioning Low Pressure Low Velocity ACCA Manual D or Duct System Design Manual Q Winter and Summer Air Conditioning FOR MORE INFORMATION CONTACT THESE PUBLISHERS ACCA Air Condition...

Страница 4: ...ation made according to methods of Air Conditioning Contractors of America ACCA The air duct should be installed in accordance with the Standards of the National Fire Protection Systems of Other Than...

Страница 5: ...oated Alum Cond Coil 1 Phenolic Coated ID Coil 2 Phenolic Coated OD Coil 3 Phenolic Coated ID OD Coil CONTROLS X 24V Terminal Block Only w o CompleteStat 1 CompleteStat THO Temp Humidity Occupancy 2 C...

Страница 6: ...0 C 5 1 C 3 0 6 4 1 1 1 1 2 1 4 1 9 1 8 2 5 1 5 1 0 2 0 3 4 1 4 1 2 1 0 1 4 1 4 1 2 1 0 1 Z 0 A D 1 A 8 4 I 4 0 A 5 0 A 0 1 A 5 1 A 0 2 A 1 8 0 2 0 3 2 1 1 1 1 2 r o 1 2 r o 1 4 3 4 3 4 3 9 5 5 8 0 1...

Страница 7: ...5 47 3 46 1 8 With Sides Removed Vent Intake Disconnect Electrical Air Filters Vent Exhaust Door Latch Locking Filters Return Air 2 12 x 20 Door Latch Locking Air Filters 2 Washable Hinges 4 Lift Off...

Страница 8: ...tempt to do this manually Failure to do so could result in the unit tipping over causing bodily injury and or damage to the unit 7 The top section can be forked from either the RH or LH side See Figur...

Страница 9: ...a built in vertical adjustment to fit window sill heights from 31 34 inches If additional height is required two riser platform accessories are available The IRP3 increases the unit height by 3 inche...

Страница 10: ...nting holes Mounting holes 4 optional Unit Wall Opening Sleeve Mounting Hole Locations Optional Top Bracket 7 32 29 1 8 56 8 6 7 20 20 17 8 2 8 20 7 8 42 3 4 Min 16 8 11 16 15 20 94 34 Max 31 Min Cent...

Страница 11: ...e m i D X n o i s n e m i D Y n o i s n e m i D Z n o i s n e m i D Z B D A D 1 A 0 3 I 4 3 3 1 4 2 3 4 7 4 C D 1 A 0 3 I 4 3 3 1 4 2 3 4 7 4 B D A D 1 A 6 3 I 4 3 3 1 4 2 3 4 7 4 C D 1 A 6 3 I 4 3 3...

Страница 12: ...Manual 2100 597 Page 12 of 52 FIGURE 3 COMPRESSOR SHIPPING BOLTS FIGURE 4 REMOVAL OF AIR DUCT COMPRESSOR SHIPPING BOLT COMPRESSOR SHIPPING BOLT CRV ERV AIR DUCT...

Страница 13: ...NDED TO BOTTOM OF ROOF 9 7 MINIMUM OR FIXED CEILING FLOOR OR FIXED CEILING BOTTOM OF ROOF SUSPENDED CEILING 20 MINIMUM 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED MINIMUM 12 4 MI...

Страница 14: ...NDED TO BOTTOM OF ROOF 9 10 MINIMUM OR FIXED CEILING 3 RISER FIELD SUPPLIED DUCT TURNING VANES RECOMMENDED 12 MINIMUM 4 MINIMUM FROM TOP OF UNIT TO DUCT BOTTOM MIS 2989 B FLOOR OR FIXED CEILING BOTTOM...

Страница 15: ...XED CEILING 6 RISER 9 8 MINIMUM REQUIRED INSTALLATION HEIGHT BOTTOM OF ROOF FLOOR OR FIXED CEILING SUSPENDED CEILING MINIMUM 20 7 9 3 4 UNIT HEIGHT FIELD SUPPLIED DUCT MIS 2988 B TURNING VANES RECOMME...

Страница 16: ...DF Plenum Box mounts on top of the unit and has both vertically and horizontally adjustable louvers on the front discharge grille When used with a ducted supply an ICX28 Cabinet Extension may be used...

Страница 17: ...t about 12 inches in from the front on both the left and right side are drain holes in the bottom of the base These holes are covered with insulation and are not visible They are located very close to...

Страница 18: ...k bead to Apply liberal amount of caulk to back of flange before installing Use 4 1 1 2 Long Screws to Sleeve Attach Louver Grille to Outer Unit Fan Shroud to Outer Sleeve to Unit Back to Attach Inner...

Страница 19: ...Manual 2100 597 Page 19 of 52 INTERIOR FLOOR I TEC UNIT OUTSIDE WALL FILL INSULATION FILL INSULATION OUTDOOR GRILLE SIZE VARIES INSIDE WALL SLEEVE MIS 2928 A FIGURE 9B UNIT MOUNTING...

Страница 20: ...nformation and maximum fuse or HACR Type circuit breaker size Each unit is marked with a Minimum Circuit Ampacity This means that the field wiring used must be sized to carry that amount of current De...

Страница 21: ...e v o e g n a h c l a u n a M r o o t u A 7 6 0 3 0 4 8 Y L R D C L 0 4 W 2 T D C r o f D C L h t i w r o s n e S e d i x o i D n o b r a C s g n i d a e R r o s n e S O H T B 9 S C v n o C r o P H g...

Страница 22: ...e Term Strip R 3 SC W1 E A D L O B Y2 Y1 24V G COM W2 Completestat Model CS9B THO or Model CS9BE THO SC SC Thermostat W1 E A YO D L O B Y2 Y1 R G C W2 Bard 8403 060 2 1 Additional wire required for de...

Страница 23: ...L O B Y2 Y1 R G C W2 Bard 8403 060 BLACK WHITE ORANGE BROWN WHITE 1 Additional wire required for dehumidification models 2 Not needed below 15KW 3 to N C fire alarm circuit if emergency shutdown requ...

Страница 24: ...d jumper Remove jumper and connect 4 Connect to G terminal when thermostat has Occupancy Signal 6 without Occupance Signal is used Install a jumper between G and A only when thermostat 5 4 5 CRV Wirin...

Страница 25: ...ACK WHITE ORANGE 1 Additional wire required for dehumidification models 2 Not needed below 15KW 3 to N C fire alarm circuit if emergency shutdown required Factory installed jumper Remove jumper and co...

Страница 26: ...mper Remove jumper and connect 4 Connect to G terminal when thermostat has Occupancy Signal 6 without Occupance Signal is used Install a jumper between G and A only when thermostat 5 4 5 ERV Wiring Ha...

Страница 27: ...below 15KW to N C fire alarm circuit if emergency shutdown required Factory installed jumper Remove jumper and connect 2 3 2 4 Connect to G terminal when thermostat has Occupancy Signal without Occup...

Страница 28: ...ng multiple leaks and recharges R 410A refrigerant is close to being an azeotropic blend it behaves like a pure compound or single component refrigerant The remaining refrigerant charge in the system...

Страница 29: ...the power Since there is a 50 50 chance of connecting power in such a way as to cause rotation in the reverse direction verification of proper rotation must be made Verification of proper rotation di...

Страница 30: ...heat completes R Y1 circuit pulling in compressor contactor starting compressor and outdoor motor R G also make starting indoor blower motor HEATING STAGE 2 Circuit R Y1 Y2 makes at the thermostat en...

Страница 31: ...lectronic thermostat with auxiliary terminal to control the CRV based on daily programmed occupance periods Bard markets and recommends Bard Part 8403 060 programmable electronic thermostat 2 Use Bard...

Страница 32: ...OPTION INTAKE EXHAUST SPEEDS BROWN WHITE BLACK BLUE ORANGE NOM CFM BLACK BLUE WIRE COLOR SPEED RED WIRE WITH WHITE TRACE 300 375 450 525 LO MED LO MED HI HI RED Move brown white wire to corresponding...

Страница 33: ...CRV SPEED CHANGE TERMINAL ACCESS REMOVE 5 SCREWS FROM CRV DOOR TO ACCESS CRV COMPONENTS MIS 3023 CRV INTAKE BLOWER NOTE CRV EXHAUST BLOWER IS BEHIND INTAKE BLOWER BLOWER SPEED CONTROL LOCATION BLOWER...

Страница 34: ...erature freezing of moisture in the heat transfer wheel can occur Consult the factory if this possibility exists The I TEC ERV can be controlled in different ways It can be turned ON OFF with an occup...

Страница 35: ...re Then perform the following steps 1 Open front swinging doors of main unit by popping front door latches 2 Throw main power disconnect to the OFF position to eliminate risk of injury or death due to...

Страница 36: ...0 5 9 0 8 0 9 5 1 3 0 2 7 9 0 7 8 1 2 3 3 5 0 2 8 1 3 6 5 1 2 4 1 5 2 3 6 2 0 0 1 8 5 2 2 8 1 4 7 3 7 1 5 4 3 5 8 2 0 2 1 0 6 0 1 2 0 8 4 6 0 8 5 4 1 0 1 1 4 1 1 4 3 4 8 6 7 9 5 7 5 6 4 1 2 0 2 7 9 4...

Страница 37: ...ng blinks for the TEN COUNT of the FLOW RATE INDEX which then is immediately followed by fast blinks which indicate the second digit For example a Flow Index of 23 would be two long blinks followed by...

Страница 38: ...Manual 2100 597 Page 38 of 52 FIGURE 20 VENTILATION AIRFLOW DIAGRAM EXHAUST Return Air Indoor Air VENT Outdoor Air BLOWER BLOWER INTAKE Supply Air VENT SUPPLY BLOWER MIS 3024...

Страница 39: ...Page 39 of 52 FIGURE 21 ERV ACCESS ERV DOOR TO ACCESS ERV COMPONENTS ASSEMBLIES REMOVE 5 SCREWS FROM PANEL LOCATION MIS 3025 ERV CONTROL ERV CASSETTE NOTE ERV EXHAUST BLOWER IS BEHIND INTAKE BLOWER ER...

Страница 40: ...quipment damage Make sure all connections are in accordance with the job wiring diagram and in accordance with national and local electrical codes Use copper conductors only Use electrostatic discharg...

Страница 41: ...ure below Finish installing wiring the control Then refer to Figure 19 and the building ventilation specifications to decide what the maximum ventilation rate desired is and what the minimum maximum v...

Страница 42: ...2 low output range Sets the CO2 concentration for the lowest output 4 mA or 0 VDC Low limit 0 PPM Factory setting 0 PPM High limit 2000 5000 PPM depending on model COH CO2 high output range Sets the C...

Страница 43: ...to remove oils grease tars and dirt that can impede performance or generate odors Washing of the desiccant surfaces is required to remove contaminate buildups that can reduce adsorption of water molec...

Страница 44: ...based cleaners aromatic solvents temperatures in excess of 170 F or steam Damage to the wheel may result Do not disassemble and immerse the entire heat wheel in a soaking solution as bearing and othe...

Страница 45: ...5 5 0 4 6 3 5 1 5 0 2 5 4 1 5 0 5 8 2 0 9 4 0 9 5 4 1 0 0 2 6 4 5 5 8 4 4 4 5 5 3 4 5 9 2 2 4 7 7 0 1 4 8 9 8 9 3 7 5 7 8 3 2 5 6 7 3 3 8 5 6 3 8 4 5 5 3 5 4 5 4 3 4 7 5 3 3 4 3 6 2 3 3 2 7 1 3 0 4 8...

Страница 46: ...it is tight on the motor shaft Also ensure the motor is secure in its mounting system and the mounting system is secure to the unit c The Bard I TEC is equipped with a low ambient control pressure swi...

Страница 47: ...er that is a direct replacement for the failed motor USING THE WRONG MOTOR VOIDS ALL PRODUCT WARRANTIES AND MAY PRODUCE UNEXPECTED RESULTS Always mount the replacement motor and control according to t...

Страница 48: ...e if it s air noise cabinet duct or motor noise interview customer if necessary Air noise High static creating high blower speed Is airflow set properly Does removing filter cause blower to slow down...

Страница 49: ...Refer to the manufacturer s authorized replacement list USING THE WRONG CONTROL WILL RESULT IN IMPROPER OR NO BLOWER OPERATION Orient the control module so that the 3 wire motor plug can be inserted...

Страница 50: ...TOR MOTOR HALF R O T C E N N O C R E W O P R E D A E H B W P 0 5 4 9 0 5 3 1 P M A N I P n o i t p i r c s e D 1 r o f 2 n i P o t 1 n i P r e p m u J t u p n I e n i L C A V 0 2 1 y l n O 2 3 d n u o...

Страница 51: ...1 9 9 2 0 3 1 9 1 3 1 3 1 9 3 3 3 3 1 0 6 3 4 3 1 0 8 3 5 3 1 4 0 4 6 3 1 8 2 4 7 3 1 2 5 4 8 3 1 6 7 4 9 3 1 0 0 5 0 4 1 4 2 5 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 4 3 1 7 1 2 6 3 1 9 3 2 8...

Страница 52: ...1 4 7 2 6 3 1 4 9 2 8 3 1 5 1 3 9 3 1 5 3 3 1 4 1 6 5 3 2 4 1 9 7 3 3 4 1 2 0 4 4 4 1 6 2 4 5 4 1 9 4 4 6 4 1 2 7 4 7 4 1 6 9 4 B D 0 8 B W 7 6 e d i S w o L e d i S h g i H 0 4 1 5 9 1 1 4 1 6 1 2 3...

Отзывы: